SIEMENS SINAMICS G150 Drive converter cabinet units

SINAMICS G150

SINAMICS G150 converter cabinet units, versions A and C

With its SINAMICS G150 converter cabinet units, a drive system is available on which all line-side and motor-side components are integrated together with the Power Module extremely compact into a specially designed cabinet enclosure. This approach minimizes the effort and expense required to configure and install them.

SINAMICS G150 has been specially designed to meet the requirements of drives with square-wave and constant load characteristics, with medium performance requirements, and without regenerative feedback capability.

The control accuracy of the sensorless vector control is suitable for most applications, which means that an additional actual speed value encoder is not required.

SINAMICS G150 converter cabinet units are optionally available with an encoder evaluation function in order to handle applications that require an encoder for plant-specific reasons.

SINAMICS G150 converter cabinet units offer an economic drive solution that can be adapted to customer-specific requirements through a wide range of components and options.

SINAMICS G150 is available in two versions:

  • Version A
    All optionally available line connection components, such as the main switch, circuit breakers, line contactor, line fuses, line filter or motor-side components and additional monitoring devices, can be installed as required. This version is also available with power units connected in parallel.
  • Version C
    Offers an extremely space-optimized structure without line-side components. This particularly slimline version can be used, for example, when line connection components are accommodated in a central low-voltage distribution panel (MCC) in the plant.

The following voltages and power ratings are available:

Line voltage

Power range
single connection

(versions A and C)

Power range
parallel connection

(version A)

380 … 480 V 3 AC

110 … 560 kW

630 … 900 kW

500 … 600 V 3 AC

110 … 560 kW

630 … 1000 kW

660 … 690 V 3 AC

75 … 800 kW

1000 … 2700 kW

Degrees of protection are IP20 (standard) and optionally IP21, IP23, IP43 and IP54.

