SCADA system SIMATIC WinCC WinCC/Redundancy

WinCC/Redundancy
  • Option for SIMATIC WinCC, supporting the parallel operation of two interfaced WinCC single-user systems or process data servers for mutual monitoring
  • If one of the two server PCs or one of the two WinCC stations fails, the second one will take over control of the entire system. Once the failed server or station is restored to operation, the content of all the message and process value archives are copied to it.
  • One WinCC/Redundancy package is required for each redundant pair of servers.

1.Bank/Wire Transfer

2.Western union

3.PayPal

4.Cheque (Check)

5.We accept currency: USD, or RMB or EUR

12-Month-Warranty-dental-ha12 Month Warranty On All Parts100% Tested & Cleaned Guaranteed100-Cleaned-GuaranteedFree Technica Support

We focus on industrial automation and process instrument over 20 years

Ordering data

Product No. / Product DescriptionListprice / Your price
6AV6371-1CF07-3AX0
SIMATIC WinCC/Redundancy V7.3, Option for SIMATIC WinCC V7.3, Runtime software, Single Lic. f. 2 installations
6AV6371-1CF07-4AX0
SIMATIC WinCC/Redundancy V7.4, Option for SIMATIC WinCC V7.4, Runtime software, Single Lic. f. 2 installations
6AV6371-1HF07-3AX0
SIMATIC WinCC/Redundancy V7.3, Option for SIMATIC WinCC V7.3, Runtime software, Single Lic. f. 2 installations License key download ******************************* E-mail address required for delivery
This product is downloadable only. This product is downloadable only.
6AV6371-1HF07-4AX0
SIMATIC WinCC/Redundancy V7.4, Option for WinCC V7.4, runtime software, Single license, License key download ******************************* E-mail address required for delivery

Benefits

  • Increased system availability with continuous data integrity
  • Automatic changeover of client in the event of failure of a server or failure of the communication to a server
  • Continuous operator control and visualization thanks to automatic client changeover to the intact server
  • Automatic updating of all archives in the background after rectification of the fault

Function

Normally, two WinCC stations or process data servers run in parallel. Each station has its own process connection and its own data archives. WinCC/Redundancy ensures automatic matching of system and user archive data.

If one of the two server computers or WinCC stations fails, the second will take over the archiving of messages and process data, thereby ensuring seamless data integrity. In client/server mode, the clients are automatically switched from the failed server to the redundant partner. This ensures continuous plant visualization and operation on every operator station.

When the failed partner resumes operation, all process values, messages and data archived during the fail period are automatically matched with the partner. This process runs in the background and does not affect plant continuity. Once this is complete, two equivalent servers/stations will be available again.

Communication with the SIMATIC S7 PLC can also be configured with redundancy (an H Series SIMATIC S7 is required) by plugging in two communication modules and configuring two communication paths (S7-REDCONNECT software package). The use of failsafe H Series SIMATIC S7 PLCs can, if required, further increase availability at control level.

Popular Products Series

Mitsubishi F740 Series Frequency Inverter

The FR-F700 Series was launched in 2004 as the successor to the FR-F500 Series VFD. With growing market demands for energy saving inverters in building automation, water processing and HVAC industries, the FR-F700 was able to exceed power-saving expectations in fan and pump applications by incorporating “OEC” (optimum excitation control) which combined maximum drive utilization with minimal power consumption.

Siemens PLC spare part 6AV 6DD 6SN 6ES5 6ES7

Main supply Siemens 6ES7 6AV6 6AV3 6SE7 Spare parts...

Allen-Bradley 6176M Standard Industrial Monitors

Allen-Bradley 6176M Standard Industrial Monitors
6176M Standard Monitors are flat panel industrial color monitors for use in less demanding environments. All Standard Monitors have USB and RS232 touch screen inputs, DVI and VGA video inputs, and an On Screen Display (OSD) that enables image rotation, color pallet changes, and push button auto reset.

Allen-Bradley 6186M Performance Monitors

Simatic S7-200 Smart PLC

SIEMNES SIMATIC S7-200 Smart, newly launched micro PLC Product, is designed to suit the needs of developing markets that are under constant pressure due to price and demands for continuous performance. Providing an excellent performance – to – price ratio, SIMATIC S7 200 SMART when combined with other smart drive products from Siemens helps in building a cost effective yet efficient automation Solution.

ACS800-104/-104LC – inverter module

ACS800-04 – single drive modules

Siemens SIMOVERT MasterDrive Rectifier Regenerative Unit

Load more