SIEMENS Process controllers SIPART DR19
SIPART DR19 controller
The SIPART DR19 process controller is a digital controller. It is mainly used for applications in mechanical engineering and device manufacture. Its internal program memory contains a large number of standard functions for the control of process engineering applications. A user with no programming knowledge can simply call up and execute these functions.
It includes as standard an input for direct connection of temperature sensors such as thermocouples (TC), Pt 100 resistance thermometers (RTD), resistance based sensors (R) or voltage signals in the mV range (also mA and V with adaptor plug).
The SIPART DR19 controller is very flexible and can be quickly and easily configured to meet the requirements of the application.
An adaptation process is built in as standard.
The SIPART DR19 controller can be used as a:
- Fixed setpoint controller with 2 internal setpoints, optionally for one, two or three-component control
- Fixed setpoint controller with up to 5 internal setpoints, optionally for one, two or three-component control
- Slave, synchro or SPC controller, with the option of internal/external switchover
- Fixed or controlled ratio controller with internal/external switchover
- M/A control station, process variable indicator or setpoint transmitter. The control algorithm is disabled in these cases
- Program controller/transmitter, optionally for one, two or three-component control.
SIEMENS SIPART DR19 controllers Accessories
SIPART DR19 controller Technical specifications
SIPART DR19 controller | |
---|---|
General | |
Mounting position | Any |
Climatic classes | |
| -25 to +75 °C |
| -25 to +75 °C |
| 0 to +50 °C |
Protection according to EN 60 529 | |
| IP64 |
| IP30 |
| IP20 |
Controller design Electrical safety
EC Certificate of Conformity no. 1225.00-03/01 CE marking: conformity concerning EMC Guideline 89/336/EWG and NS Guideline 73/23/EWG is fulfilled without restrictions. Emitted interference, immunity to interference to EN 61 326, NAMUR NE21 8/98 The SIPART DR19 controller has already acquired the following certifications:
| |
Weight of basic unit | Approx. 1.2 kg |
Dimensions | |
Color | |
Fascia frame | RAL 7037 |
Fascia | RAL 7035 |
Material | |
Housing and fascia frame | Polycarbonate, reinforced with glass fiber |
Front foil | Polyester |
Rear panels, modules | Polybutylene-terephthalate |
Auxiliary supply connections | |
115/230 V AC | 3-pin earthed plug |
24 V AC/DC | Special 2-pin plug |
Connections for process signals | Multi-pin screw-type terminal blocks, protected against reversed polarity for cables of 1.5 mm2 (AWG 14) |
Protective earth connection | Earthing screw |
A rail can be mounted on the rear panel of the power supply. The rail is included in the delivery of the coupling relay module. | |
The connectors for the auxiliary supply and the screw-type terminal blocks for the process signals are part of the scope of the supply of the basic unit or the option modules. |
Power supply | ||||
---|---|---|---|---|
Rated voltage | Switchable | |||
230 V AC | 115 V AC | 24 V AC/DC | ||
Operating voltage range | 195 to 264 V | 97 to 132 V | 20 to 28 V | 20 to 35 V |
Frequency | 48 to 63 Hz | – | ||
Peak voltages to IEC 801-5 | ||||
symmetric | 1 kV | 1 kV | 0.5 kV | 0.5 kV |
asymmetric | 2 kV | 2 kV | 1 kV | 1 kV |
Total of all output currents (L+, BA, AA and SES) | max. 200 mA | |||
Power consumption Active power/ Basic unit | ||||
| 5 W/9 VA | 5 W/9 VA | 4 W/6 VA | 4 W |
| 11 W/15 VA | 11 W/15 VA | 8.5 W/12 VA | 8.5 W |
| 15 W/19 VA | 15 W/19 VA | 12 W/17 VA | 12 W |
Permitted voltage dips at Basic unit with options | ≤ 20 ms | |||
Test voltages (1 min) | ||||
| 1.5 kV AC | 500 V AC | ||
| 1.5 kV AC | 500 V AC | ||
| 700 V DC | 700 V DC |
1 ) Includes harmonic content.