SIEMENS SINAMICS G150 AC Drives Ordering data

Product No. / Product DescriptionListprice / Your price
6SL3710-1GE32-1AA3
SINAMICS G150 CONVERTER CABINET UNIT, AC/AC WITH CIM+CU320-2 3AC 380-480 V, 50/60 HZ NOM. POWER RATING: 110 KW 6-PULSE SYSTEM WITHOUT REGENERATIVE FEEDBACK VERSION A, INCL. EMV-FILTER 2. AMB. CONDITION, CATEGORY C3
6SL3710-1GE32-1CA3
SINAMICS G150 CONVERTER CABINET UNIT, AC/AC WITH CIM+CU320-2 3AC 380-480 V, 50/60 HZ NOM. POWER RATING: 110 KW 6-PULSE SYSTEM WITHOUT REGENERATIVE FEEDBACK VERSION C, INCL. EMV-FILTER 2. AMB. CONDITION, CATEGORY C3
6SL3710-1GE32-6AA3
SINAMICS G150 CONVERTER CABINET UNIT, AC/AC WITH CIM+CU320-2 3AC 380-480 V, 50/60 HZ NOM. POWER RATING: 132 KW 6-PULSE SYSTEM WITHOUT REGENERATIVE FEEDBACK VERSION A, INCL. EMV-FILTER 2. AMB. CONDITION, CATEGORY C3
6SL3710-1GE32-6CA3
SINAMICS G150 CONVERTER CABINET UNIT, AC/AC WITH CIM+CU320-2 3AC 380-480 V, 50/60 HZ NOM. POWER RATING: 132 KW 6-PULSE SYSTEM WITHOUT REGENERATIVE FEEDBACK VERSION C, INCL. EMV-FILTER 2. AMB. CONDITION, CATEGORY C3
6SL3710-1GE33-1AA3
SINAMICS G150 CONVERTER CABINET UNIT, AC/AC WITH CIM+CU320-2 3AC 380-480 V, 50/60 HZ NOM. POWER RATING: 160 KW 6-PULSE SYSTEM WITHOUT REGENERATIVE FEEDBACK VERSION A, INCL. EMV-FILTER 2. AMB. CONDITION, CATEGORY C3
6SL3710-1GE33-1CA3
SINAMICS G150 CONVERTER CABINET UNIT, AC/AC WITH CIM+CU320-2 3AC 380-480 V, 50/60 HZ NOM. POWER RATING: 160 KW 6-PULSE SYSTEM WITHOUT REGENERATIVE FEEDBACK VERSION C, INCL. EMV-FILTER 2. AMB. CONDITION, CATEGORY C3
6SL3710-1GE33-8AA3
SINAMICS G150 CONVERTER CABINET UNIT, AC/AC WITH CIM+CU320-2 3AC 380-480 V, 50/60 HZ NOM. POWER RATING: 200 KW 6-PULSE SYSTEM WITHOUT REGENERATIVE FEEDBACK VERSION A, INCL. EMV-FILTER 2. AMB. CONDITION, CATEGORY C3
6SL3710-1GE33-8CA3
SINAMICS G150 CONVERTER CABINET UNIT, AC/AC WITH CIM+CU320-2 3AC 380-480 V, 50/60 HZ NOM. POWER RATING: 200 KW 6-PULSE SYSTEM WITHOUT REGENERATIVE FEEDBACK VERSION C, INCL. EMV-FILTER 2. AMB. CONDITION, CATEGORY C3
6SL3710-1GE35-0AA3
SINAMICS G150 CONVERTER CABINET UNIT, AC/AC WITH CIM+CU320-2 3AC 380-480 V, 50/60 HZ NOM. POWER RATING: 250 KW 6-PULSE SYSTEM WITHOUT REGENERATIVE FEEDBACK VERSION A, INCL. EMV-FILTER 2. AMB. CONDITION, CATEGORY C3
6SL3710-1GE35-0CA3
SINAMICS G150 CONVERTER CABINET UNIT, AC/AC WITH CIM+CU320-2 3AC 380-480 V, 50/60 HZ NOM. POWER RATING: 250 KW 6-PULSE SYSTEM WITHOUT REGENERATIVE FEEDBACK VERSION C, INCL. EMV-FILTER 2. AMB. CONDITION, CATEGORY C3
Product No. / Product DescriptionListprice / Your price
6SL3710-1GE36-1AA3
SINAMICS G150 CONVERTER CABINET UNIT, AC/AC WITH CIM+CU320-2 3AC 380-480 V, 50/60 HZ NOM. POWER RATING: 315 KW 6-PULSE SYSTEM WITHOUT REGENERATIVE FEEDBACK VERSION A, INCL. EMV-FILTER 2. AMB. CONDITION, CATEGORY C3
6SL3710-1GE36-1CA3
SINAMICS G150 CONVERTER CABINET UNIT, AC/AC WITH CIM+CU320-2 3AC 380-480 V, 50/60 HZ NOM. POWER RATING: 315 KW 6-PULSE SYSTEM WITHOUT REGENERATIVE FEEDBACK VERSION C, INCL. EMV-FILTER 2. AMB. CONDITION, CATEGORY C3
6SL3710-1GE37-5AA3
SINAMICS G150 CONVERTER CABINET UNIT, AC/AC WITH CIM+CU320-2 3AC 380-480 V, 50/60 HZ NOM. POWER RATING: 400 KW 6-PULSE SYSTEM WITHOUT REGENERATIVE FEEDBACK VERSION A, INCL. EMV-FILTER 2. AMB. CONDITION, CATEGORY C3
6SL3710-1GE37-5CA3
SINAMICS G150 CONVERTER CABINET UNIT, AC/AC WITH CIM+CU320-2 3AC 380-480 V, 50/60 HZ NOM. POWER RATING: 400 KW 6-PULSE SYSTEM WITHOUT REGENERATIVE FEEDBACK VERSION C, INCL. EMV-FILTER 2. AMB. CONDITION, CATEGORY C3
6SL3710-1GE38-4AA3
SINAMICS G150 CONVERTER CABINET UNIT, AC/AC WITH CIM+CU320-2 3AC 380-480 V, 50/60 HZ NOM. POWER RATING: 450 KW 6-PULSE SYSTEM WITHOUT REGENERATIVE FEEDBACK VERSION A, INCL. EMV-FILTER 2. AMB. CONDITION, CATEGORY C3
