ALLEN BRADLEY Drive – 1305 AC Drive

The 1305 Adjustable Frequency AC Drive is a variable speed drive designed to control the speed of three-phase AC induction motors in a variety of demanding applications where flexibility, performance and ease of use are essential. The 1305 Adjustable Frequency AC drive is available with ratings 0.37 to 4 kW (0.5 to 5HP) at 380-460V and 0.37to 2.2 kW (0.5 to 3HP) at 200-230V.

1305 AC Drives

Allen-Bradley 1305 AC Drives

Technical Specifications

  • 1305 Drives horsepower ratings range from 0.5-3HP or 0.5-5HP
  • Input-voltage range from 200-230V or 380-460V
  • Output voltage adjustable from 0V to input voltage for all 1305 Drives
  • Operational range from 180-265V or 340-500V
  • Typical efficiency for all 1305 Drives is 97.5%
  • Output frequency 0.00 to 400.00Hz programable for all 1305 Drives
  • SCANport Load maximum is 205 mA for all adapters combined

Troubleshooting your 1305 AC Drive

1305 Fault Descriptions

Name and Fault NumberDescriptionSuggested Action
Diag C Lim Fault – F36Drive ouptut current exceeded the software [Current Limit] and the [Cur Lim Trip En] parameter was enabled.Check programming of [Curr Lim Trip En] parameter. Check for excess load, improper DC boost setting, DC brake volts set too high or other causes of excess current.
Drive → HIMThe check sum read from the HIM’s EEPROM does not match the check sum calculated from the EEPROM data.Repeat operation. Replace HIM.
Drive Reset Fault – F22May occur on power-up. Caused by having the Start (or Run) Input closed, witht eh Stop input open and [Run On Power Up] = DisabledCheck stop connection located at TB2, terminal 8.
EEprom Fault – F32EEPROM has invalid data or cannot be programmed to valid dataCheck cable connection from main control board to power board. Reset to Default Parameters and Cycle power.
Hz Err Fault – F29No valid operating frequency. Possible causes:

1. [Maximum Frequency] is less than [Minimum Freq]

2. Skip frequencies and skip bandwith eliminate all operating frequencies.

3. 4-20mA input signal speed reference has been lost or is out of range and [4-20mA Loss Sel] has “Stop-Fault” selected.

1. Check [Minimum Freq] and [Maximum Freq] parameters.

2. Check [Skip Freq 1], [Skip Freq 2], [Skip Freq 3] and [Skip Freq Band] parameters.

3. Check for broken wires, loose connections, or transducer loss at 4-20mA input, TB2.

Hz Sel Fault – F30An unconnected adapter has been selected as the active frequency source.Connect proper adapter or change active frequency source.
HIM→DriveError 1 – Check sum read from the HIM’s EEPROM does not match check sum calculated from the EEPROM data.

Error 2 – The number of parameters in saved profile does not equal master number.

Error 3 – Download was attempted to a different type drive (i.e. 1336 -> 1305).

Error 4 – Saved data for parameter not correct for new drive.

Error 5 – Drive is running while attempting download

Repeat operation. Old profile corrupt. Save a new profile. Repeat operation.

The last parameter programmed will be displayed on the top line. Verify that all parameters have been programmed. If not, manually program any remaining parameters.

Download can only occur with the same type of drive.

Capabilities of drive are different than the master drive. Press Enter to continue download. when download is complete, manually program the parameter where the error occured.

Stop drive, then re-run download.

IPM Current Fault – F44The internal power module overcurrent limit has been exceeded.Inspect for short at the drive output or excessive load conditions on the motor, especially cable capacitance to ground.
IPM Overtemp Fault – F45The internal power module thermal limit has been exceeded.Inspect for blocked or contaminated heat sink fins. Inspect for proper mounting and spacing. Inspect to ensure that the ambient temperature limit has not been exceeded.
Max Retries Fault – F33Drive unsuccessfully attempted to reset a fault and resume running for the preset number of [Reset/Run Tries].Inspect fault buffer for fault code requiring reset. Correct the cause of the fault and manually clear by cycling the stop command or cycling power.
Motor Mode Fault – F24Internal errorReset your drive to the factory default settings.
Motor Stall Fault – F6The motor has stalledIf the motor is drawing excessive current, the motor load is excessive and will not allow the drive to accelerate to set speed. A longer acceleration tiime or a lighter load may be required.
Neg Slope Fault – F35Drive software detected a portion of the volts/Hertz curve with a negative slopeInspect drive programming.

