2711E-UK14EK10 overview
The Allen-Bradley 2711E-UK14EK10 is an operator terminal for the PanelView platform, and the front bezel closes to IP65 on a sealed cutout.
This 2711E-UK14EK10 is an operator interface from the PanelView line. The panel replaces pushbuttons and lamps with screens, so recipe changes and fault messages can be handled without rewiring the door.
Screens are built in the configuration software and downloaded over the same link the terminal uses at runtime. The terminal holds the project in internal memory, so a replacement unit needs the file before it can go back into service — that file is usually the first thing to look for when an old panel dies. Contrast, backlight and touch calibration are set from the terminal menus and are not lost when the power is cycled.
Power for the terminal wants its own breaker, not a tap off the drive rail. Earth goes to the panel stud, and the screen of the communication cable is bonded at one end only. When a unit goes dark as a contactor drops out, suspect the supply before the panel: a dip resets the terminal and the project comes back blank.
These terminals sit on packaging lines, water plants, press cells and conveyor control desks. In most plants they are the only place where the fault text appears, which is why a dark screen stops production faster than a failed I/O card.
Before ordering, match the panel cutout, the supply and the network type against the existing unit. The mounting hardware is normally reusable, and the same project file can be downloaded to the replacement once the model matches.
Before fitting, confirm the supply and the wiring against the terminal markings on the new unit rather than against the old one, because revisions sometimes move a terminal. Allow the panel to cool and isolate the field supply first; on I/O and communication cards most damage happens during installation, not in service.
2711E-UK14EK10 specifications
| Model | 2711E-UK14EK10 |
| Manufacturer | Allen-Bradley |
| Product family | PanelView Standard 2711 |
| Product type | Operator Terminal |
| Display type | Monochrome or color TFT, size depending on catalog number |
| Operator input | Touch screen or keypad, depending on catalog number |
| Supply voltage | 24 VDC or 85 to 264 VAC, depending on catalog number |
| Enclosure rating | NEMA Type 12/4/4X front panel, IP65 |
| Operating temperature | 0 to 50 °C (32 to 122 °F) |
| Storage temperature | -25 to 70 °C (-13 to 158 °F) |
| Relative humidity | 5 to 95%, non-condensing |
| Certifications | CE, cULus |
| Condition | Tested and cleaned, in good working order |
| Warranty | 12 months |
| Place of origin | Made in USA |
| Stock status | In stock |
| Series | PanelView |
| Current rating | Not available |
| Communication interface | Not available |
2711E-UK14EK10 installation and sourcing
Units are tested on the bench before dispatch and covered by a 12 month warranty. If the machine is down, say so on the enquiry and we will check availability first and quote the freight with the goods.