SIEMENS SIMATIC LOGO! logic module-LOGO! modular expansion modules

LOGO! modular expansion modules Overview

  • Expansion modules for connection to LOGO! Modular
  • With digital inputs and outputs, analog inputs, or analog outputs

DesignLOGO! modular expansion modules

  • Relay outputs with max. 5 A output current.
  • Different modules:
    • 4 digital inputs, 4 digital outputs or
    • 4 digital inputs, 4 relay outputs or
    • 2 analog inputs or
    • 2 analog outputs.
  • Interface for connection to LOGO! modular logic modules.

Product No. / Product Description Listprice /  Your price
6ED1055-1CB00-0BA2
LOGO! DM8 24 EXPANSION MODULE, PU/I/O: 24V/24V/TRANS., 4 DI/4 DO FOR LOGO! 8
6ED1055-1CB10-0BA2
LOGO! DM16 24, EXP. MODULE PU/I/O: 24V DC/24V DC/TRANS., 8 DI/8 DO, 4TE FOR LOGO! 8
6ED1055-1FB00-0BA2
LOGO! DM8 230R, EXP. MODULE, PU/I/O: 230V/230V/RELAIS, 2TE, 4 DI/4 DO FOR LOGO! 8
6ED1055-1FB10-0BA2
LOGO! DM16 230R, EXP. MODULE, PU/I/O: 230V/230V/RELAIS, 4TE, 8 DI/8 DO FOR LOGO! 8
6ED1055-1HB00-0BA2
LOGO! DM8 24R EXPANSION MODULE, PU/I/O: 24V/24V/RELAY, 2TE 4 DI/4 DO, AC/DC/NPN INPUT FOR LOGO! 8
6ED1055-1MA00-0BA2
LOGO! AM2 EXPANSION MODULE, PU: DC 12/24V, 2 AI, 0 – 10V OR 0/4 – 20MA FOR LOGO! 8
6ED1055-1MB00-0BA2
LOGO! DM8 12/24R, EXP. MODULE PU/I/O: 12, 24V/12V/24V/RELAIS, 2TE, 4 DI/4 DO FOR LOGO! 8
6ED1055-1MD00-0BA2
LOGO! AM2 RTD EXPAN. MODULE, PU: DC 12/24V, 2AI, -50 … +200 DEGR/C PT100/1000 FOR LOGO! 8
6ED1055-1MM00-0BA2
LOGO! AM2 AQ EXPAN. MODULE, PU: DC 24V, 0/4-20MA 2AQ, 0-10V FOR LOGO! 8
6ED1055-1NB10-0BA2
LOGO! DM16 24R, EXP. MODULE, PU/I/O: 24V DC/24V DC/RELAY, 8 DI/8 DO, 4TE FOR LOGO! 8

Technical specifications

Article number

6ED1055-1CB00-0BA2

6ED1055-1HB00-0BA2

6ED1055-1MB00-0BA2

6ED1055-1FB00-0BA2

LOGO! DM8 24 EXPANSION MODULE,

LOGO! DM8 24R EXPANSION MODULE,

LOGO! DM8 12/24R, EXP. MODULE

LOGO! DM8 230R, EXP. MODULE,

Installation type/mounting

Mounting

on 35 mm DIN rail, 2 spacing units wide

on 35 mm DIN rail, 2 spacing units wide

on 35 mm DIN rail, 2 spacing units wide

on 35 mm DIN rail, 2 spacing units wide

Supply voltage

Rated value (DC)

  • ● 12 V DC

Yes

  • ● 24 V DC

Yes

Yes

Yes

  • ● 115 V DC

Yes

  • ● 230 V DC

Yes

permissible range, lower limit (DC)

20.4 V

20.4 V

10.8 V

100 V

permissible range, upper limit (DC)

28.8 V

28.8 V

28.8 V

253 V

Rated value (AC)

  • ● 24 V AC

Yes

  • ● 115 V AC

Yes

  • ● 230 V AC

Yes

Line frequency

  • ● permissible range, lower limit

47 Hz

47 Hz

  • ● permissible range, upper limit

63 Hz

63 Hz

Digital inputs

Number of digital inputs

4

4

4

4

Input voltage

  • ● Type of input voltage

DC

AC/DC

DC

AC/DC

  • ● for signal “0”

< 5 V DC

< 5 V AC/DC

< 5 V DC

< 40 V AC, < 30 V DC

  • ● for signal “1”

> 12 V DC

> 12 V AC/DC

> 8.5 V

> 79 V AC, > 79 V DC

Input current

  • ● for signal “0”, max. (permissible quiescent current)

0.88 mA

1.1 mA

0.88 mA

0.06 mA; 0.05 mA with AC, 0.06 mA with DC

  • ● for signal “1”, typ.

