SIEMENS SIPLUS S7-300 SM 326 – Safety Integrated Overview
Overview
- Digital inputs for the fail-safe SIPLUS S7 systems
- For connecting:
- Switches and 2-wire proximity switches
- Sensors according to NAMUR and mechanical contacts, also for signals from hazardous areas
- With integral safety functions for fail-safe operation
- Can be used in fail-safe operation
- Centrally: with S7-31xF-2 DP
- Distributed in ET 200M: With SIMATIC IM 151-7 F-CPU, S7-31xF-2 DP, S7-416F-2 and S7-400F/FH
- In standard operation can be used in the same way as S7-300 modules
Note:
SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme-specific information was added.
Fail-safe digital input modules are suitable for connecting
- Switches and 2-wire proximity switches (BEROs)
- Sensors according to NAMUR and mechanical contacts, also for signals from hazardous areas
The modules are implemented centrally with SIMATIC S7-31xF-2 DP and in the ET 200M distributed I/O station in combination with SIMATIC IM 151-7 F-CPU, S7-31xF-2 DP, S7-416F-2 and S7-400F/FH. They can also be used in non-safety-relevant standard mode and then respond like standard S7-300 modules.
Product No. / Product Description | Listprice / Your price | ||||||
![]() | 6AG1326-1BK02-2AB0 SIPLUS S7-300 SM326F DI24 40PIN -25 … +60 DEGREES C 70 DEG C WITH FORCED CONVECTION WITH CONFORMAL COATING BASED ON 6ES7326-1BK02-0AB0 . DIGITAL INPUT F-DI 24 X DC 24V, FAILSAFE DIGITAL INPUTS FOR SIMATIC S7 FAILSAFE SYSTEMS WITH DIAGNOST. INTERRUPT | ||||||
![]() | 6AG1326-1BK02-2AY0 SIPLUS S7-300 SM326F DI24 WITH CONFORMAL COATING CONFORMITY ACCORDING EN50155 T1 CAT 1 CL A/B BASED ON 6ES7326-1BK02-0AB0 . DIGITAL INPUT FAILSAFE DIGITAL INPUTS FOR SIMATIC S7 FAILSAFE SYSTEMS WITH DIAGNOST. INTERRUPT, 1 X 40 PIN | ||||||
![]() | 6AG1326-1RF01-4AB0 SIPLUS S7-300 SM326F DI8 NAMUR FOR MEDIAL STRESS WITH CONFORMAL COATING BASED ON 6ES7326-1RF01-0AB0 . DIGITAL INPUT SM 326, 8 DI; DC 24V, NAMUR, FAILSAFE NAMUR INPUTS FOR SIMATIC S7 F SYSTEMS, UP TO CATEGORY 4 (EN954-1)/ SIL3 (IEC61508)/PLE (ISO13849), 1 X 40 PIN |
Technical specifications
Article number | 6AG1326-1BK02-2AB0 | 6AG1326-1BK02-2AY0 | 6AG1326-1RF01-4AB0 | |
---|---|---|---|---|
SIPLUS S7-300 SM326F DI24 | SIPLUS S7-300 SM326F DI24 | SIPLUS S7-300 SM326F DI8 NAMUR | ||
Supply voltage | ||||
Rated value (DC) | 24 V | 24 V; A power supply according to EN 50155 shall be used | ||
Input current | ||||
from load voltage L+ (without load), max. | 450 mA | 450 mA | 160 mA | |
from backplane bus 5 V DC, max. | 100 mA | 100 mA | 90 mA | |
Encoder supply | ||||
Number of outputs | 4; Isolated | 4; Isolated | 8 | |
Type of output voltage | 8.2 V DC | |||
Output current | ||||
| 400 mA | 400 mA | ||
Power loss | ||||
Power loss, typ. | 10 W | 10 W | 4.5 W | |
Digital inputs | ||||
Number of digital inputs | 24 | 24 | 8 | |
Number of simultaneously controllable inputs | ||||
all mounting positions | ||||
| 24 | 24 | 8 | |
| 24; (at 24 V) or 18 (at 28.8 V) | 24; (at 24 V) or 18 (at 28.8 V) | 8 | |
Input voltage | ||||
| DC | DC | ||
| 24 V | 24 V | ||
| -30 to +5V | -28.8 … +5V | ||
| +11 to +30V | +11 to +28.8V | ||
Input current | ||||
| 2 mA | 2 mA | 0.35 to 1.2 mA | |
| 10 mA | 10 mA | 2.1 to 7 mA | |
Input delay (for rated value of input voltage) | ||||
for standard inputs | ||||
