SIEMENS SIPLUS S7-300 FM 350-1 Product Information

SIPLUS S7-300 FM 350-1

  • Single-channel, intelligent counter module for simple counting tasks
  • For direct connection of incremental encoders
  • Comparison function with 2 definable comparison values
  • Integrated digital outputs for output of the response on reaching the comparison value
  • Operating modes:
    • Continuous countingSIPLUS S7-300 FM 350-1
    • Single counting
    • Periodic counting
  • Special functions:
    • Set counter
    • Latch counter
  • Start/stop counter by gate function
Note:

SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme-specific information was added.

The FM 350-1 is the intelligent single-channel counter module for a wide range of basic counting tasks. It can be used in the SIMATIC S7-300 and in the ET 200M (with S7-300/-400 as master).

Applications include:

  • Assembly and handling equipment
  • Plastics machines
  • Production machines
  • Paper-making machines
  • Textile machines
  • Packaging machines
Product No. / Product Description Listprice / Your price
6AG1350-1AH03-2AE0
SIPLUS S7-300 FM350-1 -25 … +60 DEGREES C WITH CONFORMAL COATING BASED ON 6ES7350-1AH03-0AE0 . COUNTER MODULE COUNTER FUNCTIONS UP TO 500 KHZ 1 CHANNEL FOR CONNECTING 5V- A. 24V-IINCREMENTAL ENCODER ISOCHRONE MODE MEASUREMENT MODE INCL. CONFIGURING PACKAGE ON CD
6AG1350-1AH03-2AY0
SIPLUS S7-300 FM350-1 -25 … + 60 DGR C ACCORDING EN50155 BASED ON 6ES7350-1AH03-0AE0 . COUNTER MODULE FM 350-1 FOR S7-300, COUNTER FUNCTIONS UP TO 500 KHZ 1 CHANNEL FOR CONNECTION OF 5V AND 24V INCREMENTAL ENCODERS ISOCHRON MODE, MEASUREMENT MODE INCL. CONFIG. PACKAGE ON CD
Function

The FM 350-1 off-loads the CPU by:

  • Direct connection of incremental encoders
  • Direct connection for gate signals (light barrier etc.) using integrated digital inputs.
  • A comparison function and output of response using integrated digital output modules.

The following functions are provided:

  • 1 channel for upcounting and downcounting; 32 bit
  • Counting frequency up to 500 kHz (RS 422 encoders)
  • Counting range 0 to 32 bit or +/- 31 bit, as required
  • One-shot or periodic counting process
  • 1-, 2- or 4-fold evaluation
  • Incremental encoder can be connected
  • Gate control via levels, pulses or software control
  • Setting via the digital input
  • Counter can be loaded with a predefined starting value
  • Comparison function using two selectable comparison values
  • Interrupt response when a comparison value is reached, zero crossing, range violation (selectable)
  • Output signal (24 V-level) that the comparison function controls: With jointly selectable pulse duration or as a continuous signal from the comparison value to the limit of the counting range.

Standard Function Blocks

CNT_CTRL (FC 0)

For controlling the counters of the FM 350-1

DIAG_INF (FC 1)

For providing the diagnostic information of the FM 350-1

Mode of operation

The FM 350-1 counter module detects pulses from incremental encoders at up to 500 kHz, as a function of directly connectable gate signals.

  • It evaluates the direction of the pulses and compares the actual value with two comparison values, which can be preset.There are two possibilities available to output the reaction to the process:
    • 2 digital outputs;
      they can be configured using the selectable minimum pulse or with level switching.
    • Backplane bus;
      the FM 350-1 can send an alarm signal to the CPU via the integrated backplane bus.

Operating Modes

Continuous counting

After the gate is enabled, endless counting takes place between the lower and upper count limit from the starting value

One-shot counting

After the gate is enabled, the system counts once from the starting value to the upper or lower limit depending on the main count direction

  • Main counting direction up: from 0 to the programmable range limit
  • Main counting direction down: from the programmable start value to 0

Periodic counting

After the gate is enabled, periodic counting takes place from the starting value within the programmed counting range depending on the main count direction

  • Main counting direction up: periodic from 0 to the programmed range limit – 1
  • Main counting direction down: periodically from the programmed start value to 1

Parameterization

Parameters are assigned with STEP 7 with the help of parameterization screen forms. A configuring package is available for this purpose.

Design

The module provides the encoder supply.

It has the following mechanical features:

  • Compact configuration;
    The rugged plastic housing contains:

    • Fault LEDs (GF)
    • LEDs to indicate that the counter is running (CR) and the counting direction (DIR)
    • LEDs for digital input and output modules.
    • Slot for the front connector, protected by the front cover
    • Labeling area on the front cover
  • Easy installation:
    The module is simply mounted in the rack and screwed tight. It can be fitted with a coding key, which assigns it permanently to a specific slot.
  • Coding connector (measurement range module for analog inputs) for selecting the type of encoder (5 V or 24 V)
  • User-friendly wiring:
    The module is wired by means of a plug-in front connector. When the connector is plugged in for the first time a coding element in the module engages, so that the connector can only be plugged into modules of the same type. When the module is replaced, the front connector can be used in its fully wired state for the new module of the same type.

Configuring package

The configuring package required for configuration comprises:

  • “Getting Started” instructions
  • Manual
  • Parameterization screen forms
  • Standard function blocks for data exchange with the CPU
Technical specifications

Article number

6AG1350-1AH03-2AE0

6AG1350-1AH03-2AY0

SIPLUS S7-300 FM350-1

SIPLUS S7-300 FM350-1 EN50155

Supply voltage

Auxiliary voltage 1L+, load voltage 2L+

  • ● Rated value (DC)

24 V

24 V; A power supply according to EN 50155 shall be used

  • ● permissible range, lower limit (DC)

20.4 V; Dynamic 18.5 V

20.4 V; Dynamic 18.5 V

  • ● permissible range, upper limit (DC)

28.8 V; dynamic 30.2 V

28.8 V; dynamic 30.2 V

non-periodic skip

  • — Duration

500 ms

500 ms

  • — Recovery time

50 s

50 s

  • — Value

35 V

35 V

Input current

from load voltage 1L+ (without load), max.

