SIEMENS SIPLUS LOGO Module! modular basic variants

SIPLUS LOGO!Overview

  • The space-saving basic variants
  • Interface for connecting expansion modules, up to 24 digital inputs, 20 (16) digital outputs, 8 analog inputs and 8 (2) analog outputs can be addressed
  • With connection option for LOGO! TD text display (can be connected to all LOGO! 0BA6 and 0BA7 basic variants); LOGO! TDE can be connected to LOGO! 8 or higher

New for LOGO! 8

  • All basic units with integrated web server
  • Same enclosure width as LOGO! 0BA6 (4 U)
  • All basic units with Ethernet interface for communication with LOGO!, SIMATIC Controllers, SIMATIC Panel and PC
  • Use of standard micro CF cards

LOGO! 0BA7 versions:

  • Ethernet interface for communication with SIMATIC Controllers, SIMATIC Panel and PC
  • Networking of max. 8 LOGO! devices
  • Use of standard SD card or SIMATIC Memory Card

SIPLUS LOGO! modular basic variants Ordering data

Product No. / Product DescriptionListprice / Your price
6AG1052-1CC01-2BA6
SIPLUS LOGO! 24 -25 … +70 GRD C WITH CONFORMAL COATING BASED ON 6ED1052-1CC01-0BA6 . LOGIC MODULE,DISPLAY PU/I/O: 24V/24V/24V TRANS., 8DI (4AI)/4DO; MEM 200 BLOCKS, REAL TIME CLOCK, EXPANDABLE WITH EXTRA MODULES
6AG1052-1CC01-7BA8
SIPLUS LOGO! 24CE -20…+70°C startup -20°C WITH CONFORMAL COATING BASED ON 6ED1052-1CC01-0BA8 . LOGIC MODULE,DISPLAY PU/I/O: 24V/24V/24V TRANS., 8DI (4AI)/4DO; MEM 400 BLOCKS, EXPANDABLE, ETHERNET BIULD IN WEB-SERVER, DATALOG STANDARD MICRO SD CARD FOR LOGO! SOFT COMFORT V8 PREVIOS PROJECT USABEL
6AG1052-1FB00-2BA6
SIPLUS LOGO! 230RC -25 … +70 DEGREES C BASED ON 6ED1052-1FB00-0BA6
6AG1052-1FB00-2BA7
SIPLUS LOGO! 230RCE -25 … +70 DEGREES C WITH CONFORMAL COATING BASED ON 6ED1052-1FB00-0BA7 . LOGIC MODULE, DISPLAY PU/I/O: 115V/230V/RELAY, 8 DI/4 DO, MEM. 400 BLOCKS, EXPANDABLE WITH EXTRA MODULES 230V AC/DC, ETHERNET
6AG1052-1FB00-7BA8
SIPLUS LOGO! 230RCE -20 … +60°C startup -20°C WITH CONFORMAL COATING BASED ON 6ED1052-1FB00-0BA8 . LOGIC MODULE,DISPL. PU/I/O: 115V/230V/RELAY, 8 DI/4 DO;MEM 400 BLOCKS EXPANDABLE,ETHERNET BIULD IN WEB-SERVER, DATALOG STANDARD MICRO SD CARD FOR LOGO! SOFT COMFORT V8 PREVIOS PROJECT USABEL
6AG1052-1HB00-2BA6
SIPLUS LOGO! 24RC -25 … +70 DEGREES C BASED ON 6ED1052-1HB00-0BA6
6AG1052-1HB00-7BA8
SIPLUS LOGO! 24RCE -20 … +60°C startup -20°C with conformal coating based on 6ED1052-1HB00-0BA8 . Logicmodule, Display PU/I/O: 24V AC/24V DC/Relay, 8 DI/4 DO; Mem. 400 Blocks, Expandable, Ethernet build in Web-Server, Datalog, Standard micro SD-Card for LOGO! SOFT Comfort V8 previos Project usabel
6AG1052-1MD00-2BA6
SIPLUS LOGO! 12/24RC -25 … +70 DEGREES C INCL CONFORMAL COATING BASED ON 6ED1052-1MD00-0BA6
6AG1052-1MD00-2BA7
SIPLUS LOGO!12/24RCE -25 … +70 DEGREES C WITH CONFORMAL COATING BASED ON 6ED1052-1MD00-0BA7 . LOGIC MODULE, DISPLAY PU/I/O: 12/24V DC/RELAY, 8 DI (4AI)/4 DO; MEMORY 400 BLOCKS, EXPANDABLE, ETHERNET
6AG1052-1MD00-7BA8
SIPLUS LOGO! 12/24RCE -20 … +60°C startup -20°C with conformal coating based on 6ED1052-1MD00-0BA8 . Logicmodule, Display PU/I/O: 12/24V DC/Relay, 8 DI (4AI)/4 DO; Mem. 400 Blocks, Expandable, Ethernet build in Web-Server, Datalog, Standard micro SD-Card for LOGO! SOFT Comfort V8 previos Project usabel

