Allen-Bradley Allen-Bradley – PanelView Plus 600

The PanelView Standard 600 Operator Interface Terminals have a 5 inch color flat-panel display with 320 x 234 resolution. The PanelView 600 terminal is designed for safe use when installed in a suitably rated NEMA Type 12, 13, 4X, IP54 or IP65 enclosure. These terminals support operator input via keypad, via touch screen or via keypad with touch screen.

PanelView Plus 600
Part numberManufacturerDescription
2711P-T6C20DAllen BradleyPanelView Plus 600 Color Touch Ethernet Dc Ps Incl Rs232 & Usb 32Mb Flash/64Mb Ram
2711P-T6M20DAllen BradleyPanelView Plus 600 Grayscale Touch Ethernet Dc Ps Incl Rs232 & Usb 32Mb Flash/64Mb Ram
2711PRFK6Allen BradleyReplacement Function Key Legend Strips For PanelView Plus 600 Incl Printable Blank Legends & Sw
2711PRGK6Allen BradleyProtective Antiglare Overlay Qty 3 For PanelView Plus 600 Keypad Or Key/Touch
2711PRAK6Allen BradleyCutout Adapter To Mount PanelView Plus 600 Keypad In PanelView 600 Keypad Cutout
2711PRGT6Allen BradleyProtective Antiglare Overlay Qty 3 For PanelView Plus 600 Touch
2711PT6C20AAllen BradleyPanelView Plus 600 Color Touch Ethernet Ac Ps Incl Rs232 & Usb 32Mb Flash/64Mb Ram
2711PB6C3DAllen BradleyPanelView Plus 600 Color Key/Touch Dh485 Dc Ps Incl Rs232 Ethernet & Usb 32Mb Flash/64Mb Ram
2711PB6C5DAllen BradleyPanelView Plus 600 Color Key/Touch Rs232 Dc Ps Incl Usb 32Mb Flash/64Mb Ram
2711PT6C8DAllen BradleyPanelView Plus 600 Color Touch Dh+ Dc Ps Incl Rs232 Ethernet & Usb 32Mb Flash/64Mb Ram
2711PK6C5DAllen BradleyPanelView Plus 600 Color Keypad Rs232 Dc Ps Incl Usb 32Mb Flash/64Mb Ram
2711PST6BMAllen BradleyPanelView Plus 600 Grayscale Key/Touch Starter Kit Incl 2711P-B6M20A 2711-Nc13 & 9701-Vwstmene
2711PST6BCAllen BradleyPanelView Plus 600 Color Key/Touch Starter Kit Incl 2711P-B6C20A 2711-Nc13 & 9701-Vwstmene
2711PST6KCAllen BradleyPanelView Plus 600 Color Keypad Starter Kit Incl 2711P-K6C20A 2711-Nc13 & 9701-Vwstmene
2711PRN1Allen BradleySrio Network Communication Module For PanelView Plus 400 & 600
2711PT6M8DAllen BradleyPanelView Plus 600 Grayscale Touch Dh+ Dc Ps Incl Rs232 Ethernet & Usb 32Mb Flash/64Mb Ram
2711PK6M8DAllen BradleyPanelView Plus 600 Grayscale Keypad Dh+ Dc Ps Incl Rs232 Ethernet & Usb 32Mb Flash/64Mb Ram
2711PK6M8AAllen BradleyPanelView Plus 600 Grayscale Keypad Dh+ Ac Ps Incl Rs232 Ethernet & Usb 32Mb Flash/64Mb Ram
2711PK6M5DAllen BradleyPanelView Plus 600 Grayscale Keypad Rs232 Dc Ps Incl Usb 32Mb Flash/64Mb Ram
2711PK6M5AAllen BradleyPanelView Plus 600 Grayscale Keypad Rs232 Ac Ps Incl Usb 32Mb Flash/64Mb Ram
2711PK6M3DAllen BradleyPanelView Plus 600 Grayscale Keypad Dh485 Dc Ps Incl Rs232 Ethernet & Usb 32Mb Flash/64Mb Ram
2711PST6KMAllen BradleyPanelView Plus 600 Grayscale Keypad Starter Kit Incl 2711P-K6M20A 2711-Nc13 & 9701-Vwstmene
2711PST6TCAllen BradleyPanelView Plus 600 Color Touch Starter Kit Incl 2711P-T6C20A 2711-Nc13 & 9701-Vwstmene
2711PT6M8AAllen BradleyPanelView Plus 600 Grayscale Touch Dh+ Ac Ps Incl Rs232 Ethernet & Usb 32Mb Flash/64Mb Ram
2711PT6M5AAllen BradleyPanelView Plus 600 Grayscale Touch Rs232 Ac Ps Incl Usb 32Mb Flash/64Mb Ram

