SIPLUS S7-300 SM 321 Ordering data

Product No. / Product Description Listprice / Your price
6AG1321-1BH02-2AA0
SIPLUS S7-300 SM321 – 20-POLE -40 … +70 DGR C WITH CONFORMAL COATING CONFORMITY WITH EN50155 T1 KAT 1 KL A/B BASED ON 6ES7321-1BH02-0AA0 . DIGITAL INPUT OPTIC. ISOLATED 16 DI, 24V DC, 1 X 20-POLE
6AG1321-1BL00-2AA0
SIPLUS S7-300 SM321 – 40-POLE -40 … +70 DGR C WITH CONFORMAL COATING CONFORMITY TO EN50155 T1 CAT 1 CL A/B BASED ON 6ES7321-1BL00-0AA0 . DIGITAL INPUT OPTICALLY ISOLATE 32DI, 24 V DC, 1 X 40 PIN
6AG1321-1CH20-2AA0
SIPLUS S7-300 SM321 -25 … +70 DGR C WITH CONFORMAL COATING CONFORMITY TO EN50155 T1 CAT 1 CL A/B BASED ON 6ES7321-1CH20-0AA0 . DIGITAL INPUT, OPTICALLY ISOLAT 16 DI, DC 48-125V, 1 X 20 PIN
6AG1321-1FF01-2AA0
SIPLUS S7-300 SM321 – 20-POLE -40 … +70 DGR C WITH CONFORMAL COATING Conformity with EN 50155 T1 Kat 1 Kl A/B BASED ON 6ES7321-1FF01-0AA0 . DIGITAL INPUT OPTICALLY ISOLATE 8 DI, 120V/230V AC, 1 X 20 PIN
6AG1321-1FF10-7AA0
SIPLUS S7-300 SM321 8 DI -25 … +70 DEGREES C WITH CONFORMAL COATING BASED ON 6ES7321-1FF10-0AA0 . DIGITAL INPUT OPTICALLY ISOLATED, 8 DI, 120V/230V AC, 1 X 40 PIN, WITH 1 POINT PER COMMON
6AG1321-1FH00-7AA0
SIPLUS S7-300 SM321 16DI -40 … +70 DEGREES C WITH COMFORMAL COATING BASED ON 6ES7321-1FH00-0AA0 . DIGITAL INPUT GALVANICALLY ISOLATED 16 DI, AC120/230V, 1 X 20-POLE
6AG1321-7BH01-2AB0
SIPLUS S7-300 SM321 – 20-POLE -25 … +70 DGR C WITH CONFORMAL COATING CONFORMITY WITH EN50155 T1 KAT 1 KL A/B BASED ON 6ES7321-7BH01-0AB0 . DIGITAL INPUT GALVANICALLY ISOLATED 16 DI; 24V DC, 1 X 20-POLE, PROCESS INTERRUPT, DIAGNOSTICS, FIT FOR ISOCHRONE MODE
6AG1321-7TH00-4AB0
SIPLUS PCS 7 SM321 16DE FOR MEDIAL STRESS WITH CONFORMAL COATING BASED ON 6ES7321-7TH00-0AB0 . DIGITAL INPUT MODULE, 16 DI, 24V DC, 1 X 40 PIN, CAPABLE OF DIAGNOSTICS, FOR CONTACTS (CONNECTED/ UNCONNECTED), NAMUR SENSOR, 3/4-WIRE-BERO, WITH FLUTTER MONITORING, PULSE LENGTHENING, WIRE BREAK DETECTION, IM153-2 INTERFACE MOD. REQUIRED

Application

Digital input modules can be used to connect the PLC to digital process signals. They are suitable for connecting standard switches and two-wire proximity switches (BERO).


Design

Digital input modules feature the following mechanical characteristics:

  • Compact design:
    The rugged plastic housing contains:

    • Green LEDs for indicating the signal status at the inputs.
    • Socket for the front connector, protected, behind the front door.
    • Labeling field on the front door.
    • Connector pin assignment for the wiring on the inside of the front door.
  • Easy installation:
    There are no slot rules, the addresses of the inputs are determined by the slot.
    When used in ET 200M in combination with active bus modules, hot swapping is possible without any reaction.
  • User-friendly wiring.

