SIEMENS SIMATIC WinAC – SIMATIC WinAC RTX F

SIMATIC WinAC RTX F

SIMATIC WinAC RTX F

  • SIMATIC WinAC RTX F:
    Optimized for applications that demand a high degree of flexibility and integration capability and that must also satisfy safety requirements up to SIL 3 (IEC 61508).
  • The software solution for tasks that require hard deterministic behavior and high performance.
  • With real-time expansion for assuring deterministic behavior for the control section.
  • Distributed I/O can be connected over PROFIBUS and/or PROFINET, also safety-related over PROFIsafe.

SIMATIC WinAC RTX F Product No. / Description

Product No. / Product Description Listprice / Your price
6ES7671-1RC08-0YA0
SIMATIC WINAC RTX F 2010, SINGLE LICENSE F. 1 INSTALL., R-SW, SW AND DOCU. ON DVD, LICENSE KEY ON USB STICK, CLASS A, 2 LANGUAGES (G,E), EXECUTABLE UNDER WINDOWS XP SP2, SP3 OR WINDOWS 7 32 BIT, INCL. INTERVALZERO RTX, REFERENCE-HW: SIMATIC PC
6ES7671-1RC08-0YE0
SIMATIC WINAC RTX F 2010 UPGR UPGRADE F. WINAC RTX F VERSION 2009, SINGLE LICENSE FOR 1 INSTALL., R-SW, SW AND DOCU. ON CD, LICENSE KEY ON USB STICK, CLASS A, 2 LANGUAGES (G,E), EXECUTABLE UNDER WINDOWS XP SP2, SP3 OR WINDOWS 7 32 BIT, INCL. INTERVALZERO RTX, REFERENCE-HW: SIMATIC PC

Application

WinAC RTX F is a fail-safe software controller approved by the German Technical Inspectorate for standard and safety-related applications. The STEP 7 option package “S7 Distributed Safety” is used for programming the safety-related (F) program part. SIMATIC WinAC RTX F is particularly suited to tasks requiring a high level of flexibility and effective integration in the overall solution. This also includes close interlinking with data processing systems or logistics systems and integration in the safety control.

WinAC RTX F is equally suited to implementation on cost-effective PC platforms with single-core processors and on high-end PCs, e.g. with QuadCore processors. WinAC RTX F is optimized for operation on embedded PC platforms such as the S7-modular Embedded Controller, the SIMATIC IPC427C, or the SIMATIC HMI IPC477C. These platforms offer, with their diskless and fanless design, significantly enhanced ruggedness for an automation task. Non-volatile memory is also available which permits storage of up to 512 KB retentive data (S7-mEX, EC31) on a voltage dip, independently of the file system. The I/O is connected via the leading fieldbus standards of PROFINET or PROFIBUS. With the S7-mEC, EC31, operation is also possible with the central signal modules (SM) of S7-300.
The support of the integral PROFINET or PROFIBUS interfaces of the SIMATIC IPCs, as well as the excellent performance result in an excellent price/performance ratio for the PC-based automation.

The WinAC ODK is used for expansion of the PLC functionality with application specific C/C++ applications. In the standard program part, it supports:

  • Integration of complex high-level language algorithms in the control program
  • Access to the Windows API or Windows system resources
  • Access to external HW and software components

Read-only access is permitted in the safety program part.