Design

  • Ethernet port
  • Relay outputs with max. 10 A output current
  • Integrated display field with parameterizable backlight (6 x 16 characters, 3 background colors).
  • Integrated operator control panel.
  • Integrated EEPROM memory for control program and setpoint values.
  • Optional standard micro CF cards
  • Integral real-time clock with automatic summer/winter time adjustment.
  • Backup of the integrated real-time clock for 20 days.
  • 8 digital inputs, 4 digital outputs.
  • 4 inputs as analog inputs in 12/24 V DC variants (0 to 10 V); inputs can also be used digitally.
  • 4 inputs can be used for high-speed counting up to 5 kHz (DC versions only).
  • Interface for the connection of expansion modules, up to 24 digital inputs, 20 digital outputs, 8 analog inputs and 8 analog outputs can be addressed.
  • Connection of LOGO! TDE via Ethernet.

Function

  • Integrated basic and special functions:
    • Basic logic functions:
      AND, OR, NOT, NAND, NOR, XOR, positive/negative pulse edge evaluation.
    • Special functions:
      ON delay, latching ON delay, OFF delay, impulse relay, locking relay, counter (forward/backward), time switch, interval time-delay relay, operating hours counter, trigger, asynchronous pulse generator, year time switch, comfort light switch function, random generator, staircase light switch function as per DIN 18015-2, edge-triggered interval time-delay relay, combined ON/OFF delay, analog comparator, analog trigger, analog delta trigger, analog watchdog, analog amplifier, text and variable display, shift register, soft key function, PI controller, ramp function, analog multiplexer, PWM function, analog arithmetic function, function for detecting errors in the analog arithmetic function.
  • 400 function blocks can be interlinked
  • Up to 64 bit memories
    (including restart bit memory, bit memory for controlling the backlight of the integral display and the LOGO! TDE, bit memory for switching between 2 parameterizable character sets in the message text).
  • Integrated retentivity.
  • Password protection.
  • Additional know-how protection with the optional micro CF card.
  • Data logging to internal memory or micro CF card (up to 20 000 records)
  • Macros (user-defined functions) for LOGO! Soft Comfort
  • 64 open terminals
  • 4 8-bit shift registers
  • Extended diagnostic functions

Technical specifications

Article number

6AG1052-1CC01-7BA8

6AG1052-1MD00-7BA8

6AG1052-1HB00-7BA8

6AG1052-1FB00-7BA8

SIPLUS LOGO! 24CE

SIPLUS LOGO! 12/24RCE

SIPLUS LOGO! 24RCE

SIPLUS LOGO! 230RCE

Display

with display

Yes; The legibility and response time of the display may be reduced or lengthened at temperatures outside 0 … +55 °C. These effects are self-reversing on return to the normal temperature range of 0 … +55 °C.

Yes; The legibility and response time of the display may be reduced or lengthened at temperatures outside 0 … +55 °C. These effects are self-reversing on return to the normal temperature range of 0 … +55 °C.

Yes; The legibility and response time of the display may be reduced or lengthened at temperatures outside 0 … +55 °C. These effects are self-reversing on return to the normal temperature range of 0 … +55 °C.

Yes; The legibility and response time of the display may be reduced or lengthened at temperatures outside 0 … +55 °C. These effects are self-reversing on return to the normal temperature range of 0 … +55 °C.

Installation type/mounting

Mounting

on 35 mm DIN rail, 4 spacing units wide

on 35 mm DIN rail, 4 spacing units wide

on 35 mm DIN rail, 4 spacing units wide

on 35 mm DIN rail, 4 spacing units wide

Supply voltage

Rated value (DC)

  • ● 12 V DC

Yes

  • ● 24 V DC

Yes

Yes

Yes

  • ● 115 V DC

Yes

  • ● 230 V DC

Yes

permissible range, lower limit (DC)

20.4 V

10.8 V

20.4 V

100 V

permissible range, upper limit (DC)

28.8 V

28.8 V

28.8 V

253 V

Rated value (AC)

