One hundred thousand words of user memory, a redundant dual-media ControlNet channel and a hot-backup cartridge socket put the 1785-L80C15 at the top of the C-series. This PLC-5/80C accepts a 1785-CHBM ControlNet Hot Backup Cartridge, one per processor, so critical mills can run a synchronized standby behind a 128-entry I/O map. Two DH+/Remote I/O channels keep legacy trunks alive beside it. The unit ships tested and cleaned, in good working order.
Top C-Series Redundancy
The specification reads accordingly. User memory, max 100,000 words; total I/O, 3,072 any mix, 3,072 inputs and 3,072 outputs complementary. ControlNet runs at 5 Mbps, supporting 48 nodes per link without repeaters, 99 with them, a network update time of 2 to 100 ms, and 128 I/O map entries. Twenty-three remote rack addresses cover ninety-two remote chassis among 125 total. Backplane draw is 3.0 A, dissipating 15.8 W or 59 BTU/hr, and the module weighs 1.42 kg. Discrete scan runs 0.5 ms extended-local and 10 ms remote I/O at 57.6 kbps, 7 ms at 115.2 kbps, 3 ms at 230.4 kbps.
Map Entries And Node Counts
Choose this variant over the plain L80C when the ControlNet segment cannot tolerate a single processor failure and a 1785-CHBM-based standby is planned. The EEPROM rule holds here too: 1785-ME16 modules cannot pair with ControlNet controllers, so 1785-ME32, 1785-ME64 or 1785-M100 modules carry the backup. Programs beyond 100,000 words have no PLC-5 home, and Ethernet never attaches to these channels, so TCP/IP traffic needs other hardware.
Cartridge Battery And Slot
Installation follows family practice: left-most slot in a 1771-A1B, -A2B, -A3B, -A3B1 or -A4B chassis, keying between pins 40 and 42 and between 54 and 56, 2-slot, 1-slot or 1/2-slot addressing before wiring. Install the 1785-CHBM cartridge before commissioning the standby pair, check the chassis supply against the 3.0 A draw, and keep a 1770-XYC battery current. CSA Class I Division 2, UL and CE marks apply. A year-long warranty shields the purchase.
| Model | 1785-L80C15 |
| Manufacturer | Rockwell Automation / Allen-Bradley |
| Product Family | PLC-5 Programmable Controllers |
| Product Type | Programmable controller |
| Condition | Tested and cleaned, in good working order |
| Warranty | One year warranty |
| Processor Type | PLC-5/80C |
| User Memory, Max | 100,000 words |
| Total I/O, Max (any mix) | 3072 |
| Complementary I/O | 3072 in + 3072 out (complementary) |
| Communication Channels | 1 ControlNet (redundant, dual-media) and 2 DH+/Remote I/O (Adapter or Scanner) |
| Serial Port | 1, configurable for RS-232, RS-423 and RS-422A compatible |
| Max I/O Racks (rack addresses) | 23 remote |
| I/O Chassis, Total | 125 |
| I/O Chassis, Extended-local | 0 |
| I/O Chassis, Remote | 92 |
| Backplane Current Load | 3.0 A |
| Heat Dissipation, Max | 59 BTU/hr |
| Power Dissipation, Max | 15.8 W |
| Battery | 1770-XYC |
| Memory Modules (EEPROM backup) | 1785-ME32, 1785-ME64 (1785-M100 where supported) |
| Discrete I/O Scan | 0.5 ms extended-local; 10 ms remote I/O at 57.6 kbps, 7 ms at 115.2 kbps, 3 ms at 230.4 kbps |
| Hardware Addressing | 2-slot, 1-slot or 1/2-slot (any mix of 8-, 16- or 32-point modules) |
| Chassis Location | 1771-A1B, -A2B, -A3B, -A3B1 or -A4B chassis, left-most slot |
| Keying | Between pins 40 and 42, and 54 and 56 |
| Weight | 1.42 kg (3 lb 2 oz) |
| ControlNet I/O Map Entries | 128 |
| ControlNet Nodes | 48 per link without repeater, 99 with repeaters; 5 Mbps |
| Network Update Time | 2 to 100 ms (user selectable) |
| Backup Cartridge | 1785-CHBM ControlNet Hot Backup Cartridge (one per processor) |
| Memory Modules | 1785-ME32, 1785-ME64, 1785-M100 (1785-ME16 cannot be used with ControlNet controllers) |
| Operating Temperature | 0 to 60 °C (32 to 140 °F) |
| Storage Temperature | -40 to 85 °C (-40 to 185 °F) |
| Relative Humidity | 5 to 95% (without condensation) |
| Shock | 30 g operating, 50 g non-operating, peak acceleration for 11 ±1 ms |
| Vibration | 1 g @ 10 to 500 Hz, 0.012 inches peak-to-peak displacement |
| Agency Certification | CSA Class I Division 2 Groups A, B, C, D; UL listed; CE marked |