Adding EtherNet/IP to a PowerFlex 4, 40 or 400 is a card-into-slot job, and the 22-COMM-E is that card. It occupies the drive communication port, presents one RJ45 to the network, and carries drive status and control over the same connection, so no separate gateway or hardwired status wiring is needed. For plants standardising on Ethernet, it turns three separate drive families into one networked population. The adapter draws its power from the host drive, which removes the external supply run that many retrofit cards otherwise demand.
Network Capacity and Timing Figures
Data rates cover 10 Mbps and 100 Mbps in both full and half duplex. The card supports up to 30 TCP connections, a 5 ms minimum RPI, and packet rates to 400 total I/O packets per second, split 200 in and 200 out. Four status LEDs on the face give a quick read on link and activity during commissioning. Those figures cover drive control and status across a plant network without touching the motor wiring or the drive’s own terminal block.
Power Draw, Ports and Physical Fit
Power consumption is 350 mA at 5V DC, supplied by the host drive or a DPI external communications kit, so one less point to check during troubleshooting. The DSI connector carries 20 pins, and the body measures 19 mm high by 86 mm long by 78.5 mm wide, so cabinet fit is never the obstacle. Fitting comes down to seating the card, terminating the RJ45 at the switch and assigning the address ahead of energising.
Ambient Limits and Regulatory Coverage
The operating window runs -10 to 50 °C (14 to 122 °F) with 5 to 95% non-condensing humidity, comfortable inside most drive cabinets, and storage tolerance reaches -40 to 85 °C. Set the node address before the first power-up, since the drive will not appear on the network until addressing is done. Compliance spans UL508C, CAN/CSA C22.2 No. 14-M91, EN50178 and EN61800-3.Every drive passes a bench check before dispatch under a 12 month warranty.
| Catalog number | 22-COMM-E |
| Manufacturer | Allen-Bradley |
| Product family | PowerFlex AC drive |
| Product type | AC Drive |
| Description | Ethernet I/P communication adapter |
| Compatible Drives | PowerFlex 4, 40 and 400 |
| Communication Port | One (1) RJ45 |
| Communication Protocol | Ethernet I/P |
| Data Rate | 10 Mbps Full Duplex, 10 Mbps Half Duplex, 100 Mbps Full Duplex, and 100 Mbps Half Duplex. |
| No. of TCP connections | 30 TCP connections |
| RPI | 5 ms minimum |
| Packet Rate | Up to 400 total I/O packets per second (200 in and 200 out) |
| Drive Power consumption | 350 mA at 5V DC supplied by the host (drive or DPI External Comms Kit) |
| Operating Temperature | `-10…50 °C (14…122 °F) |
| Storage | -40…85 °C (-40…185 °F) |
| Relative Humidity | 5…95% non-condensing |
| Dimensions | Height 19 mm (0.75 inches) Length 86 mm (3.39 inches) Width 78.5 mm (3.09 inches) |
| Regulatory Compliance | UL508C, CAN / CSA C22.2 No. 14-M91, EN50178 and EN61800-3, EN61800-3 specifications |
| Status Indicators | 4 LEDs |
| Connection | Ethernet/IP |
| DSI Connector | 20 pins |
| Output frequency | 0 to 400 Hz |
| Enclosure rating | IP20 / NEMA 1 standard |
| Communication | EtherNet/IP, DeviceNet, ControlNet or Modbus options |