The modules are available with 8, 16, 32, or 64 channels.


Function

Digital input modules convert the level of the external digital signals from the process to the internal signal level (logical “0” or “1”) of the controller.

Various input voltages support the connection of different process signals:

  • 24 V DC
  • 48 to 125 V DC
  • 120/230 V AC

Apart from cost-effective, easy-to-handle modules, modules with special functions are also available:

  • For use in isochronous mode
  • Process and diagnostic alarms
  • Use for current sourcing or current sinking

Special modules are also available for process engineering which, for example, support the NAMUR standard.


Technical specifications

Article number

6AG1321-1BH02-2AA0

6AG1321-1BL00-2AA0

6AG1321-1CH20-2AA0

6AG1321-1FF01-2AA0

6AG1321-1FF10-7AA0

SIPLUS SM321 16DE/24VDC

SIPLUS SM321 32DE/24VDC

SIPLUS SM 321 16DE/ DC 48-125 V

SIPLUS S7-300 SM321 8DE/120/230VAC

SIPLUS S7-300 SM321 8DI/120/230VAC

Supply voltage

Load voltage L+

  • ● Rated value (DC)

24 V

24 V

48 V

  • ● permissible range, lower limit (DC)

20.4 V

20.4 V

48 V

  • ● permissible range, upper limit (DC)

28.8 V

28.8 V

125 V

Load voltage L1

  • ● Rated value (AC)

230 V; 120/230V AC

230 V; 120/230 V AC; all load voltages must have the same phase.

Input current

from backplane bus 5 V DC, max.

10 mA

15 mA

40 mA

29 mA

100 mA

Power loss

Power loss, typ.

3.5 W

6.5 W

4.3 W

4.9 W

4.9 W

Digital inputs

Number of digital inputs

16

32

16

8

8

Input characteristic curve in accordance with IEC 61131, type 1

Yes

Yes

Yes

Yes

Yes

Number of simultaneously controllable inputs

all mounting positions

  • — up to 60 °C, max.

8; 6 @ Ue 146 V

  • — up to 70 °C, max.

6; 4 @ Ue 146 V

horizontal installation

  • — up to 40 °C, max.

16

32

  • — up to 50 °C, max.

8

  • — up to 60 °C, max.

16; 16 @ > 60 °C

16; 12 @ > 60 °C

8; 6 to Ue 146 V

8; up to 70 °C

8; 8 @ > 60 °C

vertical installation

  • — up to 40 °C, max.

16

8

Input voltage

  • ● Type of input voltage

DC

DC

DC

AC

AC

  • ● Rated value (DC)

24 V

24 V

48 V; 48 V DC to 125 V DC

  • ● Rated value (AC)

230 V; 120/230 V AC (47 … 63 Hz)

120 V; 120/230 V AC (47 … 63 Hz)

  • ● for signal “0”

-30 to +5V

-30 to +5V

-146 V DC to +15 V DC

0 to 40V

0 to 40V

  • ● for signal “1”

13 to 30V

13 to 30V

30 V DC to 146 V DC

79 to 264V

79 to 264V

Input current

  • ● for signal “1”, typ.

7 mA

7 mA

3.5 mA

6.5 mA; (120 V); 11 mA (230 V)

7.5 mA; (120 V); 17.3 mA (230 V)

Input delay (for rated value of input voltage)

for standard inputs

  • — parameterizable

No

No

No

No

No

  • — at “0” to “1”, min.

1.2 ms

1.2 ms

0.1 ms

  • — at “0” to “1”, max.

4.8 ms

4.8 ms

3.5 ms

25 ms

25 ms

  • — at “1” to “0”, min.

1.2 ms

1.2 ms

0.7 ms

  • — at “1” to “0”, max.

