140CPU43412U – SCHNEIDER ELECTRIC – Modicon QUANTUM 434 PLC

140CPU43412U

140CPU43412U

Unity processor Modicon Quantum – 1056 kB – 66 MHz

TELEMECANIQUE 140CPU43412U PROGRAMMABLE LOGIC CONTROLLER PROCESSOR (CPU) (MODICON QUANTUM), 800KB, 66MHZ, (2) RS 232 MODBUS/ASCII – (1) MODBUS PLUS

140CPU43412U Specifications

 Application  MODICON QUANTUM AUTOMATION PLATFORM
 Brand Name  Schneider Electric
 Catalog Number  140CPU43412U
 Data Memory  INTERNAL RAM 1056 KB
 Interface  2 MODBUS WITH-1 MODBUS PLUS WITH
 PDW CAPACITY  66MHZ
 Program Memory  INTERNAL RAM 1056 KB
 Special Features  (2) RS 232 MODBUS/ASCII – (1) MODBUS PLUS
 Sub Brand  MODICON QUANTUM AUTOMATION PLATFORM
 Type  2 MODBUS WITH-1 MODBUS PLUS WITH,UNITY PROCESSOR
 United Item Number  68042

MORE :Characteristics

Complementary
 
clock frequency
66 MHz
number of slots
6
4
10
16
2
number of racks
2 – local rack(s)
number of distributed I/O station
63 station(s) – 1 rack(s) – 3 Modbus Plus network(s)
number of remote I/O station
31 – 2 S908 remote I/O rack(s)
0 – 0 ethernet remote I/O rack(s)
discrete I/O number
8000 inputs, 8000 outputs – distributed – per network Modbus Plus
Unlimited (26 slots max) – local
31744 inputs, 31744 outputs – remote
analogue I/O number
Unlimited (26 slots max) – local
1984 inputs,1984 outputs – S908 remote I/O
500 inputs, 500 outputs – distributed – per network Modbus Plus
application specific I/O
Serial link
Accurate time stamping
High-speed interrupt inputs
Counter
number of optional modules
6 ( Ethernet, Modbus, Modbus Plus, Profibus DP, Sy/Max)
maximum number of connections
2 ( AS-Interface) – distributed
2 ( Modbus) – RS232/485 Modbus/ASCII
4 ( AS-Interface) – remote
6 ( Ethernet TCP/IP) – local
6 ( Modbus Plus) – local
6 ( Profibus DP) – local
integrated connection type
1 Modbus Plus with
2 Modbus with
checks
Process control
memory description
Internal RAM 1056 kB
switch function
Key switch memory start/stop memory protection
Slide switch communication port : ASCII/RTU/Memory
application structure
1 cyclic/periodic master task –
1 periodic fast task –
16 timer interrupt tasks –
64 I/O interrupt tasks –
64 interrupt tasks –
No auxiliary task –
execution time per instruction
0.1…0.27 µs floating points
0.1…0.27 µs on fixed-point arithmetic
0.12…0.585 µs Boolean
0.12…0.585 µs on word
number of instructions per ms
1.86 Kinst/ms if 100 % Boolean
2.49 Kinst/ms if 65 % Boolean and 35 % numerical
system overhead
1 ms – master task
0.2 ms – fast task
bus current requirement
1800 mA
local signalling
1 LED green communications are active on the Modbus Plus port (Modbus Plus)
1 LED green communications are active on the Modbus port (Modbus)
1 LED green CPU has been started and is solving logic (RUN)
1 LED green CPU has passed the power-up diagnostic tests (READY)
1 LED orange write-protected memory (memory port)
1 LED red battery needs replacing or is not present (BAT LOW)
1 LED red communications error on the Modbus Plus port (ERROR A)
electrical connection
1 female connector, connector type: SUB-D 9 for connecting to the Modbus Plus network
2 female connectors, connector type: SUB-D 9 for connecting to the Modbus bus
Main
range of product
Modicon Quantum automation platform
product or component type
Unity processor
Environment
 
product certifications
CSA
UL
CE
standards
HazLoc
Ordering and shipping details
 
Category
18150 – QUANTUM CONTROLLERS,HSBY,COMM.
Discount Schedule
PC21
GTIN
00785901421078
Nbr. of units in pkg.
1
Package weight(Lbs)
1.3500000000000001
Returnability
Y
Country of origin
FR
Offer Sustainability
 
Sustainable offer status
Green Premium product
RoHS (date code: YYWW)
Compliant  – since  0948  –  Schneider Electric declaration of conformity Schneider Electric declaration of conformity
REACh
Reference not containing SVHC above the threshold
Product environmental profile
Available
Product end of life instructions
Available
Contractual warranty
 
Warranty period
18 months

140CPU43412U Technical FAQs

1、Is function 15 for the MBP_MSTR block supported with a 140CPU43412U PLC?

Yes.
MBP_MSTR function code 15 has the following requirements at minimum;
NOE77101 version 5.0
NOE77111 version 5.0
Unity Quantum CPU (includes 534 and 434) Exec firmware version 3.0
Unity 6.0
The CPU native Ethernet port or MB+ ports do not support this function, NOE only.

2、What is the replacement for the 140CPU43412A?

The replacement is the 140CPU43412U.

3、Can I create a Quantum Hot Standby configuration running one 140CPU53414A PLC with Unity firmware and one with NxT firmware?

No. When using an NxT configuration in hot standby, both PLCs must have NxT firmware. When using a Unity Quantum hot standby configuration, only specific hot standby controllers can be used. The 140CPU43412A and 140CPU53414A PLCs are not supported in Unity Hot Standby configurations.

4、Which Quantum PLCs allow the use of an Aux task in Unity?

The 140CPU65150, 140CPU65160, and 140CPU67160 allow the use of Aux tasks numbered 0 thru 3. The 140CPU31110, 140CPU43412A, and 140CPU53414A will only allow the use of a Fast and a Mast task.

5、Which Quantum controllers support Concept IEC Hot Standby?

The following Quantum controllers support Concept IEC HSBY:
140CPU43412
140CPU43412A
140CPU53414
140CPU53414A
140CPU53414B

Dimensions Drawings

Racks for Modules Mounting
Dimensions of Modules and Racks