The 1746-ITV16 is a 16-point DC input module for the SLC 500 family, taking source signals from 10 to 30 volts DC and built for fast response duties. Sixteen points on one card keeps slot count down on machines with a lot of sensors.
Fast response, wide window
The wide 10-30 V window means the card accepts signals from 12 V and 24 V control circuits alike, which helps when a machine mixes sensor generations after years of piecemeal upgrades. The fast-response design is the reason to pick this card over a general-purpose input: counters, encoder-style pulse pickups, and high-speed sensor streams need an input that reacts on the same scan the pulse arrives, not two scans later.
Key specifications
| Manufacturer | Allen-Bradley |
| Product family | SLC 500 (1746/1747) |
| Product type | PLC Module |
| Product Code | 1746-ITV16 |
| Voltage Range | 10-30 V DC (source) |
| Inputs | 16 |
| Intended Duty | Fast response applications |
| Place of Origin | Made in USA |
| Backplane Current (5 V DC) | Not available |
| Net weight | Not available |
| Mounting | 1746 chassis (4, 7, 10, 13 or 16 slot) |
| Enclosure rating | Open style, IP20 |
| Operating temperature | 0 to 60 °C (32 to 140 °F) |
| Storage temperature | -40 to 85 °C (-40 to 185 °F) |
| Relative humidity | 5 to 95%, non-condensing |
| Certifications | CE, cULus |
| Condition | Tested and cleaned, in good working order |
| Warranty | 12 months |
| Stock status | In stock |
Sensor compatibility quick check
Before wiring, sort the field sensors by output type: sourcing sensors feed this input directly, sinking sensors need the other input family or a relay interface. The 10-30 volt window accepts aged sensors whose supply has drifted, which is genuinely useful on machines that have grown organically for a decade, but a sensor running below ten volts will read as a permanent fault and deserves a supply fix, not a module change. Group fast-response points on this card and leave ordinary status inputs to a standard module, so scan behavior stays predictable. Note which points feed counters in the program comments, because the next programmer will look for exactly that.
Wiring notes
This is a sourcing arrangement, so sensors must deliver source signals to the input terminals; check your sensor output type before ordering, because a sinking sensor on a sourcing input is a classic no-work commissioning call. Keep the 24 V sensor supply separate from noisy load circuits, and land shields per your standard practice. For spare shelves, one ITV16 covers any SLC 500 rack running fast 24 V sensor duties.