4.8 ms

4.8 ms

3 ms

25 ms

25 ms

Cable length

  • ● shielded, max.

1 000 m

1 000 m

1 000 m

1 000 m

1 000 m

  • ● unshielded, max.

600 m

600 m

600 m

600 m

600 m

Encoder

Connectable encoders

  • ● 2-wire sensor

Yes

Yes

Yes

Yes

Yes

  • — permissible quiescent current (2-wire sensor), max.

1.5 mA

1.5 mA

1 mA

2 mA

2 mA

Isochronous mode

Isochronous operation (application synchronized up to terminal)

No

No

No

No

No

Interrupts/diagnostics/status information

Diagnostic functions

No

No

No

No

No

Alarms

  • ● Diagnostic alarm

No

No

No

No

No

  • ● Hardware interrupt

No

No

No

No

No

Diagnostics indication LED

  • ● Group error SF (red)

No

No

No

  • ● Status indicator digital input (green)

Yes

Yes

Yes

Yes

Yes

Potential separation

Potential separation digital inputs

  • ● between the channels

No

No

No

No

Yes

  • ● between the channels, in groups of

16

16

8

2

1

  • ● between the channels and backplane bus

Yes; Optocoupler

Yes; Optocoupler

Yes; Optocoupler

Yes; Optocoupler

Yes; Optocoupler

Permissible potential difference

between different circuits

75 V DC/60 V AC

75 V DC/60 V AC

146 V DC/132 V AC

Isolation

Isolation tested with

500 V DC

500 V DC

1500 V DC

4 000 V DC

1500 V AC

Standards, approvals, certificates

CE mark

Yes

Yes

Yes

Yes

Yes

UL approval

Yes; File E239877

Yes; File E239877

Yes; File E239877

Yes; File E239877

Yes; File E239877

FM approval

Yes; CofC 3028431

Yes; CofC 3028431

No

No

Yes; CofC 3028431

RCM (formerly C-TICK)

Yes

Yes

Yes

Yes

Yes

KC approval

Yes

Yes

Yes

Yes

Yes

EAC (formerly Gost-R)

Yes

Yes

Yes

Yes

Yes

Railway application

  • ● EN 50155

Yes; Sections 4, 5 and 12; no further agreements apply; T1, Category 1, Class A/B

Yes; Sections 4, 5 and 12; no further agreements apply; T1, Category 1, Class A/B

Yes; Sections 4, 5 and 12; no further agreements apply; T1, Category 1, Class A/B

Yes; Sections 4, 5 and 12; no further agreements apply; T1, Category 1, Class A/B

Use in hazardous areas

  • ● ATEX

Yes

Yes

No

No

No

Ambient conditions

Ambient temperature during operation

  • ● min.

-40 °C; = Tmin

-40 °C; = Tmin

-25 °C

-40 °C; = Tmin

-25 °C

  • ● max.

70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use

70 °C; = Tmax; for use on railway vehicles according to EN50155, the rated temperature range -25 … +55 °C (T1) or 60 °C @ UL/ULhaz/ATEX/FM use applies

70 °C; = Tmax; for use on railway vehicles according to EN50155, the rated temperature range -25 … +55 °C (T1) or 60 °C @ UL/ULhaz/ATEX/FM use applies

70 °C; = Tmax; for use on railway vehicles according to EN50155, the rated temperature range -25 … +55 °C (T1) or 60 °C @ UL/ULhaz/ATEX/FM use applies

70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use

Ambient temperature during storage/transportation

  • ● min.

-40 °C

-40 °C

-40 °C

-40 °C

-40 °C

  • ● max.

