SIEMENS S7-1200 Controllers SIPLUS fail-safe CPUs Overview/Ordering data

Product No. / Product Description Listprice / Your price
6AG1214-1AF40-5XB0
SIPLUS S7-1200 CPU 1214FC DC/DC/DC -25 … +55 DEGREES C WITH CONFORMAL COATING BASED ON: 6ES7214-1AF40-0XB0 . COMPACT CPU, DC/DC/DC, ONBOARD I/O: 14 DI 24V DC; 10 DO 24 V DC; 2 AI 0- 10V DC, POWER SUPPLY: DC 20,4 – 28,8 V DC, PROGRAM/DATA MEMORY 125 KB
6AG1214-1HF40-5XB0
SIPLUS S7-1200 CPU 1214FC DC/DC/RLY -25 … +55 GRAD C WITH CONFORMAL COATING BASED ON 6ES7214-1HF40-0XB0 . COMPACT CPU, DC/DC/RELAY, ONBOARD I/O: 14 DI 24V DC; 10 DO RELAY 2A; 2AI 0 – 10V DC, POWER SUPPLY:DC20.4-28.8VDC, PROGRAM/DATA MEMORY 125 KB

SIPLUS fail-safe CPUs OverviewSIPLUS fail-safe CPUs

The fail-safe SIPLUS S7-1200 Controllers are based on the S7-1200 standard CPUs and offer additional safety-related functions.

They can be used for safety-oriented tasks according to IEC 61508 up to SIL 3 and ISO 13849-1 up to PL e.

Safety-related programs are created in the TIA Portal. The STEP 7 Safety engineering tool offers commands, operations and blocks for safety-related programs in the LAD and FBD languages. To this end, there is a library with pre-configured, TÜV-approved blocks for safety-related functions.

  • Standard controller with integrated safety functions:
    • Standardized and convenient diagnostic functions for standard and safety
    • Uniform symbols, data consistency, …
  • Modular system with scalable range of CPUs and expandable I/O quantity structure:
    • One engineering for standard and fail-safe automation
    • Use of the standard I/O modules together with the fail-safe I/O modules in the central system
    • Integrated standard PROFINET functionalities for PROFINET controllers and PROFINET iDevice services
    • Connection of distributed standard I/O via field bus such as PROFINET or PROFIBUS
    • F-library certified by the German Technical Inspectorate (TÜV) for all common safety functions
    • Free programming of the safety logic using FBD and LAD
    • Standard-compliant printout of the F-program
  • One integrated engineering for both standard and safety from S7-1200 to S7-300/400/1500 and WinAC RTX F:
    • STEP 7 Safety Basic for easy engineering of the CPU 1200 FC
    • STEP 7 Safety Advanced for the entire fail-safe SIMATIC S7 portfolio
  • Integrated system diagnosis of the CPUs, for standard and safety:
    • Consistent plain text display of system diagnostic information in the TIA Portal, HMI and web server
    • Messages are updated even if the CPU is in STOP state
    • System diagnostics integrated in the CPU firmware. Configuration by user not required
    • The diagnostics is automatically updated on configuration changes.
  • 2 fail-safe compact controllers with graded performances in the versions DC/DC/DC and DC/DC/relay

Characteristics

SIPLUS CPU 1214 FC

Variants

DC/DC/DC, DC/DC/relay

Main memory, integrated

125 KB

Load memory, integrated

4 MB

Memory card

SIMATIC memory card (optional)

Standard digital inputs/outputs, integrated

14/10

Standard analog inputs, integrated

2

Standard analog outputs, integrated

Process image

1024 bytes for inputs, 1024 bytes for outputs

Expansion by signal board

Max. 1

Expansion by signal modules

Max. 8

Expansion by communication modules

Max. 3

Application

SIMATIC S7-1200 is the ideal controller for local and distributed automation solutions with safety requirements in the central system.

Via the engineering, the fail-safe SIMATIC S7-1200 makes preassembled, tested and TÜV-certified blocks available for implementing all common safety functions, such as emergency stop or protective door monitoring with or without interlocking.

  • CPU 1212FC:
    The ideal compact solution for standard and fail-safe applications
  • CPU 1214 FC:
    The compact CPU for standard and fail-safe applications
  • CPU 1215 FC:
    The compact CPU with two PROFINET ports for standard and fail-safe applications

Design

Mechanical features

  • Horizontal or vertical mounting on DIN rail or direct mounting in the cabinet using integral drill holes (not horizontal).
  • Terminal block for independent wiring for all CPUs and associated components.