Our Main Business on :PanelView Plus 6,PanelView Plus 400,PanelView Plus 600,PanelView Plus 700 ,PanelView Plus 1000,PanelView Plus 1500 ,PanelView Plus 1250…All the ALLEN BRADLEY AC Drives we sell Made in America! 100% Original!

Allen-Bradley PanelView 600 Technical Specifications

Troubleshooting Your PanelView 600

PanelView 600 Startup Failure

If your PanelView 600 fails to startup properly, always check the power supply first. Ensure the terminal is receiving the correct voltage and that the wiring and connections to the power source are valid. In addition, you should also ensure the DC power positive and negative are attached to the proper terminals.

PanelView 600 Status Indicators

The status indicators are located on the back of your PanelView 600 terminal.  The COMM indicator is green and reflects communication. The FAULT indicator is red and reflects hardware faults. Upon startup, the fault indicator should be off and the comm indicator on. If the fault indicator flashes a few times at startup, this is not a concern. However, if both indicators are off you should check the power cable. See the table below to interpret the terminal’s indicator status:

Status Indicators – DH+, DH-485, DF1

IndicatorStatusMeaning
CommOnNormal Operation
OffFault Present-

Ensure controller is in run mode. Check baud settings of controller/terminal. Check for proper controller connections.

BlinkingFailed to establish communication
FaultOnFault Present –

Restart terminal. If the error persists, the terminal requires servicing. Click here for information about DO Supply’s repair service.

OffNormal Operation
BlinkingNo applications loaded/application is corrupt. Reload the application.

Status Indicators – Ethernet/IP, ControlNet, DeviceNet Networks

IndicatorStatusMeaning
CommOnNormal operation
OffHardware failure
BlinkingFailed to establish communication
FaultOnHardware failure.
OffNormal operation
BlinkingApplication not loaded/application is corrupt

Status Indicators – Remote I/O

IndicatorStatusMeaning
CommOnNormal operation
OffCommunication non-functional
BlinkingFailed to establish communication, PLC may be in program mode
FaultOnFault Present –

Check baud rate and rack settings. Ensure proper connections from terminal to controller. Verify remote I/O is enabled.

OffNormal Operation
BlinkingApplication not loaded/application is corrupt

PanelView 600 Application Issues

Application Issues

IssuePossible CauseAction
Failed Application Download (Initial Attempt)Disconnected Communication CableCheck cable type and connection
Improper Computer COM Port SelectionEnsure you have the correct COM port number in PanelBuilder32 or WinPFT software
Communication Settings/Rate IncorrectEnsure computer and terminal share the same communication settings
Failed Application  Download (Subsequent Attempts)Communication Settings/Rate IncorrectEnsure computer and terminal share the same communication settings. Adjust settings in the Communication Setup screen
Application File Name Appears as *******Invalid ApplicationRedownload application
Unusable Application Due to ErrorDownload new application
Failed Application Transfer from Memory CardMemory card incorrectly installedReinstall, verify its installed correctly
Application to Large for Terminal MemoryReduce application size
Incorrect Data ChecksumEnsure memory card is properly seated. It is possible the application may be corrupt
File Format InvalidVerify file format (.PVA)
Failed Application Transfer to Memory CardMemory card incorrectly installedReinstall, verify its installed correctly
Memory Card May be Wire ProtectedChange memory card protection switch
Another File on the Memory CardErase/reformat card
Application to LargeReduce application size, erase/reformat card
Memory Card Format InvalidReplace/reformat card
Incorrect Data ChecksumEnsure card is installed correctly
Application Does Not ExistEnsure application exists