70 °C

70 °C

70 °C

70 °C

70 °C

Altitude during operation relating to sea level

  • ● Ambient air temperature-barometric pressure-altitude

Tmin … Tmax at 1080 hPa … 795 hPa (-1000 m … +2000 m) // Tmin … (Tmax – 10K) at 795 hPa … 658 hPa (+2000 m … +3500 m) // Tmin … (Tmax – 20K) at 658 hPa … 540 hPa (+3500 m … +5000 m)

Tmin … Tmax at 1080 hPa … 795 hPa (-1000 m … +2000 m) // Tmin … (Tmax – 10K) at 795 hPa … 658 hPa (+2000 m … +3500 m) // Tmin … (Tmax – 20K) at 658 hPa … 540 hPa (+3500 m … +5000 m)

Tmin … Tmax at 1080 hPa … 795 hPa (-1000 m … +2000 m) // Tmin … (Tmax – 10K) at 795 hPa … 658 hPa (+2000 m … +3500 m) // Tmin … (Tmax – 20K) at 658 hPa … 540 hPa (+3500 m … +5000 m)

Tmin … Tmax at 1080 hPa … 795 hPa (-1000 m … +2000 m)

Tmin … Tmax at 1080 hPa … 795 hPa (-1000 m … +2000 m)

Relative humidity

  • ● With condensation, tested in accordance with IEC 60068-2-38, max.

100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation

100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation

100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation

100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation

100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation

Resistance

Use in stationary industrial systems

  • — to biologically active substances according to EN 60721-3-3

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

  • — to chemically active substances according to EN 60721-3-3

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

  • — to mechanically active substances according to EN 60721-3-3

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Connection method

required front connector

20-pin

40-pin

20-pin

20-pin

40-pin

Dimensions

Width

40 mm

40 mm

40 mm

40 mm

40 mm

Height

125 mm

125 mm

125 mm

125 mm

125 mm

Depth

120 mm

120 mm

120 mm

120 mm

120 mm

Weights

Weight, approx.

200 g

260 g

200 g

240 g

240 g

Article number

6AG1321-1FH00-7AA0

6AG1321-7BH01-2AB0

6AG1321-7TH00-4AB0

SIPLUS S7-300 SM 321 16DI/120/230VAC

SIPLUS SM321 16DE/24VDC

SIPLUS PCS 7 SM321 16DE

Supply voltage

Load voltage L+

  • ● Rated value (DC)

24 V

24 V

  • ● permissible range, lower limit (DC)

20.4 V

  • ● permissible range, upper limit (DC)

28.8 V

Load voltage L1

  • ● Rated value (AC)

230 V; 120/230 V AC; all load voltages must have the same phase.

Input current

from load voltage L+ (without load), max.

90 mA

100 mA

from backplane bus 5 V DC, max.

29 mA

130 mA

100 mA

Power loss

Power loss, typ.

4.9 W

4 W

11 W

Time stamping

Accuracy

1 ms

Digital inputs

Number of digital inputs

16

16

16

Input characteristic curve in accordance with IEC 61131, type 1

Yes

No

Input characteristic curve in accordance with IEC 61131, type 2

Yes

Yes

horizontal installation

  • — up to 40 °C, max.

16

  • — up to 60 °C, max.

16; up to 70 °C

16

16

vertical installation

  • — up to 40 °C, max.

16

16

16

Input voltage

  • ● Type of input voltage

AC

DC

DC

  • ● Rated value (DC)

24 V

8.2 V; 8.2V/18V

  • ● Rated value (AC)

230 V; 120/230 V AC (47 … 63 Hz)

  • ● for signal “0”

0 to 40V

-30 to +5V

  • ● for signal “1”

79 to 264V

13 to 30V

Input current

  • ● for signal “1”, typ.

6.5 mA; (120V, 60Hz), 16mA (230V, 50Hz)

7 mA

10 mA; for NAMUR: 2.1 to 7 mA, for 10k ohm/47k ohm contact: typical 10mA, for 4 wire BEROs: typical 10 mA

Input delay (for rated value of input voltage)

for standard inputs

  • — parameterizable

No

Yes; 0.1 / 0.5 / 3 / 15 / 20 ms

  • — at “0” to “1”, min.

25 ms

2.5 ms

  • — at “0” to “1”, max.

25 ms

3.5 ms

  • — at “1” to “0”, min.