6SL3710-1GE38-4CA3
SINAMICS G150 CONVERTER CABINET UNIT, AC/AC WITH CIM+CU320-2 3AC 380-480 V, 50/60 HZ NOM. POWER RATING: 450 KW 6-PULSE SYSTEM WITHOUT REGENERATIVE FEEDBACK VERSION C, INCL. EMV-FILTER 2. AMB. CONDITION, CATEGORY C3
6SL3710-1GE41-0AA3
SINAMICS G150 CONVERTER CABINET UNIT, AC/AC WITH CIM+CU320-2 3AC 380-480 V, 50/60 HZ NOM. POWER RATING: 560 KW 6-PULSE SYSTEM WITHOUT REGENERATIVE FEEDBACK VERSION A, INCL. EMV-FILTER 2. AMB. CONDITION, CATEGORY C3
6SL3710-1GE41-0CA3
SINAMICS G150 CONVERTER CABINET UNIT, AC/AC WITH CIM+CU320-2 3AC 380-480 V, 50/60 HZ NOM. POWER RATING: 560 KW 6-PULSE SYSTEM WITHOUT REGENERATIVE FEEDBACK VERSION C, INCL. EMV-FILTER 2. AMB. CONDITION, CATEGORY C3
6SL3710-1GF31-8AA3
SINAMICS G150 CONVERTER CABINET UNIT, AC/AC WITH CIM+CU320-2 3AC 500-600V, 50/60HZ NOM. POWER RATING: 110KW 6-PULSE SYSTEM WITHOUT REGENERATIVE FEEDBACK VERSION A, INKL. EMV-FILTER 2. AMB. CONDITION, CATEGORY C3
6SL3710-1GF31-8CA3
SINAMICS G150 CONVERTER CABINET UNIT, AC/AC WITH CIM+CU320-2 3AC 500-600V, 50/60HZ NOM. POWER RATING: 110KW 6-PULSE SYSTEM WITHOUT REGENERATIVE FEEDBACK VERSION A, INKL. EMV-FILTER 2. AMB. CONDITION, CATEGORY C3
Product No. / Product DescriptionListprice / Your price
6SL3710-1GF32-2AA3
SINAMICS G150 CONVERTER CABINET UNIT, AC/AC WITH CIM+CU320-2 3AC 500-600V, 50/60HZ NOM. POWER RATING: 132KW 6-PULSE SYSTEM WITHOUT REGENERATIVE FEEDBACK VERSION A, INKL. EMV-FILTER 2. AMB. CONDITION, CATEGORY C3
6SL3710-1GF32-2CA3
SINAMICS G150 CONVERTER CABINET UNIT, AC/AC WITH CIM+CU320-2 3AC 500-600V, 50/60HZ NOM. POWER RATING: 132KW 6-PULSE SYSTEM WITHOUT REGENERATIVE FEEDBACK VERSION A, INKL. EMV-FILTER 2. AMB. CONDITION, CATEGORY C3
6SL3710-1GF32-6AA3
SINAMICS G150 CONVERTER CABINET UNIT, AC/AC WITH CIM+CU320-2 3AC 500-600V, 50/60HZ NOM. POWER RATING: 160KW 6-PULSE SYSTEM WITHOUT REGENERATIVE FEEDBACK VERSION A, INKL. EMV-FILTER 2. AMB. CONDITION, CATEGORY C3
6SL3710-1GF32-6CA3
SINAMICS G150 CONVERTER CABINET UNIT, AC/AC WITH CIM+CU320-2 3AC 500-600V, 50/60HZ NOM. POWER RATING: 160KW 6-PULSE SYSTEM WITHOUT REGENERATIVE FEEDBACK VERSION A, INKL. EMV-FILTER 2. AMB. CONDITION, CATEGORY C3
6SL3710-1GF33-3AA3
SINAMICS G150 CONVERTER CABINET UNIT, AC/AC WITH CIM+CU320-2 3AC 500-600V, 50/60HZ NOM. POWER RATING: 200KW 6-PULSE SYSTEM WITHOUT REGENERATIVE FEEDBACK VERSION A, INKL. EMV-FILTER 2. AMB. CONDITION, CATEGORY C3
6SL3710-1GF33-3CA3
SINAMICS G150 CONVERTER CABINET UNIT, AC/AC WITH CIM+CU320-2 3AC 500-600V, 50/60HZ NOM. POWER RATING: 200KW 6-PULSE SYSTEM WITHOUT REGENERATIVE FEEDBACK VERSION A, INKL. EMV-FILTER 2. AMB. CONDITION, CATEGORY C3
6SL3710-1GF34-1AA3
SINAMICS G150 CONVERTER CABINET UNIT, AC/AC WITH CIM+CU320-2 3AC 500-600V, 50/60HZ NOM. POWER RATING: 250KW 6-PULSE SYSTEM WITHOUT REGENERATIVE FEEDBACK VERSION A, INKL. EMV-FILTER 2. AMB. CONDITION, CATEGORY C3
6SL3710-1GF34-1CA3
SINAMICS G150 CONVERTER CABINET UNIT, AC/AC WITH CIM+CU320-2 3AC 500-600V, 50/60HZ NOM. POWER RATING: 250KW 6-PULSE SYSTEM WITHOUT REGENERATIVE FEEDBACK VERSION A, INKL. EMV-FILTER 2. AMB. CONDITION, CATEGORY C3
6SL3710-1GF34-7AA3
SINAMICS G150 CONVERTER CABINET UNIT, AC/AC WITH CIM+CU320-2 3AC 500-600V, 50/60HZ NOM. POWER RATING: 315KW 6-PULSE SYSTEM WITHOUT REGENERATIVE FEEDBACK VERSION A, INKL. EMV-FILTER 2. AMB. CONDITION, CATEGORY C3
6SL3710-1GF34-7CA3
SINAMICS G150 CONVERTER CABINET UNIT, AC/AC WITH CIM+CU320-2 3AC 500-600V, 50/60HZ NOM. POWER RATING: 315KW 6-PULSE SYSTEM WITHOUT REGENERATIVE FEEDBACK VERSION A, INKL. EMV-FILTER 2. AMB. CONDITION, CATEGORY C3