  • ● 24 V AC

Yes

  • ● 115 V AC

Yes

  • ● 230 V AC

Yes

Line frequency

  • ● permissible range, lower limit

47 Hz

47 Hz

  • ● permissible range, upper limit

63 Hz

63 Hz

Time of day

Time switching clocks

  • ● Number

190

190

190

190

  • ● Power reserve

480 h

480 h

480 h

480 h

Digital inputs

Number of digital inputs

8; Of which 4 can be used in analog mode (0 to 10 V)

8; Of which 4 can be used in analog mode (0 to 10 V)

8

8

Digital outputs

Number of digital outputs

4; Transistor

4; Relays

4; Relays

4; Relays

Short-circuit protection

Yes; electrical (1 A)

No; external fusing necessary

No; external fusing necessary

No; external fusing necessary

Output current

  • ● for signal “1” permissible range for 0 to 55 °C, max.

0.3 A

10 A

Relay outputs

Switching capacity of contacts

  • — with inductive load, max.

3 A

3 A

3 A

  • — with resistive load, max.

10 A

10 A

10 A

EMC

Emission of radio interference acc. to EN 55 011

  • ● Limit class B, for use in residential areas

Yes; Radio interference suppression according to EN55011, Limit Value Class B

Yes

Yes

Yes

Degree and class of protection

Degree of protection acc. to EN 60529

  • ● IP20

Yes

Yes

Yes

Yes

Standards, approvals, certificates

CE mark

Yes

Yes

Yes

Yes

developed in accordance with IEC 61131

Yes

Yes

Yes

Yes

according to VDE 0631

Yes

Yes

Yes

Yes

Ambient conditions

Ambient temperature during operation

  • ● min.

-20 °C; = Tmin; Startup @ -20 °C

-20 °C; = Tmin; Startup @ -20 °C

-20 °C; = Tmin; Startup @ -20 °C

-20 °C; = Tmin; Startup @ -20 °C

  • ● max.

60 °C; Tmax; Tmax > +55 °C max. load 0.2 A per output

60 °C; Tmax; Tmax > +55 °C max. load 1 A per relay or max. load 3 A per relay and half the number of DIs (no adjacent points)

60 °C; Tmax; Tmax > +55 °C max. load 1 A per relay or max. load 3 A per relay and half the number of DIs (no adjacent points)

60 °C; Tmax; Tmax > +55 °C max. load 1 A per relay

  • ● At cold restart, min.

0 °C

0 °C

0 °C

0 °C

Ambient temperature during storage/transportation

  • ● min.

-40 °C

-40 °C

-40 °C

-40 °C

  • ● max.

70 °C

70 °C

70 °C

70 °C

Altitude during operation based on sea level

  • ● Ambient air temperature-barometric pressure-altitude

Tmin … Tmax at 1080 hPa … 795 hPa (-1000 m … +2000 m) // Tmin … (Tmax – 10K) at 795 hPa … 658 hPa (+2000 m … +3500 m) // Tmin … (Tmax – 20K) at 658 hPa … 540 hPa (+3500 m … +5000 m)

Tmin … Tmax at 1 140 hPa … 795 hPa (-1 000 m … +2 000 m) // Tmin … Tmax -5K) at 795 hPa … 701 hPa (+2 000 m … +3 000 m)

Relative humidity

  • ● With condensation, tested in accordance with IEC 60068-2-38, max.

100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation

100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation

100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation

100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation

Dimensions

Width

71.5 mm

71.5 mm

71.5 mm

71.5 mm

Height

90 mm

90 mm

90 mm

90 mm

Depth

60 mm

60 mm

60 mm

60 mm

Article number

6AG1052-1MD00-2BA7

6AG1052-1FB00-2BA7

SIPLUS LOGO!12/24RCE

SIPLUS LOGO! 230RCE

Display

with display

Yes

Yes

Installation type/mounting

Mounting

on 35mm DIN rail, 6 spacing units wide

on 35mm DIN rail, 6 spacing units wide

Supply voltage

Rated value (DC)

  • ● 12 V DC

Yes

  • ● 24 V DC

Yes

  • ● 115 V DC

Yes

  • ● 230 V DC

Yes

permissible range, lower limit (DC)

10.8 V

100 V

permissible range, upper limit (DC)

28.8 V

253 V

Rated value (AC)

  • ● 115 V AC

Yes

  • ● 230 V AC

Yes

Time of day

Time switching clocks

  • ● Number

333

333

  • ● Power reserve

480 h

480 h

Digital inputs

Number of digital inputs

8; of which 4 can be used in analog mode (0 to 10 V); max. load 9 A per relay @ all DI @ +55 °C to +60 °C; max. load 1 A per relay @ all DI @ > +60 °C; max. load 3 A per relay @ half the number of DI @ > +60 °C

8; half the number of DI @ max. load 1A per relay @ > +60 °C

Digital outputs

Number of digital outputs

4; Relays

4; Relays

Short-circuit protection

No; external fusing necessary

No; external fusing necessary

Relay outputs

Switching capacity of contacts

  • — with inductive load, max.

