SIEMENS SIMATIC ET 200S Technical specifications

Information on SIMATIC ET 200S

Introduced in 2012, the successor system of the tried and tested SIMATIC ET 200S, the SIMATIC ET 200SP, brings a number of advantages.

For this reason, we recommend the use of the successor system SIMATIC ET 200SP for new automation concepts.

In addition to the well-known good system properties of the SIMATIC ET 200S such as

  • Finely modular design for adaptation to the automation task in hand
  • Permanent wiring (replacement of the I/O modules without affecting the wiring, even during operation)
  • Connection to PROFINET and PROFIBUS

SIMATIC ET 200SP offers further innovative system advantages compared to SIMATIC ET 200S:

Faster and more compact setup

      • Up to 50 % reduced space requirements in the control cabinet, with unchanged cross-section area
      • No tools needed for one-handed wiring thanks to push-in terminals
      • Reduced part variance with increased scope of functions
      • System-integrated self-assembling load group formation without power modules
      • As many as 16 channels per module and 1024 channels per station
      • Flexible PROFINET connection via BusAdapter (RJ45, FastConnect, plastic or glass fiber-optic cables), also as integrated media converter
      • System-integrated shield connection

Increased performanceSIMATIC ET 200S

      • Short response times and isochronous mode for motion applications
      • High-speed data acquisition (digital from 1 µs, analog from 50 µs) and transmission (up to 100 Mbps):
        for digital signals with time-based I/O for precisely timed controlling independent of bus cycles;
        for analog and digital signal oversampling, n-fold acquisition or output of signals within a PN cycle.

Additional functions

    • Measurement of machine consumption, e.g. current, using an integrated energy meter (up to 480 V)
    • Comprehensive diagnostics function (wire break and short-circuit) integrated by default even in Standard-class modules
    • System-integrated fail-safe modules (PROFIsafe) with simplified switchless address setting
    • Enhanced configuration control for easy option handling
    • Operation with gaps
    • Multi hot swapping
    • Larger module range (AS-i, AS-i Safety, additional CPU versions, Open Controller, etc.)
    • MSI/MSO: Simultaneous access to input and output data from up to 4 controllers
    • Adaptation of measuring range: Increased resolution by adapting the measuring range to a limited section of a measuring range supported by the analog input module
    • Station expansion through system-integrated IP67 components (ET 200AL)
  • Block I/O to IP20 degree of protection with 32 channels, comprising terminal block and electronic block
  • Discretely modular expansion to maximum of 128 channels or 12 modules
  • The complete ET 200S module spectrum can be used (with the exception of PROFIsafe modules)
  • Separation of terminal connections and electronics with permanent wiring
  • Screw-type and spring-loaded terminal connections
  • Standard terminal block with 2-wire connection system; 3-wire and 4-wire systems available using additional terminals
  • Mounting on standard rail
  • Hot swapping of expansion modules
  • Communication via PROFIBUS
  • Up to 100 bytes inputs and outputs (address space)

SIMATIC ET 200S Technical specifications

General technical specifications

Degree of protection

IP20

Ambient temperature

0 to 60 °C

Vibration resistance

g continuously,
g periodically
(motor starter max. 2 g)

Maximum configuration (none of the limits listed below must be exceeded)

  • Number of modules per IM 151, max.

IM151-1 BASIC: Up to 12 modules

IM151-1 COMPACT: Up to 12 modules

IM151-1 STANDARD: Up to 63 modules

IM151-1 HIGH FEATURE: Up to 63 modules

IM151-7 CPU: Up to 63 modules

IM151-3 PN: Up to 63 modules

  • Line width, max.

IM151-1 BASIC: Up to 2 m

IM151-1 COMPACT: Up to 2 m

IM151-1 STANDARD: Up to 2 m

IM151-1 HIGH FEATURE: Up to 2 m

IM151-7 CPU: Up to 1 m

IM151-3 PN: Up to 2 m

  • User data length

Depending on the number and type of connected modules

IM151-1 BASIC: Up to 88 bytes for inputs and outputs

IM151-1 COMPACT: Up to 100 bytes for inputs and outputs

IM151-1 STANDARD: Up to 244 bytes for inputs and outputs

IM151-1 HIGH FEATURE: Up to 244 bytes for inputs and outputs

IM151-7 CPU: Not relevant

IM151-3 PN: 256 bytes

  • Parameter length

Depending on the number and type of connected modules

IM151-1 BASIC: 198 bytes

IM151-1 COMPACT: 218 bytes

IM151-1 STANDARD: Up to 244 bytes

IM151-1 HIGH FEATURE: Up to 244 bytes

IM151-7 CPU: Not relevant

IM151-3 PN: Not relevant

Requirements of the DP master system

  • PROFIBUS DP master

In accordance with EN 50170

  • Parameter length

>32 bytes, depending on the number and type of connected modules

  • User data length

Depending on the number and type of connected modules

  • Diagnostics length

17 to 64 bytes (adjustable)

Standards and approvals

  • PROFIBUS

EN 50170, Volume 2

  • IEC 1131

IEC 1131, Part 2

  • UL

Acc. to standard UL508, File No. E 116536/E 75310 (AC modules)

  • RCM (formerly C-Tick)

AS/NZS 2064 (Class A)

  • CSA

Acc. to standard C22.2 No. 142, File No. LR 48323/LR 44226 (AC modules)

  • cULus for hazardous locations

Acc. to standard UL 508, File No. E 116536
acc. to hazardous locations UL 1604, File No. E 222109
acc. to standard CSA C22.2, no. 142

  • FM

Standard Class No. 3611, Class I, Division 2, Group A, B, C, D, Class I, Zone 2, Group IIC (without motor starter and frequency converter)

  • Shipbuilding

American Bureau of Shipping

Bureau Veritas

Det Norske Veritas

Germanischer Lloyd

Lloyds Register of Shipping

Nippon Kaiji Kyokai

(without motor starters and frequency converters)

  • Ex approval Cat. 3 (for Zone 2 acc. to ATEX–100a)

EN 50021

(without frequency converters)