Isolated Output Points
Loop devices that cross-talk on a shared ground belong on the 1756-OF8I, an isolated analog output with eight channels in one 1756 slot. It drives each loop from its own terminals so a ground fault on one signal cannot reach the others. Current or voltage ranges are selected per channel, which keeps a mixed valve and drive set on a single card. The module is open style, IP20 and rated for 0 to 60 °C control-room use.
Range And Resolution
Eight isolated outputs cover 0 to 20 mA and 4 to 20 mA current, plus -10 to 10 V, 0 to 10 V and 0 to 5 V voltage, chosen per point. Resolution is 15 to 16 bits with IEEE 32-bit floating point data for the processor, converted by an R-Ladder DAC with no missing codes. Isolation stands at 50 V continuous between channels and backplane, so the loops stay separate under fault. Power dissipation is 6.5 W, drawn from the 24 VDC backplane at 400 mA.
Terminal And Fault Checks
This module is the choice when analog loops must not share a ground, such as valve positions and drive speeds in a noisy panel where a shared card invites cross-talk. It is not for a current-only rack where a cheaper non-isolated card would do. Open-circuit detection works on current loops and short-circuit detection on voltage, so the fault LEDs point to the right channel. For a small panel with one signal type a simpler output fits better; this one pays off on mixed, isolated loads.
Wire each loop to its own terminals on the 1756-TBNH or 1756-TBSH removable block, or the 1756-TBCH and 1756-TBS6H variant, and seat the module in any chassis slot. Ground the chassis to panel earth and keep the 24 VDC supply isolated from the backplane. Add the 400 mA at 24 VDC draw, 6.5 W, to the rack budget before the supply is sized. A 12 month warranty protects the module from the dispatch date.
| Catalog number | 1756-OF8I |
| Manufacturer | Allen-Bradley |
| Product family | ControlLogix 1756 |
| Product type | PLC Module |
| Outputs | 8 Current |
| Module Type | Isoloated Analog Output Module |
| Current Draw (24 Volts DC) | 400 milliamps |
| No. of Outputs | Eight (8) Current / Voltage |
| Power Dissipation | 6.5 Watts |
| Output Current Range | 0-20 mA; 4-20 mA |
| Output Range | 0-20 or 4-20 milliamps |
| Output Voltage Range | 10…10V; 0…10V; 0…5V |
| Resolution | 15 bits |
| esolution | 16-Bit |
| Data Format | IEEE 32-bit floating point |
| Removeable Terminal Block(s) | 1756-TBNH, 1756-TBSH |
| Conversion Method | R-Ladder DAC, monotonicity with no missing codes |
| Isolation Voltage | 50 Volts Continuous |
| Removable Terminal Block(s) | 1756-TBCH, 1756-TBS6H |
| Open circuit detection | Current only |
| Short circuit detection | Voltage only |
| Mounting | 1756 chassis slot (4, 7, 10, 13 or 17 slot chassis) |
| Enclosure rating | Open style, IP20 |
| Operating temperature | 0 to 60 °C (32 to 140 °F) |