SIEMENS SITRANS P DS III for gauge and absolute pressure, with Diaphragm

Product No. / Product DescriptionListprice / Your price
7MF4133-…..-….
SITRANS P pressure transmitters for relative pressure, front-flush membrane, series DS III HART
7MF4134-…..-….
SITRANS P DS III PA, transmitter for pressure DS III PA series, with flush diaphragm
7MF4135-…..-….
SITRANS P pressure transmitters for relative pressure, front-flush membrane, DS III FF series (Foundation Fieldbus)

Technical specifications

SITRANS P DS III series for gauge and absolute pressure, with flush-mounted diaphragm

Input of gauge pressure, with flush diaphragm

Measured variable

Gauge pressure, flush-mounted

Span (infinitely adjustable) or nominal measuring range, max. operating pressure and max. test pressure

HART

PROFIBUS PA and FOUNDATION Fieldbus

Span

Nominal measuring range

Max. perm. operating pressure MAWP (PS)

Max. permissible test pressure

0.01 … 1 bar
1 … 100 kPa
0.15 … 14.5 psi

1 bar
100 kPa
14.5 psi

4 bar
400 kPa
58 psi

6 bar
600 kPa
87 psi

0.04 … 4 bar
4 … 400 kPa
0.58 … 58 psi

4 bar
400 kPa
58 psi

7 bar
0.7 MPa
102 psi

10 bar
1 MPa
145 psi

0.16 … 16 bar
16 … 1600 kPa
2.32 … 232 psi

16 bar
1.6 MPa
232 psi

21 bar
2.1 MPa
305 psi

32 bar
3.2 MPa
464 psi

0.6 … 63 bar
63 … 6300 kPa
9.14 … 914 psi

63 bar
6.3 MPa
914 psi

67 bar
6.7 MPa
972 psi

100 bar
10 MPa
1450 psi

Low measuring limit

  • Measuring cell with silicone oil filling

100 mbar a/10 kPa a/1.45 psia

  • Measuring cell with inert fill fluid

100 mbar a/10 kPa a/1.45 psia

  • Measuring cell with neobee

100 mbar a/10 kPa a/1.45 psia

Upper measuring limit

100 % of max. span

Input of gauge pressure, with flush diaphragm

Measured variable

Absolute pressure, flush-mounted

Span (infinitely adjustable) or nominal measuring range, max. operating pressure and max. test pressure

HART

PROFIBUS PA and FOUNDATION Fieldbus

Span

Nominal measuring range

Max. perm. operating pressure MAWP (PS)

Max. permissible test pressure

43 … 1300 mbar a
4.2 … 130 kPa a
17 … 525 inH2O a

1300 mbar a
130 kPa a
525 inH2O a

2.6 bar a
260 kPa a
37.7 psia

10 bar a
1 MPa a
145 psia

0.16 … 5 bar a
16 … 500 kPA a
2.32 … 72.5 psia

5 bar a
500 kPA a
72.5 psia

10 bar a
1 MPa a
145 psia

30 bar a
3 MPa a
435 psia

1 … 30 bar a
0.1 … 3 MPa a
14.5 … 435 psia

30 bar a
3 MPa a
435 psia

45 bar a
4.5 MPa a
653 psia

100 bar a
10 MPa a
1450 psia

Depending on the process connection, the span may differ from these values.

Low measuring limit

0 bar a/0 kPa a/0 psia

Upper measuring limit

100 % of max. span

Output

HART

PROFIBUS PA and FOUNDATION Fieldbus

Output signal

4 … 20 mA

Digital PROFIBUS PA and FOUNDATION Fieldbus signal

  • Lower limit (infinitely adjustable)

3.55 mA, factory preset to 3.84 mA

  • Upper limit (infinitely adjustable)

23 mA, factory preset to 20.5 mA or optionally set to 22.0 mA

Load

  • Without HART

RB ≤ (UH – 10.5 V)/0.023 A in Ω,
UH: Power supply in V

  • With HART

RB = 230 … 500 Ω (SIMATIC PDM) or
RB = 230 … 1100 Ω (HART Communicator)

Physical bus

IEC 61158-2

Protection against polarity reversal

Protected against short-circuit and polarity reversal. Each connection against the other with max. supply voltage.