Program controller/transmitter | |
---|---|
Program | P1 |
Intervals per program | P1 = 10 |
Variable ramp/stop time | All intervals can be used as ramps or stop time, interval and amplitude for interval end can be modified |
Interval period on time basis | |
| 00.00 to 23.59 |
| 00.00 to 59.59 |
Time base | Same for all intervals |
Status signals | 6 digital outputs (time-controlled) |
Each interval can be signalled on each digital output | |
Program – Start – Stop | From front panel or digital input |
Reset | From front panel or digital input |
Basic unit | ||
---|---|---|
Analog input AE1 | See standard controller, Analog input AE1 | |
Transmitter supply L+ | ||
| 20 to 26 V | |
| ≤ 60 mA, short-circuit proof | |
| ≤ 200 mA, pulsed | |
Digital outputs BE1 and BE2 | ||
| ≤ 4.5 V or open | |
| ≥ 13 V | |
| ≥ 27 kΩ | |
Digital outputs BA1 and BA2 | ||
| ≤ 1.5 V | |
| +19 to 26 V | |
| ≤ 50 mA | |
| ≤ 80 mA, pulsed | |
Analog output Iy (K controller) | ||
| 0 to 20 mA or 4 to 20 mA | |
| 0 to 20.5 mA or 3.8 to 20.5 mA | |
| -1 to +18 V | |
| 0.1 H | |
Relay output (S controller) | ||
| Ag-Ni | |
| ||
| 250 V AC 250 V DC | |
| 8 A 8 A | |
| 1250 VA 100 W at 24 V | |
Service life | ||
Mechanical | 2 . 107 switching operations | |
Electrical. 230 V AC, | 2 . 106 switching operations | |
Spark suppressor | 22 nF and 220 Ω connected in series with a 420 V varistor wired in parallel | |
CPU data | ||
| 100 ms | |
A/D conversion | ||
| Successive approximation with > 120 measurements per input and averaging within 20 or 16.67 ms | |
| 18 bit for AE 1 | |
| ≤ 0.2 % of measuring span | |
| ≤ 0.2 % of measuring span | |
| ≤ 0.2 % of measuring span | |
Display technology | ||
Digital x indicator | 4-digit, red, 7-segment LED display | |
Digital w indicator | 4-digit, green, 7-segment LED display | |
| 10 mm | |
| Adjustable start and full scale | |
| -1999 to +9999 | |
| Adjustable (fixed point) | |
| 0.1 to 9.9 s, variable | |
Analog indicator | Vertical row of 21 LEDs (red) | |
| ||
| ± 5 % to ± 20 % | |
| 0 to 100 % | |
Basic unit, analog input AE 1 | ||
Pt100 resistance thermometer | ||
Line resistance | ||
| Line resistance | |
RAb = RL1 + RL4 defined by parameters | ||
| No compensation necessary if | |
| No compensation necessary if | |
Measuring current | 400 μA | |
Configurable measuring range | ||
| RtA ≥ 18.49 Ω, tA ≥ -200 °C | |
| RtE ≤ 390.26 Ω, tE ≤ 850 °C | |
Recommended min. span | 10 K | |
Characteristic | Temperature linear | |
Filter time constant | ≈ 10 ms | |
Input | Non-floating | |
Thermocouples TC | ||
Thermocouples, configurable | Typ | |
to DIN IEC 584, Part 1 | Cu-CuNi T | |
Fe-CuNi J | ||
NiCr-Ni K | ||
NiCr-CuNi E | ||
Pt10Rh-Pt S | ||
Pt13Rh-Pt R | ||
Pt30Rh-Pt6Rh B | ||
NiCrSi-NiSi N | ||
to DIN 43 710 | Cu-CuNi U | |
Fe-CuNi L | ||
Compensating reference junction | ||
| Reference junction terminal required | |
| Temperature of external reference junction entered as parameter | |
Line resistance | ≤ 300 Ω | |
Configurable measuring range | ||
| ≥ -175 mV | |
| ≤ +175 mV | |
Recommended min. span | 5 mV | |
Configurable characteristic | Linear with voltage or temperature | |
Filter time constant | ≈ 10 ms | |
Input current | ≤ 1 μA | |
Permitted common mode voltage | ≤ 1 V | |
Stat. destruction limit across inputs | ± 35 V | |
mV source | ||
Configurable measuring range | ||
| ≥ -175 mV | |
| ≤ +175 mV | |
Recommended min. span | 5 mV | |
Line resistance | ≤ 1 kΩ | |
Characteristic | Voltage linear | |
Input current | ≤ 1 μA | |
Permitted common mode voltage | ≤ 1 V | |
Stat. destruction limit across inputs | ± 35 V | |
Resistance based sensor R | ||
Measuring range | ||
Configurable measuring range | ||
Measuring range limits incl. line resistance | Rtot ≤ 600 Ω | Rtot ≤ 2.8 kΩ |
Recommended min. span | 30 Ω | 70 Ω |
Input current | 400 μA | 140 μA |
Linearity error | ± 60 mΩ | ± 0.2 Ω |
Test voltage | 500 V AC | |
Input | Non-floating | |
mA source | ||
Measuring range | ||
| 0/4 mA ≡ 0/20 mV | |
| 20 mA ≡ to 100 mV | |
Transformation error | 0,3 % | |
Input resistance | 50 Ω | |
Smart input resistance | 250 Ω | |
Permitted common mode voltage | ≤ 1 V | |
Stat. destruction limit across inputs | ± 40 mA | |
10 V voltage source | ||
Measuring range, can be compensated | ||
| 0/2 V ≡ to 0/20 mV | |
| 10 V ≡ to 100 mV | |
Transformation error | 0.2 % | |
Input resistance | 90 kΩ | |
Permitted common mode voltage | ≤ 1 V | |
Stat. destruction limit across inputs | ± 35 V |