Design

SIMATIC WinAC RTX F comprises the following components:

  • Windows Failsafe Logic Controller (WinLC RTX F V4.6)
  • WinAC TimeSynchronization
  • SIMATIC NET SOFTNET-S7 Lean
  • Real-time driver for PROFINET and PROFIBUS interfaces
  • IntervalZero RTX real-time core for ensuring real-time and a deterministic response

Optional:

  • Interfaces for connection to PROFIBUS DP:
    • CP 5612 or the integral PROFIBUS interface of the SIMATIC IPC
    • CP 5622
    • CP 5613 A2
    • CP 5603
    • CP 5623
  • Interfaces for connection to PROFINET:
    • CP 1616 (HW version 8 and above) or integral CP 161 onboard interface of the SIMATIC IPC
    • Integral CP 1616 onboard interfaces of the SIMATIC IPC
    • Integrated standard Ethernet interfaces of selected SIMATIC IPCs (e.g. SIMATIC IPC427D and HMI IPC477D)
  • WinAC Open Development Kit (ODK):
    • For integrating C/C++ code in WinAC RTX
    • Integration of external software (technology programs) or PC components (e.g. barcode scanner, PC cards for measured value acquisition)

Benefits

  • Hard real-time and maximum performance up to SIL 3 according to IEC 61508/62061 or according to EN ISO 13849-1 up to PL e
  • Implementation of fast, S7-compatible control solutions with low processor loading.
    Alongside the control task, sufficient processor capability is available for processing complex, demanding PC applications in parallel.

Function

Windows Failsafe Logic Controller (WinLC RTX F)

The Windows Failsafe Logic Controller is responsible for the actual control job and execution of the control program. It coordinates the associated input and output of process values via the lower-level PROFINET or PROFIBUS fieldbus system and makes the process values available for visualization and data processing tasks.

Fail-safe programs are created with the STEP 7 option package S7 Distributed Safety.

A safety control can be built up using fail-safe signal modules. This opens up

  • Classical safety applications in the field of machine safety and press automation as well as
  • Applications in process engineering and chemicals.

The I/O can be connected over PROFINET IO or PROFIBUS DP. The PROFIsafe profile supports fail-safe communication over the fieldbuses for this purpose.

The functional safety is implemented by means of targeted safety functions in the software. Safety functions are implemented with S7 Distributed Safety, to place the plant in a safe state or to hold it in a safe state. The safety functions are mainly contained within the following components:

  • In the safety-related user program (safety program) in WinLC RTX F
  • In the fail-safe inputs and outputs (F I/O).

The F I/O ensures safety-related processing of the field information (emergency stop pushbutton, light barriers, motor pre-control). It features all the hardware and software components required for reliable processing, according to the required safety class.

The user only programs the user safety functions. The safety functions for the process can be implemented with a user safety function or a system-internal fault reaction function. If the F system is unable to execute the actual user safety function, it will execute the fault response function: e.g. deactivation of the associated outputs and, if appropriate, F-CPU in STOP.

Interface to visualization

SIMATIC WinAC RTX F is easy to use with the SIMATIC HMI systems SIMATIC WinCC flexible or SIMATIC WinCC.

Visualization systems from third-party suppliers can be connected via the included SIMATIC NET OPC server.

Communication

The programming of the Windows Logic Controller with STEP 7 and also the visualization with SIMATIC HMI can be implemented both locally in the same PC and remotely using the standard SIMATIC networks Ethernet or PROFIBUS.

WinAC RTX F can exchange data via these networks:

  • With additional WinAC stations
  • With S7 controllers as well as
  • With safety-oriented S7 controllers (safe PLC-to-PLC communication)

A SOFTNET S7 Lean license is included for Industrial Ethernet communication over the integral Ethernet interfaces of the SIMATIC PC.

SIMATIC WinAC RTX F Technical specifications

Article number

6ES7671-1RC08-0YA0

SIMATIC WINAC RTX F 2010

General information

Firmware version

V4.6

Engineering with

  • ● Programming package

STEP 7 V5.5 or higher + S7 Distributed Safety V5.4 SP5 or higher + S7 F Configuration Pack V5.5 SP6 HF1 / iMap V3.0 SP1; STEP 7 in TIA Portal V13 or higher + STEP 7 Safety Advanced V13

Memory

Type of memory

RAM

Work memory

  • ● integrated (for program)

4 Mbyte; Adjustable; depends on Non Paged Memory Pool

  • ● integrated (for data)

4 Mbyte; Adjustable; depends on Non Paged Memory Pool

Load memory

  • ● integrated RAM, max.