Technical specifications

Article number

6AG1214-1AF40-5XB0

6AG1214-1HF40-5XB0

SIPLUS S7-1200 CPU 1214FC DC/DC/DC

SIPLUS S7-1200 CPU 1214FC DC/DC/RLY

General information

Product type designation

CPU 1214FC DC/DC/DC

CPU 1214FC DC/DC/Relay

Supply voltage

Rated value (DC)

  • ● 24 V DC

Yes

Yes

permissible range, lower limit (DC)

20.4 V

20.4 V

permissible range, upper limit (DC)

28.8 V

28.8 V

Load voltage L+

  • ● Rated value (DC)

24 V

24 V

  • ● permissible range, lower limit (DC)

20.4 V

20.4 V

  • ● permissible range, upper limit (DC)

28.8 V

28.8 V

Input current

Current consumption, max.

1 500 mA; max. with all expansion accessories

1 500 mA; max. with all expansion accessories

Inrush current, max.

12 A; at 28.8 V DC

12 A; at 28.8 V

Encoder supply

24 V encoder supply

  • ● 24 V

L+ minus 4 V DC min.

L+ minus 4 V DC min.

Power loss

Power loss, typ.

12 W

12 W

Memory

Work memory

  • ● integrated

125 kbyte

125 kbyte

  • ● expandable

No

No

Load memory

  • ● integrated

4 Mbyte

4 Mbyte

  • ● Plug-in (SIMATIC Memory Card), max.

with SIMATIC memory card

with SIMATIC memory card

Backup

  • ● present

Yes; maintenance-free

Yes; maintenance-free

  • ● without battery

Yes

Yes

CPU processing times

for bit operations, typ.

0.08 µs; / instruction

0.08 µs; / Operation

for word operations, typ.

1.7 µs; / instruction

1.7 µs; / Operation

for floating point arithmetic, typ.

2.3 µs; / Operation

2.3 µs; / instruction

CPU-blocks

Number of blocks (total)

1 024; OBs, FBs, FCs, DBs

1 024; OBs, FBs, FCs, DBs

OB

  • ● Number, max.

Limited only by RAM for code

Limited only by RAM for code

Data areas and their retentivity

Retentive data area (incl. timers, counters, flags), max.

10 kbyte

10 kbyte

Address area

I/O address area

  • ● Inputs

1 024 byte

1 024 byte

  • ● Outputs

1 024 byte

1 024 byte

Process image

  • ● Inputs, adjustable

1 024 byte

1 024 byte

  • ● Outputs, adjustable

1 024 byte

1 024 byte

Hardware configuration

Number of modules per system, max.

8; 3 comm. modules, 1 signal board, 8 signal modules

8; 3 comm. modules, 1 signal board, 8 signal modules

Time of day

Clock

  • ● Hardware clock (real-time)

Yes

Yes

  • ● Backup time

480 h; typical; 12 days min. at 40 °C

480 h; typical; 12 days min. at 40 °C

  • ● Deviation per day, max.

±60 s per month

±60 s per month

Digital inputs

Number of digital inputs

14

14

  • ● of which inputs usable for technological functions

6; HSC (High Speed Counting)

6; HSC (High Speed Counting)

Source/sink input

Yes

Yes

Number of simultaneously controllable inputs

all mounting positions

  • — up to 40 °C, max.

14; 14 inputs at 55 °C horizontal or 45 °C vertical

14; 14 inputs at 55 °C horizontal or 45 °C vertical

Input voltage

  • ● Rated value (DC)

24 V; DC at 4 mA nominal

24 V; DC at 4 mA nominal

  • ● for signal “0”

5 V DC at 1 mA

5 V DC at 1 mA

  • ● for signal “1”

15 V DC at 2.5 mA

15 V DC at 2.5 mA

Input current

  • ● for signal “1”, typ.

4 mA; nominal

4 mA; nominal

Input delay (for rated value of input voltage)

for standard inputs

  • — parameterizable

0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 μs; 0.05 / 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 ms

0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 μs; 0.05 / 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 ms

  • — at “0” to “1”, min.

0.1 µs

0.1 µs

  • — at “0” to “1”, max.