Electrical damping (step width 0.1 s)

Set to 2 s (0 … 100 s)

Measuring accuracy

According to IEC 60770-1

Reference conditions
(All error data refer always refer to the set span)

  • Rising characteristic curve
  • Start of scale 0 bar
  • Seal diaphragm stainless steel
  • Silicone oil filling
  • Room temperature 25 °C (77 °F)

Measuring span ratio r (spread, Turn-Down)

r = maximum measuring span/set measuring span or nominal measuring range

Error in measurement at limit setting including hysteresis and reproducibility

  • Linear characteristic

Gauge pressure with flush-mounted diaphragm

Absolute pressure with flush-mounted diaphragm

  • r ≤ 5

≤ 0.075 %

  • 5 < r ≤ 100

≤ (0.005 · r + 0.05) %

  • r ≤ 10

≤ 0.2 %

  • 10 < r ≤ 30

≤ 0.4 %

Influence of ambient temperature
(in percent per 28 °C (50 °F))

≤ (0.08 · r + 0.16) %

≤ (0.16 · r + 0.24) %

Influence of the process temperature (in pressure per temperature unit)

  • Temperature difference between process temperature temperature and ambient temperature

3 mbar/0.3 kPa/0.04 psi per 10 K

Long-term stability (temperature change ±30 °C (±54 °F))

≤ (0.25 · r) % in 5 years

Effect of mounting position (in pressure per change of angle)

0.4 mbar/0.04 kPa/0.006 per 10° incline (zero point correction is possible with position error compensation)

Effect of auxiliary power (in percent per voltage change)

0.005 % per 1 V

Measured-value resolution for PROFIBUS PA and FOUNDATION Fieldbus

3 · 10-5 of nominal measuring range

Rated conditions

Installation conditions

Ambient temperature

Observe the temperature class in areas subject to explosion hazard.

  • Measuring cell with silicone oil

-40 … +85 °C (-40 … +185 °F)

  • Measuring cell with Neobee oil (with flush-mounted diaphragm)

-10 … +85 °C (14 … 185 °F)

  • Measuring cell with inert liquid

-40 … +85 °C (-40 … +185 °F)

  • Transmitter

-40 … +85 °C (-40 … +185 °F)

  • Display readable

-30 … +85 °C (-22 … +185 °F)

  • Storage temperature

-50 … +85 °C (-58 … +185 °F)
(for neobee: -20 … +85 °C (-4 … +185 °F))
(for high-temperature oil: -10 … +85 °C (14 … 185 °F))

  • Climatic class
  • Condensation

Relative humidity 0 … 100 %
Condensation permissible, suitable for use in the tropics

Degree of protection according to IEC 60529

IP66 (optional IP66/IP68), NEMA 4X

  • Electromagnetic compatibility
  • Emitted interference and interference immunity

According to IEC 61326 and NAMUR NE 21

Process conditions

Temperature of medium

The max. medium temperature of the flush-mounted process connections is to be taken into account in accordance with the relevant connection standards (e.g. DIN 32676, DIN 11851, etc.).

  • Measuring cell with silicone oil

-40 … +100 °C (-40 … +212 °F)

  • Measuring cell with silicone oil (with flush-mounted diaphragm)

-40 … +150 °C (-40 … +302 °F)

  • Measuring cell with Neobee oil (with flush-mounted diaphragm)

-10 … +150 °C (14 … 302 °F)

  • Measuring cell with silicone oil, with temperature decoupler (only for gauge pressure version with flush-mounted diaphragm)

-40 … +200 °C (-40 … +392 °F)

  • Measuring cell with Neobee oil, with temperature decoupler (only for gauge pressure version with flush-mounted diaphragm)

-10 … +200 °C (14 … 392 °F)

  • Measuring cell with inert fill fluid

-20 … +100 °C (-4 … +212 °F)

  • Measuring cell with high-temperature oil (only for gauge pressure version with flush-mounted diaphragm)

-10 … +250 °C (14 … 482 °F)

Design

Weight (without options)

≈ 1.5 kg (≈ 3.3 lb)

Enclosure material

Low-copper die-cast aluminum, GD-AlSi 12 or stainless steel precision casting, mat. no. 1.4408