Adjustable; depends on Non Paged Memory Pool

CPU processing times

for bit operations, typ.

0.004 µs; Typical

for fixed point arithmetic, typ.

0.003 µs; Typical

for floating point arithmetic, typ.

0.004 µs; Typical

Reference platform

Pentium 4, 2.4 GHz

CPU-blocks

DB

  • ● Number, max.

65 535; Limited only by RAM set for data

  • ● Size, max.

64 kbyte

FB

  • ● Number, max.

65 536; Limited only by RAM set for code

  • ● Size, max.

64 kbyte

FC

  • ● Number, max.

65 536; Limited only by RAM set for code

  • ● Size, max.

64 kbyte

OB

  • ● Number, max.

Limited only by RAM set for code

  • ● Size, max.

64 kbyte

  • ● Number of free cycle OBs

1; OB 1

  • ● Number of time alarm OBs

1; OB 10

  • ● Number of delay alarm OBs

1; OB 20

  • ● Number of cyclic interrupt OBs

9; OB 30-38

  • ● Number of process alarm OBs

1; OB 40

  • ● Number of ODK OBs

3; OB 52-54

  • ● Number of DPV1 alarm OBs

3; OB 55-57

  • ● Number of isochronous mode OBs

2; OB 61-62

  • ● Number of startup OBs

2; OB 100, 102

  • ● Number of asynchronous error OBs

7; OB 80, 82-85, 86, 88

  • ● Number of synchronous error OBs

2; OB 121, 122

Nesting depth

  • ● per priority class

24

  • ● additional within an error OB

24

Counters, timers and their retentivity

S7 counter

  • ● Number

2 048

Retentivity

  • — adjustable

Yes

  • — lower limit

0

  • — upper limit

2 047

  • — preset

8

Counting range

  • — can be set

Yes

  • — lower limit

0

  • — upper limit

999

IEC counter

  • ● Number

Unlimited (limited only by RAM capacity)

S7 times

  • ● Number

2 048

Retentivity

  • — adjustable

Yes

  • — lower limit

0

  • — upper limit

2 047

  • — preset

0

Time range

  • — lower limit

10 ms

  • — upper limit

9 990 s

IEC timer

  • ● present

Yes

  • ● Type

SFB

  • ● Number

Unlimited (limited only by RAM capacity)

Data areas and their retentivity

Retentivity without UPS and PS Extension Board

128 kbyte with SIMATIC IPC427C and HMI IPC477C; further SIMATIC PCs on request

Retentivity with UPS

all data

Flag

  • ● Number, max.

16 kbyte

  • ● of which retentive

MB 0 to MB 16383

  • ● Retentivity preset

MB 0 to MB 15

  • ● Number of clock memories

8

Data blocks

  • ● Number, max.

Limited only by available retentive memory (NVRAM, or file storage)

  • ● Size, max.

64 kbyte

  • ● Retentivity adjustable

Yes; via non-retain property on DB

  • ● Retentivity preset

Yes

Local data

  • ● adjustable, max.

64 kbyte

  • ● preset

32 kbyte

  • ● per priority class, max.

61 440 byte

Address area

I/O address area

  • ● Inputs

16 kbyte

  • ● Outputs

16 kbyte

of which distributed

  • — DP interface, inputs

16 kbyte

  • — DP interface, outputs

16 kbyte

  • — PROFINET interface, inputs

16 kbyte

  • — PROFINET interface, outputs

16 kbyte

Process image

  • ● Inputs, adjustable

8 kbyte

  • ● Outputs, adjustable

8 kbyte

  • ● Inputs, default

512 byte

  • ● Outputs, default

512 byte

Subprocess images

  • ● Number of subprocess images, max.