20 ms

20 ms

for interrupt inputs

  • — parameterizable

Yes

Yes

for counter/technological functions

  • — parameterizable

Yes; Single phase: 3 @ 100 kHz & 3 @ 30 kHz, differential: 3 @ 80 kHz & 3 @ 30 kHz

Single phase : 3 at 100 kHz & 3 at 30 kHz, differential: 3 at 80 kHz & 3 at 30 kHz

Cable length

  • ● shielded, max.

500 m; 50 m for technological functions

500 m; 50 m for technological functions

  • ● unshielded, max.

150 m; For technological functions: No

300 m; For technological functions: No

Digital outputs

Number of digital outputs

10

10; Relays

  • ● of which high-speed outputs

4; 100 kHz Pulse Train Output

Short-circuit protection

No; to be provided externally

No; to be provided externally

Switching capacity of the outputs

  • ● with resistive load, max.

0.5 A

2 A

  • ● on lamp load, max.

5 W

30 W; 30 W with DC, 200 W with AC

Output voltage

  • ● for signal “0”, max.

0.1 V; with 10 kOhm load

  • ● for signal “1”, min.

20 V

Output current

  • ● for signal “1” rated value

0.5 A

  • ● for signal “0” residual current, max.

0.1 mA

Output delay with resistive load

  • ● “0” to “1”, max.

1 µs

10 ms; max.

  • ● “1” to “0”, max.

3 µs

10 ms; max.

Switching frequency

  • ● of the pulse outputs, with resistive load, max.

100 kHz

Relay outputs

  • ● Number of relay outputs

10

  • ● Number of operating cycles, max.

mechanically 10 million, at rated load voltage 100 000

Cable length

  • ● shielded, max.

500 m

500 m

  • ● unshielded, max.

150 m

150 m

Analog inputs

Number of analog inputs

2

2

Input ranges

  • ● Voltage

Yes; 0 to 10V

Yes; 0 to 10V

Input ranges (rated values), voltages

  • ● 0 to +10 V

Yes

Yes

  • ● Input resistance (0 to 10 V)

≥100k ohms

≥100k ohms

Cable length

  • ● shielded, max.

100 m; shielded, twisted pair

100 m; shielded, twisted pair

Analog outputs

Number of analog outputs

0

0

Cable length

  • ● shielded, max.

100 m; shielded, twisted pair

100 m; shielded, twisted pair

Analog value generation for the inputs

Integration and conversion time/resolution per channel

  • ● Resolution with overrange (bit including sign), max.

10 bit

10 bit

  • ● Integration time, parameterizable

Yes

Yes

  • ● Conversion time (per channel)

625 µs

625 µs

Encoder

Connectable encoders

  • ● 2-wire sensor

Yes

Yes

1. Interface

Interface type

PROFINET

PROFINET

Physics

Ethernet

Ethernet

Isolated

Yes

Yes

automatic detection of transmission rate

Yes

Yes

Autonegotiation

Yes

Yes

Autocrossing

Yes

Yes

Functionality

  • ● PROFINET IO Controller

Yes

Yes

  • ● PROFINET IO Device

Yes

Yes

PROFINET IO Controller

Services

  • — Number of IO devices with prioritized startup, max.

16

16

Protocols

Supports protocol for PROFINET IO

Yes

Yes

PROFIBUS

Yes; CM 1243-5 required

Yes; CM 1243-5 required

AS-Interface

Yes

Yes

Protocols (Ethernet)

  • ● TCP/IP

Yes

Yes

Open IE communication

  • ● ISO-on-TCP (RFC1006)

Yes

Yes

Further protocols

  • ● MODBUS

Yes

Yes

Communication functions

S7 communication

  • ● supported

Yes

Yes

  • ● as server

Yes

Yes

  • ● as client

Yes

Yes

Open IE communication

  • ● TCP/IP

Yes

Yes

  • ● UDP

Yes

Yes

Web server

  • ● supported

Yes

Yes

  • ● User-defined websites

Yes

Yes

Test commissioning functions

Status/control

  • ● Status/control variable

Yes

Yes

  • ● Variables

Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters

Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters

Forcing

  • ● Forcing

Yes

Yes

Diagnostic buffer

  • ● present

Yes

Yes

Traces

  • ● Number of configurable Traces

2; Up to 512 KB of data per trace are possible

2; Up to 512 KB of data per trace are possible

Integrated Functions

Number of counters

6

6

Counting frequency (counter) max.