Benefits

  • Particularly quiet and compact converters thanks to state-of-the-art IGBT power semiconductors and an innovative cooling concept.
  • Individual modules and power components can be replaced quickly and easily, which ensures a higher level of plant availability. Replaceable components have been designed so that they can be quickly and easily replaced. In addition, the “Spares On Web” Internet tool makes it easy to view the spare parts that are available for the particular order at all times.
  • Can be easily integrated in automation solutions by means of a standard communications interface as well as a range of analog and digital interfaces.
  • Easy commissioning and parameterization using interactive menus on the AOP30 Advanced Operator Panel with graphic LCD and plain-text display, or PC-supported using the STARTER commissioning tool (see Chapter Tools and configuration).
  • Preset software functions make it easier to adapt the converter to the individual plant. For example, the key functions for controlling pumps are stored as a preprogrammed macro in the drive.
  • With regard to EMC, the devices are subdivided into various zones, and as a consequence, they are extremely insensitive to disturbances and are very reliable in operation. With the help of simulated conditions, partitions have been designed to act as air guides and to help dissipate heat.
  • Special measures used in the construction of the cabinets ensure that they remain mechanically durable over their entire life cycle. All components, from individual parts to the ready-to-connect cabinet, undergo rigorous testing throughout the entire production process. This guarantees a high level of functional reliability during installation and commissioning, as well as in operation.

Application

Variable-speed drives are ideal for all applications that involve moving, conveying, pumping or compressing solids, liquids or gases.

Key applications include:

  • Pumps and fans
  • Compressors
  • Extruders and mixers
  • Mills

Design

SINAMICS G150 converter cabinet units are characterized by their compact, modular and service-friendly design.

A wide range of options is available depending on the cabinet version which permit optimum adaptation of the drive system to the respective requirements (see Options).

Example of the design of a SINAMICS G150 converter cabinet unit, version A

Basic design of a SINAMICS G150 converter cabinet unit with several essential options

Basic design of a SINAMICS G150 converter cabinet unit in parallel connection in order to increase the power rating, with several essential options

Coated modules

The following converter components are equipped as standard with coated modules:

  • Power Modules
  • Control Units
  • Sensor Modules
  • Terminal Modules
  • Advanced Operator Panel (AOP30)

The coating on the modules protects the sensitive SMD components against corrosive gases, chemically active dust and moisture.

Nickel-plated busbars

All of the copper busbars used in the converter cabinet are nickel-plated in order to achieve the best possible immunity to environmental effects. The bare copper connections also do not have to be cleaned for customer connections.

Note:

With some options, parts of the copper busbars cannot be nickel-plated for technical reasons.