2.5 ms

  • — at “1” to “0”, max.

25 ms

3.5 ms

Cable length

  • ● shielded, max.

1 000 m

1 000 m

400 m; max. 200m with 8.2 V sensor, max. 400m with 18 V sensor

  • ● unshielded, max.

600 m

600 m

Not permitted

Encoder

Connectable encoders

  • ● 2-wire sensor

Yes

Yes

  • — permissible quiescent current (2-wire sensor), max.

2 mA

2 mA

Isochronous mode

Isochronous operation (application synchronized up to terminal)

No

Yes

Interrupts/diagnostics/status information

Diagnostic functions

No

Yes; Parameterizable

Yes

Alarms

  • ● Diagnostic alarm

No

Yes; Parameterizable

Yes

  • ● Hardware interrupt

No

Yes; Parameterizable

Yes

Diagnostic messages

  • ● Wire-break

Yes; to I< 1 mA

Yes

Diagnostics indication LED

  • ● Group error SF (red)

No

Yes

Yes

  • ● Status indicator digital input (green)

Yes

Yes

Yes

Potential separation

Potential separation digital inputs

  • ● between the channels

No

No

Yes

  • ● between the channels, in groups of

4

16

8

  • ● between the channels and backplane bus

Yes; Optocoupler

Yes; Optocoupler

Yes

Permissible potential difference

between different circuits

75 V DC/60 V AC

75 V DC/60 V AC

Isolation

Isolation tested with

4 000 V DC

500 V DC

600 V DC

Standards, approvals, certificates

CE mark

Yes

Yes

Yes

UL approval

Yes; File E239877

Yes; File E239877

Yes; File E239877

FM approval

Yes; CofC 3028431

Yes; CofC 3028431

Yes; CofC 3028431

RCM (formerly C-TICK)

Yes

Yes

Yes

KC approval

Yes

Yes

Yes

EAC (formerly Gost-R)

Yes

Yes

Yes

Railway application

  • ● EN 50155

Yes; Sections 4, 5 and 12; no further agreements apply; T1, Category 1, Class A/B

Use in hazardous areas

  • ● ATEX

No

Yes

Yes

Ambient conditions

Ambient temperature during operation

  • ● min.

-40 °C; = Tmin

-25 °C

0 °C

  • ● max.

70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use

70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use

60 °C

  • ● At cold restart, min.

0 °C

Ambient temperature during storage/transportation

  • ● min.

-40 °C

-40 °C

-40 °C

  • ● max.

70 °C

70 °C

70 °C

Altitude during operation relating to sea level

  • ● Ambient air temperature-barometric pressure-altitude

Tmin … Tmax at 1080 hPa … 795 hPa (-1000 m … +2000 m)

Tmin … Tmax at 1080 hPa … 795 hPa (-1000 m … +2000 m) // Tmin … (Tmax – 10K) at 795 hPa … 658 hPa (+2000 m … +3500 m) // Tmin … (Tmax – 20K) at 658 hPa … 540 hPa (+3500 m … +5000 m)

Tmin … Tmax at 1080 hPa … 795 hPa (-1000 m … +2000 m) // Tmin … (Tmax – 10K) at 795 hPa … 658 hPa (+2000 m … +3500 m) // Tmin … (Tmax – 20K) at 658 hPa … 540 hPa (+3500 m … +5000 m)

Relative humidity

  • ● With condensation, tested in accordance with IEC 60068-2-38, max.

100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation

100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation

100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation

Resistance

Use in stationary industrial systems

  • — to biologically active substances according to EN 60721-3-3

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

  • — to chemically active substances according to EN 60721-3-3

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

  • — to mechanically active substances according to EN 60721-3-3

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Connection method

required front connector

20-pin

20-pin

40-pin

Dimensions

Width

40 mm

40 mm

40 mm

Height

125 mm

125 mm

125 mm

Depth

120 mm

120 mm

120 mm

Weights

Weight, approx.

240 g

200 g