  • Analog inputs for fail-safe SIPLUS S7 systems
  • Applicable in the ET 200M distributed I/O device with IM 153-2 HF as well as centrally with SIPLUS S7-31xF-2 DP
  • Properties of the SM 336; F-AI 6 x 0/4 … 20 mA HART:
    • 6 analog inputs with galvanic isolation between channels and backplane bus
    • Input ranges: 0 mA to 20 mA, 4 mA to 20 mA
    • Short-circuit proof power supply of 2 or 4-wire transmitter via the module
    • External encoder supply possible
    • Applicable in safety mode
    • HART communication
    • Firmware update using HW Config
    • Identification data
    • Temperature range -25 … +70 °C;
      (+70 °C when ensuring a forced convection with a minimal air velocity of 0.3 m/s through the module. If a violation of the permissible, specified parameters is detected during maintenance or by automatic diagnostics, the modules must be proof-tested by the manufacturer. Without this measure the temperature range is -25…60°C)
Note:

SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added.

Product No. / Product Description Listprice / Your price
6AG1336-4GE00-2AB0
SIPLUS ET 200M SM336 F 6AI 15BIT -25 … +60 DEG C 70 DEG C WITH FORCED CONVECTION WITH CONFORMAL COATING BASED ON 6ES7336-4GE00-0AB0 . FAILSAFE ANALOG INPUTS FOR SIMATIC SAFETY, WITH HART SUPPORT, UP TO CATEGORY 4 (EN954-1)/ SIL3 (IEC61508)/ PLE (ISO13849), 1 X 20 PIN
Design

  • 6 inputs for current measurement.
  • Compact design:
    • Group fault display (SF)
    • Safety mode display (SAFE)
    • Display for channel-specific faults (Fn)
    • Display for HART status (Hn)
    • Plug options for the 20-pin front connector, protected behind the front door.
    • Labeling field on the front door.
  • Easy assembly
    Assembled like the other ET 200M I/O modules.
  • User-friendly wiring with 20-pin front connector.
Function

The analog input module converts analog signals from the process to digital signals for internal processing by the fail-safe SIMATIC S7 CPUs.

The safety functions required for fail-safe operation are integrated in the module.

The following functions are available:

  • Resolution 15 bits + sign.
  • Measuring ranges:
    • 0 to 20 mA or
    • 4 to 20 mA or
    • 4 to 20 mA (HART)
  • Interrupt capability;
    the module sends diagnostic interrupts to the CPU of the controller.
  • Diagnostics;
    the module sends extensive diagnostic information to the CPU.
Application

The modules are used centrally with SIMATIC S7-31xF-2 DP and in the ET 200M distributed I/O device together with SIMATIC IM 151-7 F-CPU, S7-31xF-2 DP, S7-416F-2 and S7-400F/FH.

0 to 20 mA and 4 to 20 mA current transmitters (also HART) can be connected as encoders.

Technical specifications

Article number

6AG1336-4GE00-2AB0

SIPLUS S7-300 SM336 F 6AI 15BIT

Supply voltage

Rated value (DC)

24 V; ±5 %

Reverse polarity protection

Yes

Input current

From power supply L+, typ.

150 mA

from backplane bus 5 V DC, max.

90 mA

Power loss

Power loss, typ.

4.5 W

Analog inputs

Number of analog inputs

6

permissible input current for current input (destruction limit), max.

40 mA

Input ranges

  • ● Voltage

No

  • ● Current

Yes

Input ranges (rated values), currents

  • ● 0 to 20 mA

Yes

  • ● Input resistance (0 to 20 mA)

150 Ω; typ. 150 ohms max. 175 ohms

  • ● 4 mA to 20 mA

Yes

  • ● Input resistance (4 mA to 20 mA)

150 Ω; typ. 150 ohms max. 175 ohms

Cable length

  • ● shielded, max.

1 000 m

Analog value generation for the inputs

Integration and conversion time/resolution per channel

  • ● Integration time (ms)

20 ms @ 50 Hz, 16.7 ms @ 60 Hz

  • ● Interference voltage suppression for interference frequency f1 in Hz

f=n x (f1 ±0.5 %)

Encoder

Connection of signal encoders

  • ● for current measurement as 2-wire transducer

Yes

  • ● for current measurement as 4-wire transducer

Yes

Errors/accuracies

Operational error limit in overall temperature range

  • ● Current, relative to input range, (+/-)

0.3 %; 60 µA

Basic error limit (operational limit at 25 °C)

  • ● Current, relative to input range, (+/-)

0.1 %; 20 µA

Interrupts/diagnostics/status information

Diagnostic functions

Yes

Alarms

  • ● Diagnostic alarm

Yes

Diagnostic messages

  • ● Diagnostic information readable

Yes

Diagnostics indication LED

  • ● Fail-safe operation

Yes

  • ● Group error SF (red)

Yes

  • ● Encoder supply Vs (green)

No

Potential separation

Potential separation analog inputs

  • ● between the channels

Yes

  • ● between the channels and backplane bus

Yes

  • ● between the channels and the power supply of the electronics

Yes

Isolation

Isolation tested with

370V for 1 min

Standards, approvals, certificates

CE mark

Yes

Highest safety class achievable in safety mode

  • ● acc. to EN 954

4

  • ● SIL acc. to IEC 61508

SIL 3

Ambient conditions

Ambient temperature during operation

  • ● min.

-25 °C; = Tmin; Startup @ -25 °C

  • ● max.

60 °C; = T max; *+70 °C when forced convection at a minimum air speed of 0.3 m/s through the modules is ensured. If in the course of maintenance or automatic diagnosis it is determined that the admissible specified parameters have been exceeded, the modules should be subjected to a proof test (function check) by the manufacturer.

  • ● At cold restart, min.

-25 °C

Ambient temperature during storage/transportation

  • ● min.

-40 °C

  • ● max.

70 °C

Altitude during operation relating to sea level

  • ● Ambient air temperature-barometric pressure-altitude

Tmin … Tmax at 1080 hPa … 795 hPa (-1000 m … +2000 m)

Relative humidity

  • ● With condensation, tested in accordance with IEC 60068-2-38, max.

100 %; incl. condensation / frost permitted (no commissioning under condensation conditions)

Resistance

Use in stationary industrial systems

  • — to biologically active substances according to EN 60721-3-3

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

  • — to chemically active substances according to EN 60721-3-3

Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

  • — to mechanically active substances according to EN 60721-3-3

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Connection method

required front connector

20-pin

Dimensions

Width

40 mm

Height

125 mm

Depth

120 mm

Weights

Weight, approx.

350 g