Degrees of protection of the cabinet units

The EN 60529 standard covers the protection of electrical equipment by means of housings, covers or equivalent, and includes:

  • Protection of persons against accidental contact with live or moving parts within the housing and protection of the equipment against the ingress of solid foreign bodies (touch protection and protection against ingress of solid foreign bodies)
  • Protection of the equipment against the ingress of water (water protection)
  • Abbreviations for the internationally agreed degrees of protection

The degrees of protection are specified by abbreviations comprising the code letters IP and two digits.

Degrees of protection for the converter cabinet unit

First digit
(touch protection and protection against ingress of foreign solid bodies)

Second digit
(protection of the equipment against the ingress of water)

IP20 (standard)

Protected against solid foreign bodies with a diameter ≥ 12.5 mm

No water protection

IP21 (option M21)

Protected against solid foreign bodies with a diameter ≥ 12.5 mm

Protected against drip water

Vertically falling water drops must not have any harmful effects.

IP23 (option M23)

Protected against solid foreign bodies with a diameter ≥ 12.5 mm

Protected against spray water

Water sprayed on at an angle of up to 60° both sides of the vertical must not have any harmful effects.

IP43 (option M43)

Protected against solid foreign bodies with a diameter ≥ 1 mm

Protected against spray water

Water sprayed on at an angle of up to 60° both sides of the vertical must not have any harmful effects.

IP54 (option M54)

Dust protected.

Ingress of dust is not totally prevented, but dust must not be allowed to enter in such quantities that the functioning or safety of the equipment is impaired.

Protected against splash water

Water splashing onto the housing from any direction must not have any harmful effects.

Function

AOP30 Advanced Operator Panel

An AOP30 Advanced Operator Panel is located in the cabinet door of the converter for the operator control and monitoring as well as for the commissioning.

The AOP30’s two-stage safety concept prevents unintentional or unauthorized changes to settings. Operation of the drive from the operator panel can be disabled by the keyboard lock so that only parameter values and process variables can be displayed on the operator panel. The OFF key is factory-set to “active”, but can be deactivated by the customer. A password can be used to prevent the unauthorized changing of converter parameters.

The user is guided by interactive menus through the drive commissioning screens. When commissioning the drive for the first time, only six motor parameters (which can be found on the motor rating plate) have to be entered on the AOP30. The closed-loop control is then optimized automatically to adapt the converter to the motor.

GermanEnglishFrenchItalianSpanish and Chinese are stored on the CU320‑2 Control Unit CompactFlash card as operator panel languages. The desired language must be downloaded to the AOP30 prior to commissioning. In addition to these preinstalled languages, Russian and Portuguese (Brazil) are also available for subsequent installation. Further languages are available on request.

Examples of plain-text displays during various phases of operation are shown below.

The first commissioning is performed via the operator panel.

Only six motor parameters have to be entered:

Power, speed, current, cos φ, voltage and frequency of the motor.

This information can be found on the motor rating plate, and must be entered in the screens on the display by following a short, menu-assisted procedure. The motor cooling method must also be specified.

The next screen contains the parameter values that are used to automatically optimize the control.

During operation, the display shows current data, such as setpoints and actual values as absolute values or it is possible to parameterize up to three process variables as a quasi-analog bar display.

Any alarms which occur are signaled by the flashing of the yellow “ALARM” LED, faults by the lighting up of the red “FAULT” LED. There is also an indication of the cause displayed in plain text on the display’s status line.

Communication with higher-level controller and customer terminal block

A PROFIBUS interface on the CU320‑2 DP Control Unit is provided as standard as the customer interface for the controller.

When using the CU320‑2 PN (PROFINET) Control Unit (option K95), communication is via PROFINET in accordance with the PROFIdrive profile.

The Control Unit can be connected to the higher-level controller via its digital inputs and outputs to exchange digital signals.

The inputs and outputs available as standard can be optionally expanded using a TB30 Terminal Board (option G62) and/or up to two TM31 Terminal Modules (option G60 or G61).

To simplify configuration and commissioning of the drive, the optional TM31 Terminal Module can be preset with a variety of factory settings.

For further information, please refer to the SINAMICS Low Voltage Engineering Manual.

Open-loop and closed-loop control functions

The converter control contains a high-quality sensorless vector control with speed and current control as well as motor and converter protection.