SIEMENS SIPLUS power supplies 1-phase, 24 V DC for SIPLUS S7-1200

Overview1-phase, 24 V DC (for SIPLUS S7-1200)

  • Stabilized power supply for SIPLUS S7-1200
  • In the S7-1200 design
  • Input 120/230 V AC, output 24 V DC, 2.5 A (derating: 1.5 A above 60 °C)
Note:

SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were adopted from the respective standard products. SIPLUS extreme specific information was added.

SIEMENS SIPLUS S7-1200 Ordering data

Product No. / Product DescriptionListprice / Your price
6AG1332-1SH71-4AA0
SIPLUS S7-1200 PM1207 FOR MEDIAL STRESS WITH CONFORMAL COATING BASED ON 6EP1332-1SH71 . STABILIZED POWER SUPPLY INPUT: 120/230 V AC OUTPUT: 24 V DC/2.5 A
6AG1332-1SH71-7AA0
SIPLUS S7-1200 PM1207 -40 … +70 DEGREES C WITH CONFORMAL COATING BASED ON 6EP1332-1SH71 . STABILIZED POWER SUPPLY INPUT: 120/230 V AC OUTPUT: 24 V DC/2.5 A

SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were adopted from the respective standard products. SIPLUS extreme specific information was added.

SIPLUS power supply PM 1207

Article No.

6AG1 332-1SH71-4AA0

6AG1 332-1SH71-7AA0

Article No. based on

6EP1 332-1SH71

Ambient temperature range

0 … +60° C

-25 … +70° C

Conformal coating

Coating of the printed circuit boards and the electronic components

Technical specifications

The technical data of the standard product applies except for the ambient conditions.

Ambient conditions

Relative humidity

100%, condensation/frost permitted. No commissioning in bedewed state.

Biologically active substances, compliance with EN 60721-3-3

Class 3B2 mold and fungal spores (excluding fauna). The supplied plug covers must remain in place over the unused interfaces during operation!

Chemically active substances, compliance with EN 60721-3-3

Class 3C4 incl. salt spray in accordance with EN60068-2-52 (degree of severity 3). The supplied plug covers must remain in place over the unused interfaces during operation!

Mechanically active substances, compliance with EN 60721-3-3

Class 3S4 incl. sand, dust. The supplied plug covers must remain in place over the unused interfaces during operation!

Air pressure (depending on the highest positive temperature range specified)

1 080 … 795 hPa (-1 000 … +2 000 m)
see ambient temperature range

795 … 658 hPa (+2000 … +3500 m)
derating 10 K

658 … 540 hPa (+3500 … +5000 m)
derating 20 K

Technical specifications

SIPLUS PM 1207

Order No.

6AG1332-1SH71-7AA0

6AG1332-1SH71-4AA0

Order No. based on

6EP1332-1SH71

Input voltage, nominal value

120/230 V AC (auto-switching)

  • Range

85…132 V / 176…264 V AC

Mains buffering

> 20 ms (at 93/187 V)

Line frequency, nominal

50/60 Hz

  • Range

47 … 63 Hz

Input current, nominal value

1.2/0.67 A

  • Inrush current (25 °C)

<13 A

  • Recommended circuit-breaker

16 A Charact. B, 10 A Charact. C

Output voltage, nominal value

24 V DC

  • Tolerance

± 3%

  • Residual ripple

< 150 mVpp

  • Adjustment

No

Output current, nominal value

2.5 A (derating: 1.5 A from 60 °C)

Efficiency at nominal values, approx.

83%

Parallel operation

Yes, 2 units

Electronic short-circuit protection

Yes, automatic restart

Radio interference suppression (EN 55022)

Class B

Operating display

Green LED for “24 V o.k.”

Supply-harmonics limitation (EN 61000-3-2)

Not applicable

Degree of protection (EN 60529)

IP20

Protection class

Class 1

Electric isolation

SELV acc. to EN 60950 and EN 50178

Ambient temperature

0 … +60 °C

-25 … 70 °C

Transport and storage temperature

-25 … +85 °C

Installation

Standard rail EN 60715 35×7.5/15

Dimensions (W x H x D) in mm

70 x 100 x 75

Weight, approx.

0.3 kg

Certifications

CE