Isolated Channels And Mode
Transmitters and sensors that need per-channel isolation land on the 1756-IF8I, an eight-point analog input with each channel isolated in one 1756 slot. It reads any mix of voltage or current signals, so a panel with both types fills one card. Sigma-delta conversion feeds IEEE 32-bit floating point data to the processor for clean reads. The module is open style, IP20 and rated for 0 to 60 °C control-room use.
Signal Range And Bits
Eight isolated points take any combination of voltage or current mode, with input ranges -10 to 10 V, 0 to 10 V, 0 to 5 V and 0 to 20 mA. Resolution runs 16 to 21 bits, set by the range, which is fine for tight process control. Conversion is sigma-delta, so the data is steady under a noisy field. Backplane current is 200 mA at 5.1 VDC, with 150 mA at 24 V in voltage or non-sourcing current mode and 400 mA in sourcing current mode when the channel powers the loop.
Power And Mount
This module is the choice when each signal needs its own isolation, such as a mixed voltage and current rack where a shared card invites cross-talk. It is not for a HART instrument set; those want a HART input, though the isolation here still protects the loops. Power dissipation runs 4.6 W in voltage mode, 5.1 W non-sourcing and 7.3 W sourcing, so size the rack supply for the mode in use. For a plain single-type rack a simpler card costs less; this one pays off on the mixed, isolated load.
Land the field wiring on the 36-pin connection channel by channel and seat the module in any chassis slot. Ground the chassis to panel earth and keep the sourcing-current loops clear of the backplane at 50 V isolation. Add the 200 mA at 5.1 VDC and the chosen 24 V draw, up to 7.3 W, to the rack budget. A 12 month warranty is included with the module from the dispatch date.
| Catalog number | 1756-IF8I |
| Manufacturer | Allen-Bradley |
| Product family | ControlLogix 1756 |
| Product type | PLC Module |
| Channels | 8 Isolated Channels |
| Module Type | Analog Input |
| I-O Ranges | 0-10 Volts |
| Inputs | 8-Points, Isolated , Any combination of Voltage or Current mode |
| Conversion Method | Sigma-Delta |
| Current Draw (5.1 Volts) | 200 milliamps |
| Data format | IEEE 32-bit floating point |
| Current Draw (24 Volts) | 150 or 400 milliamps |
| Input signal Range | -10…10V 0…10V 0…5V 0…20 mA |
| Resolution | 16-21 bits |
| Enclosure | Open |
| Backplane Current (5Volts) | 200 mA |
| Backplane Current (24Volts) | Voltage/Non-sourcing Current mode: 150 mA Sourcing Current mode: 400 mA (In Sourcing Current mode, the channel provides loop power.) |
| Power Dissipation (Max) | Voltage mode: 4.6 W Non-sourcing Current mode: 5.1 W Sourcing Current mode: 7.3 W |
| UPC | 10885630245406 |
| Mounting | 1756 chassis slot (4, 7, 10, 13 or 17 slot chassis) |
| Enclosure rating | Open style, IP20 |
| Operating temperature | 0 to 60 °C (32 to 140 °F) |
| Storage temperature | -40 to 85 °C (-40 to 185 °F) |
| Relative humidity | 5 to 95%, non-condensing |