15

Digital channels

  • ● Inputs

128 000

  • ● Outputs

128 000

Analog channels

  • ● Inputs

8 000

  • ● Outputs

8 000

Number of operable FMs and CPs (recommended)

  • ● FM

4; FM distributed: FM 350-1, FM 350-2, FM 351, FM 352 / FM 352-5, FM 353, FM 354, FM 355, FM 355-2

  • ● CP, PtP

2; CP 340, CP 341 distributed

  • ● CP, LAN

Over PC CP

Submodules

  • ● Number of submodules, max

4

  • — of which PROFIBUS, max.

4; Supported interfaces: see 1st and 2nd interface

  • — of which Industrial Ethernet, max.

1; Supported interfaces: see 3rd and 4th interface

Time of day

Clock

  • ● Hardware clock (real-time)

Yes

  • ● retentive and synchronizable

Yes

Operating hours counter

  • ● Number

8

Clock synchronization

  • ● supported

Yes

  • ● to PC-CP, slave

Yes

  • ● on Ethernet via NTP

Yes

1. Interface

Interface type

CP 5611-A2, CP 5621, integrated PROFIBUS interface of the SIMATIC PC

Physics

RS 485 / PROFIBUS

Isolated

Yes

Number of simultaneously operable CPs, max.

1

Power supply to interface (15 to 30 V DC), max.

does not exist

Functionality

  • ● MPI

No

  • ● PROFIBUS DP master

Yes

  • ● PROFIBUS DP slave

No

DP master

  • ● Number of connections, max.

8

  • ● Transmission rate, max.

12 Mbit/s

  • ● Number of DP slaves, max.

64

Services

  • — PG/OP communication

Yes

  • — Routing

Yes

  • — Global data communication

No

  • — S7 basic communication

No

  • — S7 communication

Yes

  • — S7 communication, as client

Yes

  • — S7 communication, as server

Yes

  • — Equidistance

Yes; Only in conjunction with isochronous mode

  • — Isochronous mode

Yes

  • — SYNC/FREEZE

Yes

  • — Activation/deactivation of DP slaves

Yes

  • — Direct data exchange (slave-to-slave communication)

Yes

  • — DPV0

Yes

  • — DPV1

Yes

Address area

  • — Inputs, max.

16 kbyte

  • — Outputs, max.

16 kbyte

User data per DP slave

  • — Inputs, max.

244 byte

  • — Outputs, max.

244 byte

2. Interface

Interface type

CP 5613, CP 5613-A2, CP 5603, CP 5623

Physics

RS 485 / PROFIBUS

Isolated

Yes

Number of simultaneously operable CPs, max.

4

Functionality

  • ● MPI

No

  • ● PROFIBUS DP master

Yes

  • ● PROFIBUS DP slave

No

DP master

  • ● Number of connections, max.

50

  • ● Transmission rate, max.

12 Mbit/s

  • ● Number of DP slaves, max.

125

Services

  • — PG/OP communication

Yes

  • — Routing

Yes

  • — Global data communication

No

  • — S7 basic communication

No

  • — S7 communication

Yes

  • — S7 communication, as client

Yes

  • — S7 communication, as server

Yes

  • — Equidistance

Yes; Only in conjunction with isochronous mode

  • — Isochronous mode

Yes

  • — SYNC/FREEZE

Yes

  • — Activation/deactivation of DP slaves

Yes

  • — Direct data exchange (slave-to-slave communication)

Yes

  • — DPV0

Yes

  • — DPV1

Yes

Address area

  • — Inputs, max.

16 kbyte

  • — Outputs, max.

16 kbyte

User data per DP slave

  • — Inputs, max.

244 byte

  • — Outputs, max.

244 byte

3. Interface

Interface type

PROFINET

Physics

Ethernet

Isolated

Yes

Number of simultaneously operable CPs, max.

