When a ControlNet segment loses its processor, the whole scheduled I/O scheme stops until a matching unit is back in the rack. The 1785-L40C, a PLC-5/40C with a redundant ControlNet channel and two DH+/Remote I/O channels, is the like-for-like replacement many plants stock for exactly that event. It brings 48,000 words of user memory and 2,048 I/O points, so existing programs and rack maps carry over untouched. Boards are tested and cleaned, in good working order.
Redundant ControlNet Channel
The numbers behind that continuity are specific. User memory, max 48,000 words; total I/O, 2,048 any mix, 2,048 inputs and 2,048 outputs complementary. The ControlNet channel is redundant and runs at 5 Mbps, scheduling 96 I/O map entries with a network update time selectable from 2 to 100 ms; 48 nodes work per link without repeaters, 99 with them. Fifteen remote rack addresses span sixty remote chassis out of 125 total. Backplane draw is 3.3 A, dissipating 15.8 W or 59 BTU/hr.
Map Entries And Modules
Two compatibility points decide the purchase. ControlNet controllers cannot pair with 1785-ME16 EEPROM modules, so program backups belong on a 1785-ME32 or 1785-ME64 module. The 96-entry map sits above the 64 entries of the L20C15, which matters when a migrated schedule keeps growing; beyond 96 entries, the L80C and its 128 entries are the next stop. The two DH+/Remote I/O channels and the ControlNet channel remain separate networks, neither converting to Ethernet.
Slot Fit And Verification
Fit the module into the left-most slot of a 1771-A1B, -A2B, -A3B, -A3B1 or -A4B chassis, guided by keying between pins 40 and 42 and between 54 and 56, and set 2-slot, 1-slot or 1/2-slot addressing before wiring the racks. Keep a 1770-XYC battery fresh, verify the chassis supply against the 3.3 A draw, and check that CSA Class I Division 2, UL and CE marks match plant requirements. Buyers receive a one-year warranty on the unit.
| Model | 1785-L40C |
| Manufacturer | Rockwell Automation / Allen-Bradley |
| Product Family | PLC-5 Programmable Controllers |
| Product Type | Programmable controller |
| Condition | Tested and cleaned, in good working order |
| Warranty | One year warranty |
| Processor Type | PLC-5/40C |
| User Memory, Max | 48,000 words |
| Total I/O, Max (any mix) | 2048 |
| Complementary I/O | 2048 in + 2048 out (complementary) |
| Communication Channels | 1 ControlNet (redundant) and 2 DH+/Remote I/O (Adapter or Scanner) |
| Serial Port | 1, configurable for RS-232, RS-423 and RS-422A compatible |
| Max I/O Racks (rack addresses) | 15 remote |
| I/O Chassis, Total | 125 |
| I/O Chassis, Extended-local | 0 |
| I/O Chassis, Remote | 60 |
| Backplane Current Load | 3.3 A |
| Heat Dissipation, Max | 59 BTU/hr |
| Power Dissipation, Max | 15.8 W |
| Battery | 1770-XYC |
| Memory Modules (EEPROM backup) | 1785-ME32, 1785-ME64 (1785-M100 where supported) |
| Discrete I/O Scan | 0.5 ms extended-local; 10 ms remote I/O at 57.6 kbps, 7 ms at 115.2 kbps, 3 ms at 230.4 kbps |
| Hardware Addressing | 2-slot, 1-slot or 1/2-slot (any mix of 8-, 16- or 32-point modules) |
| Chassis Location | 1771-A1B, -A2B, -A3B, -A3B1 or -A4B chassis, left-most slot |
| Keying | Between pins 40 and 42, and 54 and 56 |
| Weight | 1.42 kg (3 lb 2 oz) |
| ControlNet I/O Map Entries | 96 |
| ControlNet Nodes | 48 per link without repeater, 99 with repeaters; 5 Mbps |
| Network Update Time | 2 to 100 ms (user selectable) |
| Memory Modules | 1785-ME32, 1785-ME64 (1785-ME16 cannot be used with ControlNet controllers) |
| Operating Temperature | 0 to 60 °C (32 to 140 °F) |
| Storage Temperature | -40 to 85 °C (-40 to 185 °F) |
| Relative Humidity | 5 to 95% (without condensation) |
| Shock | 30 g operating, 50 g non-operating, peak acceleration for 11 ±1 ms |
| Vibration | 1 g @ 10 to 500 Hz, 0.012 inches peak-to-peak displacement |
| Agency Certification | CSA Class I Division 2 Groups A, B, C, D; UL listed; CE marked |