40 mA

40 mA

from backplane bus 5 V DC, max.

160 mA

160 mA

5 V encoder supply

  • ● 5 V

Yes; 5.2 V ±2 %

Yes; 5.2 V ±2 %

  • ● Output current, max.

300 mA

300 mA

24 V encoder supply

  • ● 24 V

Yes; 1L+ (-3 V)

Yes; 1L+ (-3 V)

  • ● Output current, max.

400 mA

400 mA

Power loss

Power loss, typ.

4.5 W

4.5 W

Digital inputs

Number of digital inputs

3

3

Functions

1 for gate start, 1 for gate stop, 1 for setting the counter

1 for gate start, 1 for gate stop, 1 for setting the counter

Input voltage

  • ● for signal “0”

-28.8 … +5V

-28.8 … +5V

  • ● for signal “1”

+11 to +28.8V

+11 to +28.8V

Input current

  • ● for signal “1”, typ.

9 mA

9 mA

Digital outputs

Number of digital outputs

2

2

Short-circuit protection

Yes; Clocked electronically

Yes; Clocked electronically

Limitation of inductive shutdown voltage to

2L+ (-39 V)

2L+ (-39 V)

Output voltage

  • ● for signal “0”, max.

3 V

3 V

  • ● for signal “1”, min.

2L+ (-1,5 V)

2L+ (-1,5 V)

Output current

  • ● for signal “1” rated value

0.5 A

0.5 A

  • ● for signal “1” permissible range for 0 to 60 °C, min.

5 mA

5 mA

  • ● for signal “1” permissible range for 0 to 60 °C, max.

0.6 A

0.6 A

Output delay with resistive load

  • ● “0” to “1”, max.

300 µs

300 µs

Encoder

Connectable encoders

  • ● Incremental encoder (symmetrical)

Yes; With 2 pulse trains offset by 90°

Yes; With 2 pulse trains offset by 90°

  • ● Incremental encoder (asymmetrical)

Yes

Yes

  • ● 24 V initiator

Yes

Yes

  • ● 24 V directional element

Yes; 1 pulse train, 1 direction level

Yes; 1 pulse train, 1 direction level

Counter

Number of counter inputs

1

1

Counting range, description

32 bit or ±31 bit

32 bit or ±31 bit

Minimum pulse width, adjustable

Yes; 2.5 or 25 µs

Yes; 2.5 or 25 µs

Counter input 5 V

  • ● Type

RS 422

RS 422

  • ● Terminating resistor

220 Ω

220 Ω

  • ● Differential input voltage

1,3 V

1,3 V

  • ● Counting frequency, max.

500 kHz

500 kHz

Counter input 24 V

  • ● Input voltage for signal “0”

-28.8 … +5V

-28.8 … +5V

  • ● Input voltage for signal “1”

+11 to +28.8V

+11 to +28.8V

  • ● Input current for signal “1”, typ.

9 mA

9 mA

  • ● Counting frequency, max.

200 kHz

200 kHz

  • ● Minimum pulse width

2.5 µs

2.5 µs

Potential separation

Potential separation digital inputs

  • ● between the channels and backplane bus

Yes; Optocoupler

Yes; Optocoupler

Potential separation digital outputs

  • ● between the channels and backplane bus

Yes; Optocoupler

Yes; Optocoupler

Potential separation counter

  • ● between the channels and backplane bus

Yes; Optocoupler

Yes; Optocoupler

Permissible potential difference

between different circuits

75 V DC/60 V AC

75 V DC/60 V AC

Isolation

Isolation tested with

500 V

500 V

Standards, approvals, certificates

CE mark

Yes

Yes

UL approval

Yes; File E239877

Yes; File E239877

FM approval

Yes

Yes; CofC 3028431

RCM (formerly C-TICK)

Yes

Yes

KC approval

Yes

Yes

EAC (formerly Gost-R)

Yes

Yes

Railway application

  • ● EN 50155

Yes; Sections 4, 5 and 12; no further agreements apply; T1, Category 1, Class A/B

Ambient conditions

Ambient temperature during operation

  • ● min.

-25 °C; = Tmin

-25 °C; = Tmin

  • ● max.

60 °C; = Tmax

60 °C; = Tmax; the rated temperature range of -25 … +55 °C (T1) applies for the use on railway vehicles according to EN50155

Altitude during operation relating to sea level

  • ● Ambient air temperature-barometric pressure-altitude

Tmin … Tmax at 1080 hPa … 795 hPa (-1000 m … +2000 m) // Tmin … (Tmax – 10K) at 795 hPa … 658 hPa (+2000 m … +3500 m) // Tmin … (Tmax – 20K) at 658 hPa … 540 hPa (+3500 m … +5000 m)

Relative humidity

  • ● With condensation, tested in accordance with IEC 60068-2-38, max.

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

Resistance

Use in stationary industrial systems

  • — to biologically active substances according to EN 60721-3-3

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

  • — to chemically active substances according to EN 60721-3-3

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

  • — to mechanically active substances according to EN 60721-3-3

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Connection method

required front connector

1x 20-pin

1x 20-pin

Dimensions

Width

40 mm

40 mm

Height

125 mm

125 mm

Depth

120 mm

120 mm

Weights

Weight, approx.

250 g