1; Intel Pro/1000 (Intel 82571EB, 82573L, 82574L, 82541PI; non-shared IRQ required); integrated IE interface SIMATIC PC 4x7B, 6x7B, 8x7B, IPC4x7C, IPC6x7C, IPC8x7C

automatic detection of transmission rate

Yes; 10/100 Mbit/s

Autonegotiation

Yes

Autocrossing

Yes

Interface types

  • ● Number of ports

1

  • ● integrated switch

No

Media redundancy

  • ● supported

No

Functionality

  • ● PROFINET IO Controller

Yes

  • ● PROFINET IO Device

No

  • ● PROFINET CBA

Yes

  • ● Open IE communication

Yes

PROFINET IO Controller

  • ● Transmission rate, max.

100 Mbit/s

Services

  • — PG/OP communication

Yes

  • — S7 routing

Yes

  • — S7 communication

Yes

  • — Isochronous mode

No

  • — Open IE communication

Yes

  • — IRT

No

  • — Prioritized startup

Yes

  • — Number of IO devices with prioritized startup, max.

32

  • — Number of connectable IO Devices, max.

128

  • — Number of connectable IO Devices for RT, max.

128

  • — of which in line, max.

128

  • — Activation/deactivation of IO Devices

Yes

  • — Number of IO Devices that can be simultaneously activated/deactivated, max.

8

  • — IO Devices changing during operation (partner ports), supported

Yes

  • — Device replacement without swap medium

Yes

  • — Send cycles

1 ms

  • — Updating time

1 to 512 ms (minimum value depends on communication share set for PROFINET I/O, on the number of I/O devices, and on the volume of configured user data)

Address area

  • — Inputs, max.

16 kbyte

  • — Outputs, max.

16 kbyte

  • — User data per address area, max.

2 kbyte

  • — User data consistency, max.

254 byte

PROFINET CBA

  • ● acyclic transmission

Yes

  • ● cyclic transmission

Yes

Open IE communication

  • ● Number of connections, max.

32

  • ● Local port numbers used at the system end

0, 20, 21, 23, 25, 80, 102, 135, 161, 8080, 34962, 34963, 34964, 65532, 65533, 65534, 65535

  • ● Keep-alive function, supported

Yes

SIMATIC communication

  • ● Number of connections, max.

16

4. Interface

Interface type

PROFINET

Physics

Ethernet

Isolated

Yes

Number of simultaneously operable CPs, max.

1; CP 1616 (HW release 8 or above), CP 1604 (HW release 7 or higher), integrated PROFINET interface of SIMATIC PC and S7-mEC

automatic detection of transmission rate

Yes; 10/100 Mbit/s

Autonegotiation

Yes

Autocrossing

Yes

Change of IP address at runtime, supported

Yes

Interface types

  • ● Number of ports

3

  • ● integrated switch

Yes

Media redundancy

  • ● supported

Yes

  • ● Switchover time on line break, typ.

200 ms

  • ● Number of stations in the ring, max.

50

Functionality

  • ● PROFINET IO Controller

Yes

  • ● PROFINET IO Device

No

  • ● PROFINET CBA

Yes

  • ● Open IE communication

Yes

  • ● Web server

Yes

PROFINET IO Controller

  • ● Transmission rate, max.

100 Mbit/s

Services

  • — PG/OP communication

Yes

  • — S7 routing

Yes

  • — S7 communication

Yes

  • — Isochronous mode

Yes

  • — Open IE communication

Yes

  • — IRT

Yes

  • — Prioritized startup

Yes

  • — Number of IO devices with prioritized startup, max.

32

  • — Number of connectable IO Devices, max.

256

  • — Of which IO devices with IRT, max.

64

  • — of which in line, max.

64

  • — Number of IO Devices with IRT and the option “high flexibility”

64

  • — of which in line, max.

32

  • — Number of connectable IO Devices for RT, max.

256

  • — of which in line, max.

256

  • — Activation/deactivation of IO Devices

Yes

  • — Number of IO Devices that can be simultaneously activated/deactivated, max.