3 A

3 A

  • — with resistive load, max.

10 A; max. last 9 A per relay @ all DI @ +55 °C to +60 °C; max. load 1 A per relay @ all DI @ > +60 °C; max. load 3 A per relay @ half the number of DI @ > +60 °C

10 A; max. load 1A per relay @ half the number of DI @ > +60 °C

EMC

Emission of radio interference acc. to EN 55 011

  • ● Limit class B, for use in residential areas

Yes; Radio interference suppression according to EN55011, Limit Value Class B

Yes; Radio interference suppression according to EN55011, Limit Value Class B

Degree and class of protection

Degree of protection acc. to EN 60529

  • ● IP20

Yes

Yes

Standards, approvals, certificates

CSA approval

Yes

UL approval

Yes

Yes

FM approval

Yes

developed in accordance with IEC 61131

Yes

Yes

according to VDE 0631

Yes

Yes

Marine approval

Yes

Ambient conditions

Ambient temperature during operation

  • ● min.

-25 °C; = Tmin

-25 °C; = Tmin

  • ● max.

70 °C; = Tmax

70 °C; = Tmax

Altitude during operation based on sea level

  • ● Ambient air temperature-barometric pressure-altitude

Tmin … Tmax at 1080 hPa … 795 hPa (-1000 m … +2000 m) // Tmin … (Tmax – 10K) at 795 hPa … 658 hPa (+2000 m … +3500 m) // Tmin … (Tmax – 20K) at 658 hPa … 540 hPa (+3500 m … +5000 m)

Tmin … Tmax at 1080 hPa … 795 hPa (-1000 m … +2000 m)

Relative humidity

  • ● With condensation, tested in accordance with IEC 60068-2-38, max.

100 %; RH incl. condensation/frost permitted (no commissioning in bedewed state)

100 %; RH incl. condensation/frost permitted (no commissioning in bedewed state)

Dimensions

Width

107 mm

107 mm

Height

90 mm

90 mm

Depth

55 mm

55 mm

Article number

6AG1052-1CC01-2BA6

6AG1052-1MD00-2BA6

6AG1052-1HB00-2BA6

6AG1052-1FB00-2BA6

SIPLUS LOGO! 24C

SIPLUS LOGO! 12/24RC

SIPLUS LOGO! 24RC

SIPLUS LOGO! 230RC

Display

with display

Yes; The display is bright at temperatures below 0 °C and dark at temperatures over +55 °C. This procedure is self-reversing on returning to the standard temperature range (0 °C to +55 °C).

Yes; The display is bright at temperatures below 0 °C and dark at temperatures over +55 °C. This procedure is self-reversing on returning to the standard temperature range (0 °C to +55 °C).

Yes; The display is bright at temperatures below 0 °C and dark at temperatures over +55 °C. This procedure is self-reversing on returning to the standard temperature range (0 °C to +55 °C).

Yes; The display is bright at temperatures below 0 °C and dark at temperatures over +55 °C. This procedure is self-reversing on returning to the standard temperature range (0 °C to +55 °C).

Installation type/mounting

Mounting

on 35 mm DIN rail, 4 spacing units wide

on 35 mm DIN rail, 4 spacing units wide

on 35 mm DIN rail, 4 spacing units wide

on 35 mm DIN rail, 4 spacing units wide

Supply voltage

Rated value (DC)

  • ● 12 V DC

Yes

  • ● 24 V DC

Yes

Yes

Yes

  • ● 115 V DC

Yes

  • ● 230 V DC

Yes

permissible range, lower limit (DC)

20.4 V; 22 V @ >55 °C

10.8 V; 11 V @ >55 °C

20.4 V; 22 V @ >55 °C

100 V

permissible range, upper limit (DC)

28.8 V; 27.5 V @ >55 °C

28.8 V; 27.5 V @ >55 °C

28.8 V; 27.5 V @ >55 °C

253 V

Rated value (AC)

  • ● 24 V AC

Yes

  • ● 115 V AC

Yes

  • ● 230 V AC

Yes

Time of day

Time switching clocks

  • ● Number

190

8

  • ● Power reserve

80 h

80 h

80 h

80 h

Digital inputs

Number of digital inputs

8; Of which 4 can be used in analog mode (0 to 10 V)

8; Of which 4 can be used in analog mode (0 to 10 V)

8

8

Digital outputs

Number of digital outputs

4; Transistor

4; Relays

4; Relays

4; Relays

Short-circuit protection

Yes; electrical (1 A)

No; external fusing necessary

No; external fusing necessary

No; external fusing necessary

Output current

  • ● for signal “1” permissible range for 0 to 55 °C, max.

