Siemens Basic Pressure transmitter SITRANS P210 (7MF1566)

SITRANS P210

Sitrans P210

Order No: 7MF1566-….-….

The pressure transmitter SITRANS P210 measures the gauge pressure of liquids, gases and vapors.

  • Stainless steel measuring cell
  • Measuring ranges 100 to 600 mbar (1.45 to 8.7 psi) relative
  • For low-pressure applications
Product No. / Product Description SITRANS P210 for gauge pressure  Ordering data
7MF1566-…..-….
SITRANS P210 Transmitters for pressure and absolute pressure for low-pressure applications Non-linearity: 0,25 percent (typically) wetted parts material: stainless steel plus sealing material; non-wetted parts material: stainless steel

Application

The pressure transmitter SITRANS P210 for gauge pressure is used in the following industrial areas:

  • Mechanical engineering
  • Shipbuilding
  • Power engineering
  • Chemical industry
  • Water supply

Design

Device structure without explosion protection

The pressure transmitter consists of a piezoresistive measuring cell with a diaphragm installed in a stainless steel enclosure. It can be connected to the electricity supply using a connector to EN 175301-803-A (IP65), an M12 round plug (IP67), a cable (IP67) or a Quickon cable quick screw connection (IP67). The output signal is between 4 and 20 mA or 0 and 10 V.

Device structure with explosion protection

The pressure transmitter consists of a piezoresistive measuring cell with a diaphragm installed in a stainless steel enclosure. It can be used with a connector per EN 175301-803-A (IP65) or a round plug M12 (IP67) connected electrically. The output signal is between 4 and 20 mA.

Benefits

  • High measuring accuracy
  • Rugged stainless steel enclosure
  • High overload withstand capability
  • For aggressive and non-aggressive media
  • For measuring the pressure of liquids, gases and vapors
  • Compact design

Function

The pressure transmitter measures the gauge pressure of liquids and gases as well as the level of liquids.

Mode of operation

SITRANS P210 pressure transmitters (7MF1566-…), functional diagram

The stainless steel measuring cell has a thin-film resistance bridge to which the operating pressure p is transmitted through a stainless steel diaphragm.

The voltage output from the measuring cell is converted by an amplifier into an output current of 4 to 20 mA or an output voltage of 0 to 10 V DC.

The output current and voltage are linearly proportional to the input pressure.

Siemens Pressure transmitter SITRANS P220 Description Part Number Price

Sitrans P210 Pressure Transmitter, 0 to 100 mbar, 4 to 20mA Output, 1/2
Sitrans P210 Pressure Transmitter, 0 to 100 mbar, 4 to 20mA Output, 1/2″ BSP Male, 0.25% Accuracy non-Atex
7MF15663AA001AA1

Sitrans P210 Pressure Transmitter, 0 to 100 mbar, 4 to 20mA Output, 1/2
Sitrans P210 Pressure Transmitter, 0 to 100 mbar, 4 to 20mA Output, 1/2″ NPT Male, 0.25% Accuracy non-Atex
7MF15663AA001GA1

Sitrans P210 Pressure Transmitter, 0 to 160 mbar, 4 to 20mA Output, 1/2
Sitrans P210 Pressure Transmitter, 0 to 160 mbar, 4 to 20mA Output, 1/2″ BSP Male, 0.25% Accuracy non-Atex
7MF15663AB001AA1

Sitrans P210 Pressure Transmitter, 0 to 160 mbar, 4 to 20mA Output, 1/2
Sitrans P210 Pressure Transmitter, 0 to 160 mbar, 4 to 20mA Output, 1/2″ NPT Male, 0.25% Accuracy non-Atex
7MF15663AB001GA1

Sitrans P210 Pressure Transmitter, 0 to 250 mbar, 4 to 20mA Output, 1/2
Sitrans P210 Pressure Transmitter, 0 to 250 mbar, 4 to 20mA Output, 1/2″ BSP Male, 0.25% Accuracy non-Atex
7MF15663AC001AA1

Sitrans P210 Pressure Transmitter, 0 to 250 mbar, 4 to 20mA Output, 1/2
Sitrans P210 Pressure Transmitter, 0 to 250 mbar, 4 to 20mA Output, 1/2″ NPT Male, 0.25% Accuracy non-Atex
7MF15663AC001GA1

Sitrans P210 Pressure Transmitter, 0 to 400 mbar, 4 to 20mA Output, 1/2
Sitrans P210 Pressure Transmitter, 0 to 400 mbar, 4 to 20mA Output, 1/2″ BSP Male, 0.25% Accuracy non-Atex
7MF15663AD001AA1

Sitrans P210 Pressure Transmitter, 0 to 400 mbar, 4 to 20mA Output, 1/2
Sitrans P210 Pressure Transmitter, 0 to 400 mbar, 4 to 20mA Output, 1/2″ NPT Male, 0.25% Accuracy non-Atex
7MF15663AD001GA1

Sitrans P210 Pressure Transmitter, 0 to 600 mbar, 4 to 20mA Output, 1/2
Sitrans P210 Pressure Transmitter, 0 to 600 mbar, 4 to 20mA Output, 1/2″ BSP Male, 0.25% Accuracy non-Atex
7MF15663AG001AA1

Sitrans P210 Pressure Transmitter, 0 to 600 mbar, 4 to 20mA Output, 1/2
Sitrans P210 Pressure Transmitter, 0 to 600 mbar, 4 to 20mA Output, 1/2″ NPT Male, 0.25% Accuracy non-Atex
7MF15663AG001GA1