Wetted parts materials

Stainless steel, mat. no. 1.4404/316L or Hastelloy C276, mat. no. 2.4819

Measuring cell filling

Silicone oil or inert fill fluid

Process connection

  • Flanges as per EN and ASME
  • F&B and pharmaceutical flanges

Surface quality touched-by-media

Ra-values ≤ 0.8 µm (32 µ-inch)/welds Ra) ≤ 1.6 µm (64 µ-inch)

(Process connectionsaccording to 3A; Ra-values ≤ 0.8 µm (32 µ-inch)/welds Ra) ≤ 0.8 µm (32 µ-inch)

Auxiliary power UH

HART

PROFIBUS PA/FOUNDATION Fieldbus

Terminal voltage on transmitter

10.5 … 45 V DC
10.5 … 30 V DC in intrinsically-safe mode

Auxiliary power

Bus-powered

Separate supply voltage

Not necessary

Bus voltage

  • Not Ex

9 … 32 V

  • With intrinsically-safe operation

9 … 24 V

Current consumption

  • Basic current (max.)

12.5 mA

  • Start-up current ≤ basic current

Yes

  • Max. current in event of fault

15.5 mA

Fault disconnection electronics (FDE) available

Yes

Certificates and approvals

HART

PROFIBUS PA/FOUNDATION Fieldbus

Classification according to pressure equipment directive (PED 2014/68/EU)

For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of article 4, paragraph 3 (sound engineering practice)

Explosion protection

  • Intrinsic safety “i”

PTB 13 ATEX 2007 X

  • Marking

Ex II 1/2 G Ex ia/ib IIC T4/T5/T6 Ga/Gb

  • Permissible ambient temperature

-40 … +85 °C (-40 … +185 °F) temperature class T4;
-40 … +70 °C (-40 … +158 °F) temperature class T5;
-40 … +60 °C (-40 … +140 °F) temperature class T6

  • Wiring

To certified intrinsically-safe circuits with peak values:
Ui = 30 V, Ii = 100 mA,
Pi = 750 mW; Ri = 300 Ω

FISCO supply unit:
Uo = 17.5 V, Io = 380 mA, Po = 5.32 W

Linear barrier:
Uo = 24 V, Io = 174 mA, Po = 1 W

  • Effective internal inductance/capacitance

Li = 0.4 mH, Ci = 6 nF

Li = 7 μH, Ci = 1.1 nF

  • Flameproof enclosure “d”

PTB 99 ATEX 1160

  • Marking

Ex II 1/2 G Ex d IIC T4/T6 Gb

  • Permissible ambient temperature

-40 … +85 °C (-40 … +185 °F) temperature class T4;
-40 … +60 °C (-40 … +140 °F) temperature class T6

  • Wiring

To circuits with operating values: UH = 10.5 … 45 V DC

To circuits with operating values: UH = 9 … 32 V DC

  • Dust explosion protection for zone 20

PTB 01 ATEX 2055

  • Marking

Ex II 1 D Ex ta IIIC T120°C Da
Ex II 1/2 D Ex ta/tb IIIC T120°C Da/Db

  • Permissible ambient temperature

-40 … +85 °C (-40 … +185 °F)

  • Max. surface temperature

120 °C (248 °F)

  • Wiring

To certified intrinsically-safe circuits with peak values:
Ui = 30 V, Ii = 100 mA,
Pi = 750 mW, Ri = 300 Ω

FISCO supply unit:
Uo = 17.5 V, Io = 380 mA, Po = 5.32 W

Linear barrier:
Uo = 24 V, Io = 250 mA, Po = 1.2 W

  • Effective internal inductance/capacitance

Li = 0.4 mH, Ci = 6 nF

Li = 7 μH, Ci = 1.1 nF

  • Dust explosion protection for zone 21/22

PTB 01 ATEX 2055

  • Marking

Ex II 2 D Ex tb IIIC T120°C Db

  • Wiring

To circuits with operating values: UH = 10.5 … 45 V DC; Pmax = 1.2 W

To circuits with operating values: UH = 9 … 32 V DC; Pmax = 1 W

  • Type of protection “n” (zone 2)

PTB 13 ATEX 2007 X

  • Marking

Ex II 2/3 G Ex nA IIC T4/T5/T6 Gc
Ex II 2/3 G Ex ic IIC T4/T5/T6 Gc

  • Connection (Ex nA)

Um = 45 V

Um = 32 V

  • Connection (Ex ic)

