Local I/O, Not Remote I/O
Bulletin 1771 offers more than one way to put I/O in a second chassis. Remote I/O uses an adapter and a communication link; local I/O uses an adapter that keeps the chassis on the processor’s parallel local bus. The 1771-ALX is the local I/O adapter, and the distinction matters at the point of order, because the two families are not interchangeable and the cabinets they serve look similar from the outside. A remote adapter in the same cabinet looks almost identical, and the two are told apart by number rather than by shape.
What Separates It
A local adapter has no link rate to set and no trunk to terminate, because the bus it serves is the same parallel bus the processor drives. What it does have is a position in the chain: the chassis it serves has to be addressed as part of the local bus, and the run back to the processor chassis has to be cabled and terminated as the bus requires. Where an installation has been converted from one arrangement to the other, the drawing is the only trustworthy record of what is actually fitted. The bus also has a length limit recorded on that drawing, and a chassis added at the far end may need the run re-checked before it will register.
Buying and Fitting Notes
Order by the full number and confirm the chassis type, since the marketing configuration for this family spans several chassis builds. On receipt, check the module for a bent backplane connector and for a faceplate that has been levered, and compare the address setting with the drawing before the chassis is powered. Fit it with the rack isolated, check the bus termination at the end of the chain, and record the setting inside the door. A local adapter is a small part in a large cabinet, and the wrong one is discovered only when the rack will not register. Our stock is tested and cleaned, in good working order, and every adapter carries a 12 month warranty.
| Model | 1771-ALX |
| Product Type | PLC-5 System module |
| Manufacturer | Allen-Bradley (Rockwell Automation) |
| Product Family | PLC-5 / Bulletin 1771 |
| Condition | Tested and cleaned, in good working order |
| Warranty | 12 month warranty |
| Official Description | PLC-5 Local I/O Adapter Module |
| Module Location | Leftmost slot in any 1771 I/O chassis |
| Power Dissipation | 6.3 W (max); 5.7 W (min) |
| Thermal Dissipation | 21.48 BTU/hr (max) |
| Backplane Voltage | 5 V DC (±5%) |
| Chassis Compatibility | 1771-A1B, -A2B, -A3B, -A4B, -AM1, -AM2, -PSC |
| Operating Temperature | 0 to 60 °C (32 to 140 °F) |
| Storage Temperature | -40 to 85 °C (-40 to 185 °F) |
| Relative Humidity | 5 to 95% without condensation |
| Conductor Size | 14 AWG (2 mm2) stranded maximum |
| Maximum Insulation Diameter | 3/64 in. (1.2 mm) |
| Backplane Interface | Parallel I/O backplane (1771 I/O chassis) |
| Compatible Controller | PLC-5 processors, 1785-L11B through 1785-L80E |
| Wiring Arm Screw Torque | 7 to 9 in-lb |
| Agency Certification | UL listed, CSA certified (Class I, Division 2, Groups A, B, C, D), CE marked |