1. [Base Voltage] parameter must be greater than 1.5 X [Start Boost]

Network Error*Network Error 0 – Error 6 Scanport Error

Network Error 7 – Error 9 Communications Error

1. Pres the “UP” or “DOWN” key to clear the message from the HIM display.

2. Unplug the HIM from the cable or drive, then reconnect it.

3. Check for external noise sources.

Op Error Fault – F11[Motor Type] is set to “Sync PM” and [Stop Mode] is set to “DC Brake”Adjust one of these parameters. DC Braking cannot be used with a synchronous motor.
Open Pot Fault – F9An external pot is connected and the ground lead of the pot is disconnected, creating a potential drive overspeed hazard.Check the external potentiometer circuit at TB2, terminals 1, 2, and 3 for a disconnected current.
Overcurrent Fault – F12Overcurrent is detected in overcurrent hardware trip circuit.Check for a short circuit at the drive output or excessive load conditions at the motor.
Overload Fault – F7Internal electronic overload trip.Excessive motor load. Reduce so that the drive output current does not exceed the % of current set by the [Overload Current] parameter. Reduce [Start Boost] if applicable. Change [Cable Length] to “Long” if applicable.
Overspeed Fault – F25Internal error.Reset your drive to the factory default settings.
Overtemperature Fault – F8Temperature sensor detects excessive heat.Inspect for blocked or contaminated heat sink fins. Check for proper mounting and spacing. Inspect to ensure that the ambient temperature limit has not been exceeded.
Overvolt Fault – F5DC bus voltage exceeded maximum valueCheck the AC line for high line voltage or transient conditions. Bus overvoltage can also be caused by motor reeneration. Extend the deceleration time or instal dynamic brake option.
Phase U Fault – F38A phase to ground default has been detected between the drive and motor in this phase.Inspect the wiring between the drive and motor. Check the motor for grounded phase.
Phase V Fault – F39A phase to ground fault has been detected between the drive and motor in this phase.Inspect the wiring between the drive and motor. Check motor for grounded phase.
Phase W Fault – F40A phase to ground fault has been detected between the drive and motor in this phase.Inspect the wiring between the drive and motor. Check motor for grounded phase.
Pin ID ErrorCommunication Hardware problem.1. Unplug the HIM from the cable or drive and reconnect it.

2. Replace the Communication cable.

Power Loss Fault – F3DC bus voltage remained below 85% of nominal for longer than 0.500 seconds. [Line Loss Fault] paramater is set to “F03 Enable”Monitor the incoming AC line for low voltage or line power interruption.
Power Mode Fault – F26Internal errorReset your drive to the factory default settings.
Power Test Fault – F46Fault detected during initial start-up sequence.Inspect drive wiring. Inspect motor wiring. Reset your drive to the factory default settings.
Reprogram Fault – F48May occur when drive parametersare reset to default settings.Clear fault message.
Run Boost Fault – F34An attempt has been made to set the [Run Boost] parameter to a value greater than the [Start Boost] parameter.Verify that the parameter has been programmed correctly.
Serial Fault – F10An active local bus adapter is disconnected while it possesses control of a local bus function.Inspect for breaks in communications line.
Undervolt Fault – F4DC Bus voltage fell below the minimum value. [Line Loss Fault] parameter is programmed to “U Volt Run”Monitor the incoming AC line for low voltage or line power interruption.
UV Short Fault – F41Excessive current has been detected between these two drive output terminals.Inspect the motor and external wiring to the drive output terminals for a shorted condition.
UW Short Fault – F42Excessive current has been detected between these two drive output terminals.Check the motor and external wiring to the drive output terminals for a shorted condition.
VW Short Fault – F43Excessive current has been detected between these two drive output terminals.Check the motor and external wiring to the drive output terminals for a shorted condition.