To circuits with operating values:
Ui = 45 V

FISCO supply unit:
Uo = 17.5 V, Io = 570 mA

Linear barrier:
Uo = 32 V, Io = 132 mA, Po = 1 W

  • Effective internal inductance/capacitance

Li = 0.4 mH, Ci = 6 nF

Li = 7 μH, Ci = 1.1 nF

  • Explosion protection acc. to FM

Certificate of Compliance 3008490

  • Marking (XP/DIP) or (IS); (NI)

CL I, DIV 1, GP ABCD T4…T6; CL II, DIV 1, GP EFG; CL III; CL I, ZN 0/1 AEx ia IIC T4…T6; CL I, DIV 2, GP ABCD T4…T6; CL II, DIV 2, GP FG; CL III

  • Explosion protection to CSA

Certificate of Compliance 1153651

  • Marking (XP/DIP) or (IS)

CL I, DIV 1, GP ABCD T4…T6; CL II, DIV 1, GP EFG; CL III; Ex ia IIC T4…T6; CL I, DIV 2, GP ABCD T4…T6; CL II, DIV 2, GP FG; CL III

Hygiene version

In the case of SITRANS P DS III with a 7MF413x flush-mounted diaphragm, selected connections comply with the requirements of EHEDG.

HART communication

HART

230 … 1100 Ω

Protocol

HART Version 5.x

Software for computer

SIMATIC PDM

PROFIBUS PA communication

Simultaneous communication with master class 2 (max.)

4

The address can be set using

Configuration tool or local operation (standard setting address 126)

Cyclic data usage

  • Output byte

5 (one measured value) or
10 (two measured values)

  • Input byte

0, 1, or 2 (register operating mode and reset function for metering)

Internal preprocessing

Device profile

PROFIBUS PA Profile for Process Control Devices Version 3.0, Class B

Function blocks

2

  • Analog input
  • Adaptation to user-specific process variable

Yes, linearly rising or falling characteristic

  • Electrical damping adjustable

0 … 100 s

  • Simulation function

Input /Output

  • Failure mode

parameterizable (last good value, substitute value, incorrect value)

  • Limit monitoring

Yes, one upper and lower warning limit and one alarm limit respectively

  • Register (totalizer)

Can be reset, preset, optional direction of counting, simulation function of register output

  • Failure mode

parameterizable (summation with last good value, continuous summation, summation with incorrect value)

  • Limit monitoring

One upper and lower warning limit and one alarm limit respectively

  • Physical block

1

Transducer blocks

2

  • Pressure transducer block
  • Can be calibrated by applying two pressures

Yes

  • Monitoring of sensor limits

Yes

  • Specification of a container characteristic with

Max. 30 nodes

  • Square-rooted characteristic for flow measurement

Yes

  • Gradual volume suppression and implementation point of square-root extraction

Parameterizable

  • Simulation function for measured pressure value and sensor temperature

Constant value or by means of parameterizable ramp function

FOUNDATION Fieldbus communication

Function blocks

3 function blocks analog input, 1 function block PID

  • Analog input
  • Adaptation to user-specific process variable

Yes, linearly rising or falling characteristic

  • Electrical damping adjustable

0 … 100 s

  • Simulation function

Output/input (can be locked within the device with a bridge)

  • Failure mode

parameterizable (last good value, substitute value, incorrect value)

  • Limit monitoring

Yes, one upper and lower warning limit and one alarm limit respectively

  • Square-rooted characteristic for flow measurement

Yes

  • PID

Standard FOUNDATION Fieldbus function block

  • Physical block

1 resource block

Transducer blocks

1 transducer block Pressure with calibration, 1 transducer block LCD

  • Pressure transducer block
  • Can be calibrated by applying two pressures

Yes

  • Monitoring of sensor limits

Yes

  • Simulation function: Measured pressure value, sensor temperature and electronics temperature

Constant value or by means of parameterizable ramp function

Dimensional drawings

SITRANS P DS III pressure transmitters for gauge pressure, with flush-mounted diaphragm, dimensions in mm (inches)

The diagram shows a SITRANS P DS III with an example of a flange. In this drawing the height is subdivided into H1and H2.

H1 = Height of the SITRANS P DS III up to a defined cross-section

H2 = Height of the flange up to this defined cross-section

Only the height H2 is indicated in the dimensions of the flanges.