8

  • — IO Devices changing during operation (partner ports), supported

Yes

  • — Device replacement without swap medium

Yes

  • — Send cycles

250 µs, 500 µs, 1 ms

Address area

  • — User data per address area, max.

2 kbyte

Open IE communication

  • ● Number of connections, max.

32

  • ● Local port numbers used at the system end

0, 20, 21, 25, 80, 102, 135, 161, 34962, 34963, 34964, 65532, 65533, 65534, 65535

SIMATIC communication

  • ● Number of connections, max.

32

Protocols

Open IE communication

  • ● TCP/IP

  • — Number of connections, max.

32

  • — Data length for connection type 01H, max.

Not supported

  • — Data length for connection type 11H, max.

65 534 byte

  • — Data length, max.

65 534 byte

  • ● ISO-on-TCP (RFC1006)

Yes

  • — Number of connections, max.

32

  • — Data length, max.

65 534 byte

  • ● UDP

  • — Number of connections, max.

32

  • — Data length, max.

1 472 byte

Isochronous mode

Isochronous operation (application synchronized up to terminal)

Yes

Equidistance

Yes

Number of DP masters with isochronous mode

2

User data per isochronous slave, max.

128 byte

shortest clock pulse

2.2 ms; 2.2 ms without partial process image; 2.2 ms with partial process image

Communication functions

PG/OP communication

Yes

Data record routing

Yes; only with CP 5611 or integrated PROFIBUS interface of the SIMATIC PC

Global data communication

  • ● supported

No

S7 basic communication

  • ● supported

No

S7 communication

  • ● supported

Yes

  • ● as server

Yes

  • ● as client

Yes

  • ● User data per job, max.

64 kbyte; Depends on which block is used: BSEND/USEND or PUT/GET

Open IE communication

  • ● TCP/IP

Yes

  • ● UDP

Yes

Web server

  • ● supported

Yes

  • ● Number of HTTP clients

2

  • ● User-defined websites

No

PROFINET CBA (at set setpoint communication load)

  • ● Setpoint for the CPU communication load

20 %

  • ● Number of remote interconnection partners

64

  • ● Number of functions, master/slave

30

  • ● Total of all master/slave connections

1 000

  • ● Data length of all incoming connections master/slave, max.

6 800 byte

  • ● Data length of all outgoing connections master/slave, max.

6 800 byte

  • ● Number of device-internal and PROFIBUS interconnections

500

  • ● Data length of device-internal und PROFIBUS interconnections, max.

4 000 byte

  • ● Data length per connection, max.

1 400 byte

Remote interconnections with acyclic transmission

  • — Sampling frequency: Sampling time, min.

500 ms

  • — Number of incoming interconnections

100

  • — Number of outgoing interconnections

100

  • — Data length of all incoming interconnections, max.

2 000 byte

  • — Data length of all outgoing interconnections, max.

2 000 byte

  • — Data length per connection, max.

1 400 byte

Remote interconnections with cyclic transmission

  • — Transmission frequency: Transmission interval, min.

10 ms

  • — Number of incoming interconnections

200

  • — Number of outgoing interconnections

200

  • — Data length of all incoming interconnections, max.

4 800 byte

  • — Data length of all outgoing interconnections, max.

4 800 byte

  • — Data length per connection, max.

250 byte

HMI variables via PROFINET (acyclic)

  • — Number of stations that can log on for HMI variables (PN OPC/iMap)

3

  • — HMI variable updating

500 ms

  • — Number of HMI variables

200

  • — Data length of all HMI variables, max.

2 000 byte

PROFIBUS proxy functionality

  • — supported

Yes

  • — Number of linked PROFIBUS devices

16

  • — Data length per connection, max.

240 byte; Slave-dependent

Number of connections

  • ● overall

96

  • ● usable for PG communication

  • — reserved for PG communication

1

  • ● usable for OP communication

  • — reserved for OP communication

1

S7 message functions

Number of login stations for message functions, max.