2.1 mA

2.63 mA

1.5 mA

0.13 mA

Input delay (for rated value of input voltage)

for standard inputs

  • — at “0” to “1”, max.

1.5 ms

1.5 ms

1.5 ms

40 ms

  • — at “1” to “0”, max.

1.5 ms

15 ms

1.5 ms

75 ms

Digital outputs

Number of digital outputs

4

4; Relays

4; Relays

4; Relays

Short-circuit protection

Yes

No

No

No

Controlling a digital input

Yes

Yes

Yes

Switching capacity of the outputs

  • ● on lamp load, max.

1 000 W

1 000 W

1 000 W; 500 W at 115V AC

Output current

  • ● for signal “1” rated value

0.3 A

5 A

5 A

5 A

  • ● for signal “1” minimum load current

100 mA

100 mA

100 mA

Parallel switching of two outputs

  • ● for uprating

No

No

No

No

Switching frequency

  • ● with resistive load, max.

10 Hz

2 Hz

2 Hz

2 Hz

  • ● with inductive load, max.

0.5 Hz

0.5 Hz

0.5 Hz

0.5 Hz

  • ● mechanical, max.

10 Hz

10 Hz

10 Hz

Relay outputs

Switching capacity of contacts

  • — with inductive load, max.

3 A

3 A

3 A

  • — with resistive load, max.

5 A

5 A

5 A

EMC

Emission of radio interference acc. to EN 55 011

  • ● Limit class B, for use in residential areas

Yes

Yes

Yes

Yes

Degree and class of protection

Degree of protection acc. to EN 60529

  • ● IP20

Yes

Yes

Yes

Yes

Standards, approvals, certificates

CE mark

Yes

Yes

Yes

Yes

CSA approval

Yes

Yes

Yes

Yes

UL approval

Yes

Yes

Yes

Yes

FM approval

Yes

Yes

Yes

Yes

developed in accordance with IEC 61131

Yes

Yes

Yes

Yes

according to VDE 0631

Yes

Yes

Yes

Marine approval

Yes

Yes

Yes

Yes

Ambient conditions

Ambient temperature during operation

  • ● min.

0 °C

0 °C

0 °C

0 °C

  • ● max.

55 °C

55 °C

55 °C

55 °C

Dimensions

Width

35.5 mm

35.5 mm

35.5 mm

35.5 mm

Height

90 mm

90 mm

90 mm

90 mm

Depth

58 mm

58 mm

58 mm

58 mm

Article number

6ED1055-1CB10-0BA2

6ED1055-1NB10-0BA2

6ED1055-1FB10-0BA2

LOGO! DM16 24, EXP. MODULE

LOGO! DM16 24R, EXP. MODULE,

LOGO! DM16 230R, EXP. MODULE,

Installation type/mounting

Mounting

on 35 mm DIN rail, 4 spacing units wide

on 35 mm DIN rail, 4 spacing units wide

on 35 mm DIN rail, 4 spacing units wide

Supply voltage

Rated value (DC)

  • ● 24 V DC

Yes

Yes

  • ● 115 V DC

Yes

  • ● 230 V DC

Yes

permissible range, lower limit (DC)

20.4 V

20.4 V

100 V

permissible range, upper limit (DC)

28.8 V

28.8 V

253 V

Rated value (AC)

  • ● 24 V AC

No

  • ● 115 V AC

Yes

  • ● 230 V AC

Yes

Line frequency

  • ● permissible range, lower limit

47 Hz

  • ● permissible range, upper limit

63 Hz

Digital inputs

Number of digital inputs

8

8

8

Input voltage

  • ● Type of input voltage

DC

DC

AC/DC

  • ● for signal “0”

< 5 V DC

< 5 V DC

< 40 V AC, < 30 V DC

  • ● for signal “1”

> 12 V DC

> 12 V DC

> 79 V AC, > 79 V DC

Input current

  • ● for signal “0”, max. (permissible quiescent current)

0.85 mA

0.85 mA

0.06 mA; 0.05 mA with AC, 0.06 mA with DC

  • ● for signal “1”, typ.

2 mA

2 mA

0.13 mA

Input delay (for rated value of input voltage)

for standard inputs

  • — at “0” to “1”, max.

1.5 ms

1.5 ms

40 ms

  • — at “1” to “0”, max.

1.5 ms

1.5 ms

75 ms

Digital outputs

Number of digital outputs

8

8; Relays

8; Relays

Short-circuit protection

Yes

No

No

Controlling a digital input

Yes

Yes

Switching capacity of the outputs

  • ● on lamp load, max.