| 3.4 ms | 3.4 ms | ||
| 3.4 ms | 3.4 ms | ||
for NAMUR inputs | ||||
| 1.2 to 3 ms | |||
| 1.2 to 3 ms | |||
Cable length | ||||
| 200 m | 200 m | 200 m | |
| 100 m | 100 m | 100 m | |
Encoder | ||||
Connectable encoders | ||||
| Yes; if short-circuit test is deactivated | Yes; if short-circuit test is deactivated | ||
| 2 mA | 2 mA | ||
Interrupts/diagnostics/status information | ||||
Diagnostic functions | Yes | Yes | ||
Alarms | ||||
| Yes | Yes | Yes; Parameterizable | |
Diagnostic messages | ||||
| Yes | Yes | ||
Diagnostics indication LED | ||||
| Yes | Yes | Yes | |
| Yes | Yes | Yes | |
Ex(i) characteristics | ||||
Module for Ex(i) protection | Yes | |||
Maximum values of input circuits (per channel) | ||||
| 3 µF | |||
| 13.9 mA | |||
| 80 mH | |||
| 33.1 mW | |||
| 10 V | |||
| 60 V DC/30 V AC | |||
| 60 °C | 60 °C; = Tmax; the rated temperature range of -25 … +55 °C (T1) applies for the use on railway vehicles according to EN50155 | 60 °C | |
Potential separation | ||||
Potential separation digital inputs | ||||
| Yes | Yes | Yes | |
| 12 | 12 | ||
| Yes | Yes | Yes | |
| Yes | |||
Isolation | ||||
Isolation tested with | 500 V DC/350 V AC | 500V AC for 1 min (internal voltage limiting to ±120V) | ||
tested with | ||||
| 1500 V AC | |||
| 1500 V AC | |||
| 500 V DC/350 V AC | |||
Standards, approvals, certificates | ||||
CE mark | Yes | Yes | Yes | |
UL approval | Yes; File E239877 | Yes; File E239877 | ||
FM approval | Yes; CofC 3028431 | Yes; CofC 3028431 | ||
RCM (formerly C-TICK) | Yes | |||
KC approval | Yes | |||
EAC (formerly Gost-R) | Yes | |||
Railway application | ||||
| Yes; Sections 4, 5 and 12; no further agreements apply; T1, Category 1, Class A/B | |||
Highest safety class achievable in safety mode | ||||
| AK 6 | AK 6 | ||
| Cat. 4 | Cat. 4 | Cat. 4 | |
| SIL 3 | SIL 3 | SIL 2 (single-channel), SIL 3 (two-channel) | |
Ambient conditions | ||||
Ambient temperature during operation | ||||
| -25 °C; = Tmin | -25 °C; = Tmin | 0 °C; = Tmin | |
| 60 °C; = Tmax; *+70 °C where forced convection with a minimum air velocity of 0.7 m/s through the modules and rated voltage of 24 V ±5 % are ensured. If in the course of maintenance or automatic diagnosis it is determined that the admissible specified parameters have been exceeded, the modules should be subjected to a proof test (function check) by the manufacturer. | 60 °C; = Tmax; the rated temperature range of -25 … +55 °C (T1) applies for the use on railway vehicles according to EN50155 | 60 °C; = Tmax | |
Altitude during operation relating to sea level | ||||
| Tmin … Tmax at 1080 hPa … 795 hPa (-1000 m … +2000 m) | Tmin … Tmax at 1080 hPa … 795 hPa (-1000 m … +2000 m) | Tmin … Tmax at 1080 hPa … 795 hPa (-1000 m … +2000 m) | |
Relative humidity | ||||
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | ||
Resistance | ||||
Use in stationary industrial systems | ||||
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | ||
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | ||
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | ||
Connection method | ||||
required front connector | 40-pin | 40-pin | 1x 40-pin | |
Dimensions | ||||
Width | 80 mm | 80 mm | 80 mm | |
Height | 125 mm | 125 mm | 125 mm | |
Depth | 120 mm | 120 mm | 120 mm | |
Weights | ||||
Weight, approx. | 442 g | 442 g | 482 g |