62

SCAN procedure

No

Process diagnostic messages

Yes; ALARM_S, ALARM_SQ, ALARM_D, ALARM_DQ

simultaneously active Alarm-S blocks, max.

20; of a total of 20 for all SFCs

Alarm 8-blocks

Yes

  • ● Number of instances for alarm 8 and S7 communication blocks, max.

4 000

Process control messages

No

Test commissioning functions

Status block

Yes

Single step

Yes

Number of breakpoints

20

Status/control

  • ● Status/control variable

Yes

Forcing

  • ● Forcing

No

Diagnostic buffer

  • ● present

Yes

  • ● Number of entries, max.

  • — adjustable

Yes

  • — preset

120

Hardware requirement

Hardware required

PC with color monitor, keyboard, mouse or pointing device for Windows

Processor

  • ● Processor

Intel Celeron M 900 MHz or compatible (older PC systems with Programmable Interrupt Controllers (PIC) are not suitable for WinAC RTX F 2010.)

  • — Multi-processor system

No

  • — Hyper-threading

Yes

Lifetime of module

  • ● Main memory, min.

1 Gbyte

  • ● Required memory on hard disk

100 Mbyte

Operating systems

pre-installed operating system

  • ● Windows NT 4.0

No

  • ● Windows 2000

No

  • ● Windows Vista

No

  • ● Windows XP

Yes; Professional, SP2 and SP3

  • ● Windows XP Embedded

Yes; With the delivery image of the SIMATIC PC

  • — supported HAL types under Windows XP

ACPI uniprocessor PC, ACPI multiprocessor PC, MPS multiprocessor PC

  • ● Windows 7

Yes; Professional, Enterprise, Ultimate (only 32 bits)

  • ● Windows Embedded Standard 7

No

Configuration

Configuration software

  • ● STEP 7

Yes; As of V5.5 + HW update/S7 F Configuration Pack V5.5 + SP6 + HF1/option package S7 Distributed Safety V5.4 + SP5 or later

Programming

  • ● Nesting levels

8

Programming language

  • — LAD

Yes

  • — FBD

Yes

  • — STL

Yes

  • — SCL

Yes

  • — CFC

Yes

  • — GRAPH

Yes

  • — HiGraph®

Yes

Software libraries

  • — Easy Motion Control

Yes

  • — Software redundancy

Yes; As of V1.2, only for operation of WinAC RTX (F) with WinAC RTX (F)

Number of simultaneously active SFCs

  • — DPSYC_FR

20; of a total of 20 for all SFCs

  • — D_ACT_DP

20; of a total of 20 for all SFCs

  • — RD_REC

20; of a total of 20 for all SFCs

  • — WR_REC

20; of a total of 20 for all SFCs

  • — WR_PARM

20; of a total of 20 for all SFCs

  • — PARM_MOD

20; of a total of 20 for all SFCs

  • — WR_DPARM

20; of a total of 20 for all SFCs

  • — DPNRM_DG

20; of a total of 20 for all SFCs

  • — RDSYSST

20; of a total of 20 for all SFCs

Number of simultaneously active SFBs

  • — RDREC

20; of a total of 20 for all SFBs

  • — WRREC

20; of a total of 20 for all SFBs

Know-how protection

  • ● User program protection/password protection

Yes

  • ● Block encryption

No

Open Development interfaces

  • ● CCX (Custom Code Extension)

Yes; WinAC ODK V4.2 or higher

  • ● CMI (Controller Management Interface)

Yes; WinAC ODK V4.2 or higher

  • ● SMX (Shared Memory Extension)

Yes; WinAC ODK V4.2 or higher

  • — Inputs

4 kbyte

  • — Outputs

4 kbyte

Peripherals/Options

Peripherals

none

  • ● Printer

No

Weights

Weight, approx.

100 g; With packaging