100 kHz

100 kHz

Frequency meter

Yes

Yes

controlled positioning

Yes

Yes

PID controller

Yes

Yes

Number of alarm inputs

4

4

Number of pulse outputs

4

4

Limit frequency (pulse)

100 kHz

Potential separation

Potential separation digital inputs

  • ● Potential separation digital inputs

Functional isolation (Optocoupler)

Functional isolation (Optocoupler)

Permissible potential difference

between different circuits

500 V DC between 24 V DC and 5 V DC

500 V DC between 24 V DC and 5 V DC

EMC

Interference immunity against discharge of static electricity

  • ● Interference immunity against discharge of static electricity acc. to IEC 61000-4-2

Yes

Yes

  • — Test voltage at air discharge

8 kV

8 kV

  • — Test voltage at contact discharge

6 kV

6 kV

Interference immunity to cable-borne interference

  • ● Interference immunity on supply lines acc. to IEC 61000-4-4

Yes

Yes

  • ● Interference immunity on signal cables acc. to IEC 61000-4-4

Yes

Yes

Interference immunity against voltage surge

  • ● on the supply lines acc. to IEC 61000-4-5

Yes

Yes

Interference immunity against conducted variable disturbance induced by high-frequency fields

  • ● Interference immunity against high-frequency radiation acc. to IEC 61000-4-6

Yes

Yes

Emission of radio interference acc. to EN 55 011

  • ● Limit class A, for use in industrial areas

Yes; Group 1

Yes; Group 1

  • ● Limit class B, for use in residential areas

Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011

Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011

Degree and class of protection

Degree of protection acc. to EN 60529

  • ● IP20

Yes

Yes

Standards, approvals, certificates

CE mark

Yes

Yes

UL approval

Yes

Yes

cULus

Yes

Yes

FM approval

No

No

RCM (formerly C-TICK)

Yes

Yes

Marine approval

Yes

Yes

Highest safety class achievable in safety mode

  • ● Performance level according to ISO 13849-1

PLe

PLe

  • ● SIL acc. to IEC 61508

SIL 3

SIL 3

Ambient conditions

Free fall

  • ● Fall height, max.

0.3 m; five times, in product package

0.3 m; five times, in product package

Ambient temperature during operation

  • ● min.

-25 °C; = Tmin

-25 °C; = Tmin

  • ● max.

55 °C; = Tmax

55 °C; = Tmax

  • ● horizontal installation, min.

-25 °C

-25 °C

  • ● horizontal installation, max.

55 °C

55 °C

  • ● vertical installation, min.

-25 °C

-25 °C

  • ● vertical installation, max.

45 °C

45 °C

Ambient temperature during storage/transportation

  • ● min.

-40 °C

-40 °C

  • ● max.

70 °C

70 °C

Air pressure acc. to IEC 60068-2-13

  • ● Operation, min.

795 hPa

795 hPa

  • ● Operation, max.

1 080 hPa

1 080 hPa

Altitude during operation based on sea level

  • ● Ambient air temperature-barometric pressure-altitude

Tmin … Tmax at 1080 hPa … 795 hPa (-1000 m … +2000 m)

Tmin … Tmax at 1080 hPa … 795 hPa (-1000 m … +2000 m)

Relative humidity

  • ● With condensation, tested in accordance with IEC 60068-2-38, max.

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

Vibrations

  • ● Vibrations

2 g (m/s²) wall mounting, 1 g (m/s²) DIN rail

2 g (m/s²) wall mounting, 1 g (m/s²) DIN rail

  • ● Operation, tested according to IEC 60068-2-6

Yes

Yes

Shock test

  • ● tested according to IEC 60068-2-27

Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms

Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms

Pollutant concentrations

  • ● SO2 at RH < 60% without condensation

S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free

S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free

Programming

Programming language

  • — LAD

Yes; incl. failsafe

Yes; incl. failsafe

  • — FBD

Yes; incl. failsafe

Yes; incl. failsafe

  • — SCL

Yes

Yes

Cycle time monitoring

  • ● adjustable

Yes

Yes

Dimensions

Width

110 mm

110 mm

Height

100 mm

100 mm

Depth

75 mm

75 mm

Weights

Weight, approx.

415 g

435 g