1 000 W

1 000 W; 500 W at 115V AC

Output current

  • ● for signal “1” rated value

0.3 A

5 A

5 A

  • ● for signal “1” minimum load current

100 mA

100 mA

Parallel switching of two outputs

  • ● for uprating

No

No

No

Switching frequency

  • ● with resistive load, max.

10 Hz

2 Hz

2 Hz

  • ● with inductive load, max.

0.5 Hz

0.5 Hz

0.5 Hz

  • ● mechanical, max.

10 Hz

10 Hz

Relay outputs

Switching capacity of contacts

  • — with inductive load, max.

3 A

3 A

  • — with resistive load, max.

5 A

5 A

EMC

Emission of radio interference acc. to EN 55 011

  • ● Limit class B, for use in residential areas

Yes

Yes

Yes

Degree and class of protection

Degree of protection acc. to EN 60529

  • ● IP20

Yes

Yes

Yes

Standards, approvals, certificates

CE mark

Yes

Yes

Yes

CSA approval

Yes

Yes

Yes

UL approval

Yes

Yes

Yes

FM approval

Yes

Yes

Yes

developed in accordance with IEC 61131

Yes

Yes

Yes

according to VDE 0631

Yes

Yes

Yes

Marine approval

Yes

Yes

Yes

Ambient conditions

Ambient temperature during operation

  • ● min.

0 °C

0 °C

0 °C

  • ● max.

55 °C

55 °C

55 °C

Dimensions

Width

71.5 mm

71.5 mm

71.5 mm

Height

90 mm

90 mm

90 mm

Depth

58 mm

58 mm

58 mm

Article number

6ED1055-1MA00-0BA2

6ED1055-1MD00-0BA2

LOGO! AM2 EXPANSION MODULE,

LOGO! AM2 RDT, 2AI, -50..+200DECR/C

Installation type/mounting

Mounting

on 35 mm DIN rail, 2 spacing units wide

on 35 mm DIN rail, 2 spacing units wide

Supply voltage

Rated value (DC)

  • ● 12 V DC

Yes; 10.8 V DC to 28.8 V DC

Yes; 10.8 V DC to 28.8 V DC

  • ● 24 V DC

Yes; 10.8 V DC to 28.8 V DC

Yes; 10.8 V DC to 28.8 V DC

Analog inputs

Number of analog inputs

2

2; 2 or 3 wire connection

Input ranges

  • ● Voltage

Yes

No

  • ● Current

Yes

No

  • ● Resistance thermometer

No

Yes; For PT100/PT1000 sensors

Input ranges (rated values), voltages

  • ● 0 to +10 V

Yes

No

Input ranges (rated values), currents

  • ● 0 to 20 mA

Yes; 0 mA or 4 mA to 20 mA

No

Input ranges (rated values), resistance thermometer

  • ● Pt 100

No

Yes

EMC

Emission of radio interference acc. to EN 55 011

  • ● Limit class B, for use in residential areas

Yes

Yes

Degree and class of protection

Degree of protection acc. to EN 60529

  • ● IP20

Yes

Yes

Standards, approvals, certificates

CE mark

Yes

Yes

CSA approval

Yes

Yes

UL approval

Yes

Yes

FM approval

Yes

Yes

developed in accordance with IEC 61131

Yes

Yes

according to VDE 0631

Yes

Marine approval

Yes

Yes

Ambient conditions

Ambient temperature during operation

  • ● min.

0 °C

0 °C

  • ● max.

55 °C

55 °C

Dimensions

Width

35.5 mm

35.5 mm

Height

90 mm

90 mm

Depth

58 mm

58 mm

Article number

6ED1055-1MM00-0BA2

LOGO! AM2 AQ, 2AQ, 0-10V, 0/4-20MA

Installation type/mounting

Mounting

on 35 mm DIN rail, 2 spacing units wide

Supply voltage

Rated value (DC)

  • ● 12 V DC

No

  • ● 24 V DC

Yes

Analog outputs

Number of analog outputs

2

Output ranges, voltage

  • ● 0 to 10 V

Yes

Output ranges, current

  • ● 0 to 20 mA

Yes

  • ● 4 mA to 20 mA

Yes

EMC

Emission of radio interference acc. to EN 55 011

  • ● Limit class B, for use in residential areas

Yes

Degree and class of protection

Degree of protection acc. to EN 60529

  • ● IP20

Yes

Standards, approvals, certificates

CE mark

Yes

CSA approval

Yes

UL approval

Yes

FM approval

Yes

developed in accordance with IEC 61131

Yes

according to VDE 0631

Yes

Marine approval

Yes

Ambient conditions

Ambient temperature during operation

  • ● min.

0 °C

  • ● max.

55 °C

Dimensions

Width

35.5 mm

Height

90 mm

Depth

58 mm