ALLEN BRADLEY 1305 AC Drive Product Selection

1305 AC DrivesDescription
1305-AA02AAllen Bradley-DRIVE .5HP 3-PH 230VAC OUT 2.3AMP AB
1305-AA02A-HA11305-AA02A-HA1 1305 AC Drives with IP 30 (NEMA Type 1) enclosure, 200-240V, Single Phase or 200-230V…
1305-AA02A-HA21305-AA02A-HA2 1305 AC Drives with IP 30 (NEMA Type 1) enclosure, 200-240V, Single Phase or 200-230V…
1305-AA02A-HAP1305-AA02A-HAP 1305 AC Drives with IP 30 (NEMA Type 1) enclosure, 200-240V, Single Phase or 200-230V…
1305-AA03AAllen Bradley-DRIVE .5HP 3-PH 230VAC OUT 2.3AMP AB
1305-AA03A-HA11305-AA03A-HA1 1305 AC Drives with IP 30 (NEMA Type 1) enclosure, 200-240V, Single Phase or 200-230V…
1305-AA03A-HA21305-AA03A-HA2 1305 AC Drives with IP 30 (NEMA Type 1) enclosure, 200-240V, Single Phase or 200-230V…
1305-AA03A-HAP1305-AA03A-HAP 1305 AC Drives with IP 30 (NEMA Type 1) enclosure, 200-240V, Single Phase or 200-230V…
1305-AA04AAllen Bradley-DRIVE .5HP 3-PH 230VAC OUT 2.3AMP AB
1305-AA04A-FR1305-AA04A-FR 1305 AC Drives with IP 30 (NEMA Type 1) enclosure, 200-240V, Single Phase or 200-230V …
1305-AA04A-HA11305-AA04A-HA1 1305 AC Drives with IP 30 (NEMA Type 1) enclosure, 200-240V, Single Phase or 200-230V…
1305-AA04A-HA21305-AA04A-HA2 1305 AC Drives with IP 30 (NEMA Type 1) enclosure, 200-240V, Single Phase or 200-230V…
1305-AA04A-HAP1305-AA04A-HAP 1305 AC Drives with IP 30 (NEMA Type 1) enclosure, 200-240V, Single Phase or 200-230V…
1305-AA08AAllen Bradley-DRIVE .5HP 3-PH 230VAC OUT 2.3AMP AB
1305-AA08A-FRAllen Bradley-DRIVE .5HP 3-PH 230VAC OUT 2.3AMP AB
1305-AA08A-HA11305-AA08A-HA1 1305 AC Drives with IP 30 (NEMA Type 1) enclosure, 200-240V, Single Phase or 200-230V…
1305-AA08A-HA21305-AA08A-HA2 1305 AC Drives with IP 30 (NEMA Type 1) enclosure, 200-240V, Single Phase or 200-230V…
1305-AA08A-HAP1305-AA08A-HAP 1305 AC Drives with IP 30 (NEMA Type 1) enclosure, 200-240V, Single Phase or 200-230V…
1305-AA12AAllen Bradley-DRIVE .5HP 3-PH 230VAC OUT 2.3AMP AB
1305-AA12A-HA11305-AA12A-HA1 1305 AC Drives with IP 30 (NEMA Type 1) enclosure, 200-240V, Single Phase or 200-230V…
1305-AA12A-HA21305-AA12A-HA2 1305 AC Drives with IP 30 (NEMA Type 1) enclosure, 200-240V, Single Phase or 200-230V…
1305-AA12A-HAP1305-AA12A-HAP 1305 AC Drives with IP 30 (NEMA Type 1) enclosure, 200-240V, Single Phase or 200-230V…
1305-BA01AAllen Bradley-DRIVE .5HP 3-PH 230VAC OUT 2.3AMP AB
1305-BA01A-DEAllen Bradley-DRIVE .5HP 3-PH 230VAC OUT 2.3AMP AB
1305-BA01A-HA11305-BA01A-HA1 1305 AC Drives with IP 30 (NEMA Type 1) enclosure, 380-460V, Three Phase rating and H…
1305-BA01A-HA21305-BA01A-HA2 1305 AC Drives with IP 30 (NEMA Type 1) enclosure, 380-460V, Three Phase rating and H…
1305-BA01A-HAP1305-BA01A-HAP 1305 AC Drives with IP 30 (NEMA Type 1) enclosure, 380-460V, Three Phase rating and P…
1305-BA01A-ITAllen Bradley-DRIVE .5HP 3-PH 230VAC OUT 2.3AMP AB
1305-BA02AAllen Bradley-DRIVE .5HP 3-PH 230VAC OUT 2.3AMP AB