SITRANS P220 (7MF1567) Technical specifications

Application

Gauge pressure measurement

Liquids, gases and vapors

Mode of operation

Measuring principle

Piezoresistive measuring cell (stainless steel diaphragm)

Measured variable

Gauge pressure

Input

Measuring range

  • Gauge pressure

100 … 600 mbar (1.45 … 8.7 psi)

Output

Current signal

4 … 20 mA

  • Load

(UB – 10 V) / 0.02 A

  • Auxiliary power UB

7 … 33 V DC (10 … 30 V for Ex)

Voltage signal

0 … 10 V DC

  • Load

≥ 10 kΩ

  • Auxiliary power UB

12 … 33 V DC

  • Current consumption

< 7 mA at 10 kΩ

Radiometric output

10 … 90%

  • Load

≥ 10 kΩ

  • Auxiliary power UB

DC 5 V ± 10%

  • Current consumption

< 7 mA at 10 kΩ

Characteristic curve

Linear rising

Measuring accuracy

Error in measurement at limit setting including hysteresis and reproducibility

  • Typical: 0.25 % of full-scale value
  • Maximum: 0.5 % of full-scale value

Step response time T99

< 5 ms

Long-term stability

  • Lower range value and measuring span

0.25 % of full-scale value/year

Effect of ambient temperature

  • Lower range value and measuring span
  • 0.25 %/10 K of full-scale value
  • 0.5 %/10 K of full-scale value for a measuring range of 100 … 400 mbar (40 … 240 inH2O)
  • Influence of power supply

0.005 %/V

Rated conditions

Pressure transmitter with gasket made of:

  • FPM (standard)

-15 … +125 °C (5 … 257 °F)

  • Neoprene

-35 … +100 °C (-31 … +212 °F)

  • Perbunan

-20 … +100 °C (-4 … +212 °F)

  • EPDM

-40 … +145 °C (-40 … +293 °F),
usable for drinking water

Ambient temperature

-25 … +85 °C (-13 … +185 °F)

Storage temperature

-50 … +100 °C (-58 … +212 °F)

Degree of protection according to IEC 60529

  • IP65 with connector to EN 175301-803-A
  • IP67 with M12 connector
  • IP67 with cable
  • IP67 with cable quick screw connection

Electromagnetic compatibility

  • according to IEC 61326-1/-2/-3
  • according to NAMUR NE21 for ATEX devices only, and with a max. measurement error of ≤ 1 %

Mounting position

Vertical, facing up

Design

Weight

Approx. 0.090 kg (0.198 lb)

Process connections

See dimension drawings

Electrical connections

  • Connector to EN 175301-803-A Form A with cable inlet M16x1.5 or ½-14 NPT or Pg 11
  • M12 connector
  • 2 or 3-wire (0.5 mm2) cable (∅ ± 5.4 mm)
  • Quickon cable quick screw connection

Wetted parts materials

  • Measuring cell

Stainless steel, mat.-No. 1.4435

  • Process connection

Stainless steel, mat. no. 1.4404 (SST 316 L)

  • Gasket
  • FPM (standard)
  • Neoprene
  • Perbunan
  • EPDM

Non-wetted parts materials

  • Enclosure

Stainless steel, mat. no. 1.4404 (SST 316 L)

  • Rack

Plastic

  • Cable

PVC

Certificates and approvals

Classification according to pressure equipment directive (PED 2014/68/EU)

For gases of fluid group 1 and liquids of fluid group 1;

meets requirements as per article 4, paragraph 3 (sound engineering practice)

Lloyd’s Register of Shipping (LR)1)

12/20010

Germanischer Lloyd (GL)1)

GL19740 11 HH00

American Bureau of Shipping (ABS)1)

ABS_11_HG 789392_PDA

French marine classification society (BV)1)

BV 271007A0 BV

Det Norske Veritas (DNV)1)

A 12553

Drinking water approval (ACS)1)

ACS 15 ACC NY 360

EAC1)

№ TC RU C-DE.ГБ05.В.00732 OC НАНИО «ЦСВЭ»

Underwriters Laboratories (UL)1)

  • For the USA and Canada

UL 20110217 – E34453

  • Worldwide

IEC UL DK 21845

Explosion protection

Intrinsic safety “i” (only with current output)

Ex II 1/2 G Ex ia IIC T4 GA/gb

Ex II 1/2 D Ex ia IIIC T125 °C Da/Db

EC type-examination certificate

SEV 10 ATEX 0146

Connection to certified intrinsically-safe resistive circuits with maximum values

Ui ≤ 30 V DC; Ii = 100 mA; Pi ≤ 0.75 W

Effective internal inductance and capacity for versions with plugs per EN 175301-803-A and M12

Li = 0 nH; Ci = 0 nF

1) For variants with output signal 0 … 5 V and radiometric output available soon.


Dimensional drawings

SITRANS P210, electrical connections, dimensions in mm (inch)

SITRANS P210, process connections, dimensions in mm (inch)


Circuit diagrams

Connection with current output and connector per EN 175301

Connection with current output and connector M12x1

Connection with current output and cable

Connection with current output and Quickon cable quick screw connection

Connection with voltage output, ratiometric output and plug according to EN 175301

Connection with voltage output, ratiometric output and M12x1 plug

Connection with voltage output, ratiometric output and cable

Connection with voltage output, ratiometric output and Quickon fast cable termination

Version with explosion protection: 4 … 20 mA

The grounding connection is conductively bonded to the transmitter enclosure.

Connection with current output and connector per EN 175301 (Ex)

Connection with current output and connector M12x1 (Ex)