Hart Channels And Range
Transmitters that need smart config at the terminal block belong on the 1756-IF16H, a sixteen-channel analog input with a HART modem on every point. It drops into a 1756 chassis slot and reads differential current loops into the controller as clean data. Each channel carries its own HART modem, so a handheld configurator works right at the block without disturbing the others. The module is open style, IP20 and built for 0 to 60 °C control-room use.
Resolution And Scan
Sixteen differential inputs accept 0 to 20 mA and 4 to 20 mA, the ranges most analog transmitters use on a process skid. Resolution runs 16 to 21 bits via successive approximation, and the data reaches the processor as integers or IEEE 32-bit floating point. A dedicated HART modem per channel lets the smart instruments report alongside the loop value. Overvoltage protection is rated 8 V DC, which guards the card when a loop is wired live.
Wiring And Power
This module is the choice when every channel needs HART, because the per-channel modem beats a shared-HART card on a mixed instrument set. It is not for a voltage-only panel; the inputs are current loops, so a 0 to 10 V signal needs a different analog input. Scan time runs 11 to 328 ms by filter, stretching to about 1 s when all sixteen channels are HART enabled, so plan the update rate before committing. For a plain 4 to 20 mA rack without smart instruments a non-HART card costs less.
Land the field wiring on the 1756-TBCH or 1756-TBS6H removable terminal block and seat the module in any chassis slot. Backplane load is 200 mA at 5.1 VDC and 125 mA at 24 VDC, totaling 4.02 W, so add it to the rack budget. Keep the loops isolated at 50 V continuous from the backplane and ground the chassis to panel earth. Every card ships tested and cleaned with a 12 month warranty.
| Catalog number | 1756-IF16H |
| Manufacturer | Allen-Bradley |
| Product family | ControlLogix 1756 |
| Product type | PLC Module |
| Resolution | 16-21 Bits |
| Module Type | Analog Input module with HART protocol |
| No. of Inputs | 16 Differential input; Dedicated HART modem per channel |
| Analog signals | 0-20 mA and 4-20 mA |
| Conversion method | Successive approximation |
| Data Format | Integer mode (left justified, 2 s complement) IEEE 32-bit floating point |
| Module input scan time, min | 11…328 ms (filter dependent) |
| Module HART scan time | Estimate 1 s if all channels are HART enabled |
| Removable Terminal Block | 1756-TBCH; 1756-TBS6H |
| Backplane Current, 5.1VDC | 200 mA |
| Backplane Current, 24VDC | 125 mA |
| Total Backplane power | 4.02 W |
| Inputs | 16 Differential |
| Input Voltage Range | 0-20 or 4-20 milliamps |
| Overvoltage Protection | 8 Volts DC |
| Isolation Voltage | 50 Volts Continuous |
| Mounting | 1756 chassis slot (4, 7, 10, 13 or 17 slot chassis) |
| Enclosure rating | Open style, IP20 |
| Operating temperature | 0 to 60 °C (32 to 140 °F) |
| Storage temperature | -40 to 85 °C (-40 to 185 °F) |