1305-BA02A-DEAllen Bradley-DRIVE .5HP 3-PH 230VAC OUT 2.3AMP AB
1305-BA02A-HA11305-BA02A-HA1 1305 AC Drives with IP 30 (NEMA Type 1) enclosure, 380-460V, Three Phase rating and H…
1305-BA02A-HA21305-BA02A-HA2 1305 AC Drives with IP 30 (NEMA Type 1) enclosure, 380-460V, Three Phase rating and H…
1305-BA02A-HAP1305-BA02A-HAP 1305 AC Drives with IP 30 (NEMA Type 1) enclosure, 380-460V, Three Phase rating and P…
1305-BA03AAllen Bradley-DRIVE .5HP 3-PH 230VAC OUT 2.3AMP AB
1305-BA03A-DEAllen Bradley-DRIVE .5HP 3-PH 230VAC OUT 2.3AMP AB
1305-BA03A-FRAllen Bradley-DRIVE .5HP 3-PH 230VAC OUT 2.3AMP AB
1305-BA03A-HA11305-BA03A-HA1 1305 AC Drives with IP 30 (NEMA Type 1) enclosure, 380-460V, Three Phase rating and H…
1305-BA03A-HA21305-BA03A-HA2 1305 AC Drives with IP 30 (NEMA Type 1) enclosure, 380-460V, Three Phase rating and H…
1305-BA03A-HAP1305-BA03A-HAP 1305 AC Drives with IP 30 (NEMA Type 1) enclosure, 380-460V, Three Phase rating and P…
1305-BA04AAllen Bradley-DRIVE .5HP 3-PH 230VAC OUT 2.3AMP AB
1305-BA04A-DEAllen Bradley-DRIVE .5HP 3-PH 230VAC OUT 2.3AMP AB
1305-BA04A-DE-HA21305-BA04A-DE-HA2 1305 AC Drives with IP 30 (NEMA Type 1) enclosure, 380-460V, Three Phase rating an…
1305-BA04A-ESAllen Bradley-DRIVE .5HP 3-PH 230VAC OUT 2.3AMP AB
1305-BA04A-FRAllen Bradley-DRIVE .5HP 3-PH 230VAC OUT 2.3AMP AB
1305-BA04A-HA11305-BA04A-HA1 1305 AC Drives with IP 30 (NEMA Type 1) enclosure, 380-460V, Three Phase rating and H…
1305-BA04A-HA21305-BA04A-HA2 1305 AC Drives with IP 30 (NEMA Type 1) enclosure, 380-460V, Three Phase rating and H…
1305-BA04A-HAP1305-BA04A-HAP 1305 AC Drives with IP 30 (NEMA Type 1) enclosure, 380-460V, Three Phase rating and P…
1305-BA06AAllen Bradley-DRIVE .5HP 3-PH 230VAC OUT 2.3AMP AB
1305-BA06A-DE1305-BA06A-DE 1305 AC Drives with IP 30 (NEMA Type 1) enclosure, 380-460V, Three Phase rating and N/…
1305-BA06A-ES1305-BA06A-ES 1305 AC Drives with IP 30 (NEMA Type 1) enclosure, 380-460V, Three Phase rating and N/…
1305-BA06A-HA11305-BA06A-HA1 1305 AC Drives with IP 30 (NEMA Type 1) enclosure, 380-460V, Three Phase rating and H…
1305-BA06A-HA21305-BA06A-HA2 1305 AC Drives with IP 30 (NEMA Type 1) enclosure, 380-460V, Three Phase rating and H…
1305-BA06A-HAP1305-BA06A-HAP 1305 AC Drives with IP 30 (NEMA Type 1) enclosure, 380-460V, Three Phase rating and P…
1305-BA09AAllen Bradley-DRIVE .5HP 3-PH 230VAC OUT 2.3AMP AB
1305-BA09A-DEAllen Bradley-DRIVE .5HP 3-PH 230VAC OUT 2.3AMP AB
1305-BA09A-HA11305-BA09A-HA1 1305 AC Drives with IP 30 (NEMA Type 1) enclosure, 380-460V, Three Phase rating and H…
1305-BA09A-HA21305-BA09A-HA2 1305 AC Drives with IP 30 (NEMA Type 1) enclosure, 380-460V, Three Phase rating and H…
1305-BA09A-HAP1305-BA09A-HAP 1305 AC Drives with IP 30 (NEMA Type 1) enclosure, 380-460V, Three Phase rating and P…
1305-BA09FC-HJ2Allen Bradley-DRIVE .5HP 3-PH 230VAC OUT 2.3AMP AB
1305-HA02FC-HJ2CAllen Bradley-DRIVE .5HP 3-PH 230VAC OUT 2.3AMP AB