PanelView 300 Micro Graphic Terminals

Image result for ALLEN BRADLEY PanelView 300

The Allen Bradley PanelView Standard 300 Micro Graphic Terminals have a 3 in. monochrome flat-panel display with a resolution of 128 x 64. The PanelView 300 terminal is only available with 24V DC input power. These terminals support operator input via keypad only. Their small, compact design and easy to use features make them very popular.

Technical Specifications

  • Display Options:
    • Color
    • Monochrome
    • Grayscale
    • 3 – 10inch display
  • Communication Options:
    • Point-to-point
    • Network
    • EtherNet/IP
  • Includes screen security and ATA PC memory card

PanelView 300 Startup Failure

If your PanelView 300 fails to startup properly, always check the power supply first. Ensure the terminal is receiving the correct voltage and that the wiring and connections to the power source are valid. In addition, you should also ensure the DC power positive and negative are attached to the proper terminals.

PanelView 300 Status Indicators

The status indicators are located on the back of your PanelView 300 terminal.  The COMM indicator is green and reflects communication. The FAULT indicator is red and reflects hardware faults. Upon startup, the fault indicator should be off and the comm indicator on. If the fault indicator flashes a few times at startup, this is not a concern. However, if both indicators are off you should check the power cable. See the table below to interpret the terminal’s indicator status:

Status Indicators – Ethernet/IP, ControlNet, DeviceNet Networks

IndicatorStatusMeaning
CommOnNormal operation
OffHardware failure
BlinkingFailed to establish communication
FaultOnHardware failure.
OffNormal operation
BlinkingApplication not loaded/application is corrupt

Status Indicators – Remote I/O

IndicatorStatusMeaning
CommOnNormal operation
OffCommunication non-functional
BlinkingFailed to establish communication, PLC may be in program mode
FaultOnFault Present –

Check baud rate and rack settings. Ensure proper connections from terminal to controller. Verify remote I/O is enabled.

OffNormal Operation
BlinkingApplication not loaded/application is corrupt

PanelView 300 Application Issues

Application Issues

IssuePossible CauseAction
Failed Application Download (Initial Attempt)Disconnected Communication CableCheck cable type and connection
Improper Computer COM Port SelectionEnsure you have the correct COM port number in PanelBuilder32 or WinPFT software
Communication Settings/Rate IncorrectEnsure computer and terminal share the same communication settings
Failed Application  Download (Subsequent Attempts)Communication Settings/Rate IncorrectEnsure computer and terminal share the same communication settings. Adjust settings in the Communication Setup screen
Application File Name Appears as *******Invalid ApplicationRedownload application
Unusable Application Due to ErrorDownload new application
Failed Application Transfer from Memory CardMemory card incorrectly installedReinstall, verify its installed correctly
Application to Large for Terminal MemoryReduce application size
Incorrect Data ChecksumEnsure memory card is properly seated. It is possible the application may be corrupt
File Format InvalidVerify file format (.PVA)
Failed Application Transfer to Memory CardMemory card incorrectly installedReinstall, verify its installed correctly
Memory Card May be Wire ProtectedChange memory card protection switch
Another File on the Memory CardErase/reformat card
Application to LargeReduce application size, erase/reformat card
Memory Card Format InvalidReplace/reformat card
Incorrect Data ChecksumEnsure card is installed correctly
Application Does Not ExistEnsure application exists
/