0.3 A; 0.2 A @ > 55 °C; 0.3 A @ > 55 °C & < 15 s

Relay outputs

Switching capacity of contacts

  • — with inductive load, max.

3 A; 1 A per relay @ > 55 °C; 3 A per relay @ > 55 °C & < 15 s

3 A; 1 A per relay @ > 55 °C; 3 A per relay @ > 55 °C & < 15 s

3 A; 1 A per relay @ > 55 °C; 3 A per relay @ > 55 °C & < 15 s

  • — with resistive load, max.

10 A; 3 A per relay @ > 55 °C; 10 A per relay @ > 55 °C & < 15 s

10 A; 3 A per relay @ > 55 °C; 10 A per relay @ > 55 °C & < 15 s

10 A; 3 A per relay @ > 55 °C; 10 A per relay @ > 55 °C & < 15 s

EMC

Emission of radio interference acc. to EN 55 011

  • ● Limit class B, for use in residential areas

Yes; Radio interference suppression according to EN55011, Limit Value Class B

Yes

Yes

Yes

Degree and class of protection

Degree of protection acc. to EN 60529

  • ● IP20

Yes

Yes

Yes

Yes

Standards, approvals, certificates

CSA approval

No

No

No

No

UL approval

Yes; File: E120869 // Tmax = 55 °C

Yes; File: E120869 // Tmax = 55 °C

Yes; File: E120869 // Tmax = 55 °C

Yes; File: E120869 // Tmax = 55 °C

FM approval

No

No

No

No

developed in accordance with IEC 61131

Yes

Yes

Yes

Yes

according to VDE 0631

Yes

Yes

Yes

Yes

Marine approval

No

No

No

No

Ambient conditions

Ambient temperature during operation

  • ● min.

-25 °C; = Tmin

-25 °C; = Tmin

-25 °C; = Tmin

-25 °C; = Tmin

  • ● max.

70 °C; = Tmax; 55 °C @ UL/cUL use

70 °C; = Tmax; 55 °C @ UL/cUL use

70 °C; = Tmax; 55 °C @ UL/cUL use

70 °C; = Tmax; 55 °C @ UL/cUL use

Altitude during operation based on sea level

  • ● Ambient air temperature-barometric pressure-altitude

Tmin … Tmax at 1080 hPa … 795 hPa (-1000 m … +2000 m) // Tmin … (Tmax – 10K) at 795 hPa … 658 hPa (+2000 m … +3500 m) // Tmin … (Tmax – 20K) at 658 hPa … 540 hPa (+3500 m … +5000 m)

Tmin … Tmax at 1080 hPa … 795 hPa (-1000 m … +2000 m) // Tmin … (Tmax – 10K) at 795 hPa … 658 hPa (+2000 m … +3500 m) // Tmin … (Tmax – 20K) at 658 hPa … 540 hPa (+3500 m … +5000 m)

Tmin … Tmax at 1080 hPa … 795 hPa (-1000 m … +2000 m) // Tmin … (Tmax – 10K) at 795 hPa … 658 hPa (+2000 m … +3500 m) // Tmin … (Tmax – 20K) at 658 hPa … 540 hPa (+3500 m … +5000 m)

Tmin … Tmax at 1080 hPa … 795 hPa (-1000 m … +2000 m)

Relative humidity

  • ● With condensation, tested in accordance with IEC 60068-2-38, max.

100 %; RH incl. condensation/frost permitted (no commissioning in bedewed state)

100 %; RH incl. condensation/frost permitted (no commissioning in bedewed state)

100 %; RH incl. condensation/frost permitted (no commissioning in bedewed state)

100 %; RH incl. condensation/frost permitted (no commissioning in bedewed state)

Dimensions

Width

72 mm

72 mm

72 mm

72 mm

Height

90 mm

90 mm

90 mm

90 mm

Depth

55 mm

55 mm

55 mm

55 mm