Flanges as per EN and ASME

Flange to EN

EN 1092-1

 

Order code

DN

PN

∅D

H2

M11

25

40

115 mm (4.5″)

Approx. 52 mm (2″)

M21

25

100

140 mm (5.5″)

M13

40

40

150 mm (5.9″)

M23

40

100

170 mm (6.7″)

M04

50

16

165 mm (6.5″)

M14

50

40

165 mm (6.5″)

M06

80

16

200 mm (7.9″)

M16

80

40

200 mm (7.9″)

Flanges to ASME

ASME B16.5

 

Order code

DN

Class

∅D

H2

M40

1“

150

110 mm (4.3″)

Approx. 52 mm (2″)

M41

1½“

150

130 mm (5.1″)

M42

2“

150

150 mm (5.9″)

M43

3“

150

190 mm (7.5″)

M44

4“

150

230 mm (9.1″)

M45

1“

300

125 mm (4.9″)

M46

1½“

300

155 mm (6.1″)

M47

2“

300

165 mm (6.5″)

M48

3“

300

210 mm (8.1″)

M49

4“

300

255 mm (10.0″)

NuG and pharmaceutical connections

Connections to DIN

DIN 11851 (milk pipe union with slotted union nut)

 

Order code

DN

PN

∅D

H2

N04

50

25

92 mm (3.6″)

Approx. 52 mm (2″)

N06

80

25

127 mm (5.0″)

TriClamp to DIN 32676

 

Order code

DN

PN

∅D

H2

N14

50

16

64 mm (2.5″)

Approx. 52 mm (2″)

N15

65

10

91 mm (3.6″)

Other connections

Varivent connection

 

Order code

DN

PN

∅D

H2

N28

40 … 125

40

84 mm (3.3″)

Approx. 52 mm (2″)

Biocontrol connection

 

Order code

DN

PN

∅D

H2

Q53

50

16

90 mm (3.5″)

Approx. 52 mm (2″)

Q54

65

16

120 mm (4.7″)

Sanitary process connection to DRD

 

Order code

DN

PN

∅D

H2

M32

50

40

105 mm (4.1″)

Approx. 52 mm (2″)

Sanitary process screw connection to NEUMO Bio-Connect

 

Order code

DN

PN

∅D

H2

Q05

50

16

82 mm (3.2″)

Approx. 52 mm (2″)

Q06

65

16

105 mm (4.1″)

Q07

80

16

115 mm (4.5”)

Q08

100

16

145 mm (5.7″)

Q13

2”

16

82 mm (3.2″)

Q14

2½”

16

105 mm (4.1″)

Q15

3”

16

105 mm (4.1″)

Q16

4”

16

145 mm (5.7″)

Sanitary process connection to NEUMO Bio-Connect flange connection

 

Order code

DN

PN

∅D

H2

Q23

50

16

110 mm (4.3″)

Approx. 52 mm (2″)

Q24

65

16

140 mm (5.5″)

Q25

80

16

150 mm (5.9”)

Q26

100

16

175 mm (6.9″)

Q31

2”

16

100 mm (3.9″)

Q32

2½”

16

110 mm (4.3”)

Q33

3”

16

140 mm (5.5″)

Q34

4”

16

175 mm (6.9″)

Sanitary process connection to NEUMO Bio-Connect clamp connection

 

Order code

DN

PN

∅D

H2

Q39

50

16

77.4 mm (3.0″)

Approx. 52 mm (2″)

Q40

65

10

90.9 mm (3.6″)

Q41

80

10

106 mm (4.2″)

Q42

100

10

119 mm (4.7″)

Q47

2”

16

77.4 mm (3.0″)

Q48

2½”

10

90.9 mm (3.6″)

Q49

3”

10

106 mm (4.2″)

Q50

4”

10

119 mm (4.7″)

Sanitary process connection to NEUMO Bio-Connect S flange connection

 

Order code

DN

PN

∅D

H2

Q63

50

16

125 mm (4.9″)

Approx. 52 mm (2″)

Q64

65

10

145 mm (5.7″)

Q65

80

10

155 mm (6.1″)

Q66

100

10

180 mm (7.1″)

Q72

2”

16

125 mm (4.9″)

Q73

2½”

10

135 mm (5.3”)

Q74

3”

10

145 mm (5.7″)

Q75

4”

10

180 mm (7.1″)

Threaded connection G¾”, G1″ and G2″ acc. to DIN 3852

 

Order code

DN

PN

∅D

H2

R01

¾“

60

37 mm (1.5″)

approx. 45 mm (1.8″)

R02

1“

60

48 mm (1.9″)

approx. 47 mm (1.9″)

R04

2“

60

78 mm (3.1″)

Approx. 52 mm (2″)

Tank connection TG 52/50 and TG52/150

 

Order code

DN

PN

∅D

H2

R10

25

40

63 mm (2.5″)

approx. 63 mm (2.5″)

R11

25

40

63 mm (2.5″)

approx. 170 mm (6.7″)

SMS socket with union nut

 

Order code

DN

PN

∅D

H2

M67

2“

25

84 mm (3.3″)

Approx. 52 mm (2.1″)

M68

2½“

25

100 mm (3.9″)

M69

3“

25

114 mm (4.5″)

SMS threaded socket

 

Order code

DN

PN

∅D

H2

M73

2“

25

70 x 1/6 mm

Approx. 52 mm (2.1″)

M74

2½“

25

85 x 1/6 mm

M75

3“

25

98 x 1/6 mm

IDF socket with union nut

 

Order code

DN

PN

∅D

H2

M82

2“

25

77 mm (3″)

Approx. 52 mm (2.1″)

M83

2½“

25

91 mm (3.6″)

M84

3“

25

106 mm (4.2″)

IDF threaded socket

 

Order code

DN

PN

∅D

H2

M92

2“

25

64 mm (2.5″)

Approx. 52 mm (2.1″)

M93

2½“

25

77.5 mm (3.1″)

M94

3“

25

91 mm (3.6″)

Aseptic threaded socket to DIN 11864-1 Form A

 

Order code

DN

PN

∅D

H2

N33

50

25

78 x 1/6″

Approx. 52 mm (2.1″)

N34

65

25

95 x 1/6″

N35

80

25

110 x ¼”

N36

100

25

130 x ¼”

Aseptic flange with notch to DIN 11864-2 Form A

 

Order code

DN

PN

∅D

H2

N43

50

16

94

Approx. 52 mm (2.1″)

N44

65

16

113

N45

80

16

133

N46

100

16

159

Aseptic flange with groove to DIN 11864-2 Form A

 

Order code

DN

PN

∅D

H2

N43 + P11

50

16

94

Approx. 52 mm (2.1″)

N44 + P11

65

16

113

N45 + P11

80

16

133

N46 + P11

100

16

159

Aseptic clamp with groove to DIN 11864-3 Form A

 

Order code

DN

PN

∅D

H2

N53

50

25

77.5

Approx. 52 mm (2.1″)

N54

65

25

91

N55

80

16

106

N56

100

16

130

Popular Products Series

Mitsubishi F740 Series Frequency Inverter

The FR-F700 Series was launched in 2004 as the successor to the FR-F500 Series VFD. With growing market demands for energy saving inverters in building automation, water processing and HVAC industries, the FR-F700 was able to exceed power-saving expectations in fan and pump applications by incorporating “OEC” (optimum excitation control) which combined maximum drive utilization with minimal power consumption.

Siemens PLC spare part 6AV 6DD 6SN 6ES5 6ES7

Main supply Siemens 6ES7 6AV6 6AV3 6SE7 Spare parts...

Allen-Bradley 6176M Standard Industrial Monitors

Allen-Bradley 6176M Standard Industrial Monitors
6176M Standard Monitors are flat panel industrial color monitors for use in less demanding environments. All Standard Monitors have USB and RS232 touch screen inputs, DVI and VGA video inputs, and an On Screen Display (OSD) that enables image rotation, color pallet changes, and push button auto reset.

Allen-Bradley 6186M Performance Monitors

Simatic S7-200 Smart PLC

SIEMNES SIMATIC S7-200 Smart, newly launched micro PLC Product, is designed to suit the needs of developing markets that are under constant pressure due to price and demands for continuous performance. Providing an excellent performance – to – price ratio, SIMATIC S7 200 SMART when combined with other smart drive products from Siemens helps in building a cost effective yet efficient automation Solution.

ACS800-104/-104LC – inverter module

ACS800-04 – single drive modules

Siemens SIMOVERT MasterDrive Rectifier Regenerative Unit

Load more