- Standard controller with integrated safety functions:
- Standardized and convenient diagnostic functions for standard and safety
- Uniform symbols, data consistency, …
- Modular system with scalable range of CPUs and expandable I/O quantity structure:
- One engineering for standard and fail-safe automation
- Use of the standard I/O modules together with the fail-safe I/O modules in the central system
- Integrated standard PROFINET functionalities for PROFINET controllers and PROFINET iDevice services
- Connection of distributed standard I/O via field bus such as PROFINET or PROFIBUS
- F-library certified by the German Technical Inspectorate (TÜV) for all common safety functions
- Free programming of the safety logic using FBD and LAD
- Standard-compliant printout of the F-program
- One integrated engineering for both standard and safety from S7-1200 to S7-300/400/1500 and WinAC RTX F:
- STEP 7 Safety Basic for easy engineering of the CPU 1200 FC
- STEP 7 Safety Advanced for the entire fail-safe SIMATIC S7 portfolio
- Integrated system diagnosis of the CPUs, for standard and safety:
- Consistent plain text display of system diagnostic information in the TIA Portal, HMI and web server
- Messages are updated even if the CPU is in STOP state
- System diagnostics integrated in the CPU firmware. Configuration by user not required
- The diagnostics is automatically updated on configuration changes.
- 2 fail-safe compact controllers with graded performances in the versions DC/DC/DC and DC/DC/relay
Technical specifications
ARTICLE NUMBER | 6ES7212-1AF40-0XB0 | 6ES7212-1HF40-0XB0 | 6ES7214-1AF40-0XB0 | 6ES7214-1HF40-0XB0 | 6ES7215-1AF40-0XB0 | 6ES7215-1HF40-0XB0 | |
---|---|---|---|---|---|---|---|
CPU 1212FC ,DC/DC/DC, 8DI/6DO/2AI | CPU 1212FC, DC/DC/RELAY, 8DI/6DO/2AI | CPU 1214 FC, DC/DC/DC, 14DI/10DO/2AI | CPU 1214 FC, DC/DC/RELAY, 14DI/10DO/2AI | CPU 1215 FC, DC/DC/DC, 14DI/10DO/2AI/2AO | CPU 1215 FC, DC/DC/RLY,14DI/10DO/2AI/2AO | ||
General information | |||||||
Product type designation | CPU 1212FC DC/DC/DC | CPU 1214FC DC/DC | CPU 1214FC DC/DC/Relay | CPU 1215FC DC/DC/DC | |||
Firmware version | V4.2 | V4.2 | V4.2 | V4.2 | V4.2 | V4.2 | |
Engineering with | |||||||
| STEP 7 V14 or higher | STEP 7 V14 or higher | STEP 7 V14 or higher | STEP 7 V14 or higher | STEP 7 V14 or higher | STEP 7 V14 or higher | |
Supply voltage | |||||||
Rated value (DC) | |||||||
| Yes | Yes | Yes | Yes | Yes | Yes | |
permissible range, lower limit (DC) | 20.4 V | 20.4 V | 20.4 V | 20.4 V | 20.4 V | 20.4 V | |
permissible range, upper limit (DC) | 28.8 V | 28.8 V | 28.8 V | 28.8 V | 28.8 V | 28.8 V | |
Reverse polarity protection | Yes | Yes | |||||
Load voltage L+ | |||||||
| 24 V | 24 V | 24 V | 24 V | 24 V | ||
| 20.4 V | 20.4 V | 20.4 V | 20.4 V | 20.4 V | ||
| 28.8 V | 28.8 V | 28.8 V | 28.8 V | 28.8 V | ||
Input current | |||||||
Current consumption (rated value) | 375 mA; Typical | 500 mA; CPU only | 500 mA; CPU only | ||||
Current consumption, max. | 1 500 mA; max. with all expansion accessories | 1 500 mA; max. with all expansion accessories | 1 500 mA; CPU with all expansion modules | 1 500 mA; CPU with all expansion modules | |||
Inrush current, max. | 12 A; at 28.8 V DC | 12 A; at 28.8 V DC | 12 A; at 28.8 V DC | 12 A; at 28.8 V DC | 12 A; at 28.8 V DC | ||
I²t | 0.5 A²·s | 0.5 A²·s | 0.5 A²·s | 0.5 A²·s | 0.5 A²·s | 0.5 A²·s | |
Output current | |||||||
for backplane bus (5 V DC), max. | 1 000 mA; Max. 5 V DC for SM and CM | 1 000 mA; Max. 5 V DC for SM and CM | 1 600 mA; Max. 5 V DC for SM and CM | 1 600 mA; Max. 5 V DC for SM and CM | 1 600 mA; Max. 5 V DC for SM and CM | 1 600 mA; Max. 5 V DC for SM and CM | |
Encoder supply | |||||||
24 V encoder supply | |||||||
| Permissible range: 20.4V to 28.8V | Permissible range: 20.4V to 28.8V | L+ minus 4 V DC min. | L+ minus 4 V DC min. | L+ minus 4 V DC min. | L+ minus 4 V DC min. | |
Power loss | |||||||
Power loss, typ. | 9 W | 9 W | 12 W | 12 W | 12 W | 12 W | |
Memory | |||||||
Work memory | |||||||
| 100 kbyte | 100 kbyte | 125 kbyte | 125 kbyte | 150 kbyte | 150 kbyte | |
| No | No | No | No | No | No | |
Load memory | |||||||
| 2 Mbyte | 2 Mbyte | 4 Mbyte | 4 Mbyte | 4 Mbyte | 4 Mbyte | |
| with SIMATIC memory card | with SIMATIC memory card | with SIMATIC memory card | with SIMATIC memory card | with SIMATIC memory card | with SIMATIC memory card | |
Backup | |||||||
| Yes | Yes | Yes | Yes | Yes | Yes | |
| Yes | Yes | Yes | Yes | Yes | Yes | |
| Yes | Yes | Yes | Yes | Yes | Yes | |
CPU processing times | |||||||
for bit operations, typ. | 0.08 µs; / instruction | 0.08 µs; / instruction | 0.08 µs; / instruction | 0.08 µs; / instruction | 0.08 µs; / instruction | 0.08 µs; / instruction | |
for word operations, typ. | 1.7 µs; / instruction | 1.7 µs; / instruction | 1.7 µs; / instruction | 1.7 µs; / instruction | 1.7 µs; / instruction | 1.7 µs; / instruction | |
for floating point arithmetic, typ. | 2.5 µs; / instruction | 2.5 µs; / instruction | 2.3 µs; / instruction | 2.3 µs; / instruction | 2.3 µs; / instruction | 2.3 µs; / instruction | |
CPU-blocks | |||||||
Number of blocks (total) | DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used | DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used | DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used | DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used | DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used | DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used | |
OB | |||||||
| Limited only by RAM for code | Limited only by RAM for code | Limited only by RAM for code | Limited only by RAM for code | Limited only by RAM for code | Limited only by RAM for code | |
Data areas and their retentivity | |||||||
Retentive data area (incl. timers, counters, flags), max. | 10 kbyte | 10 kbyte | 10 kbyte | 10 kbyte | 10 kbyte | 10 kbyte | |
Flag | |||||||
| 4 kbyte; Size of bit memory address area | 4 kbyte; Size of bit memory address area | 8 kbyte; Size of bit memory address area | 8 kbyte; Size of bit memory address area | 8 kbyte; Size of bit memory address area | 8 kbyte; Size of bit memory address area | |
Local data | |||||||
| 16 kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB | 16 kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB | 16 kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB | 16 kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB | 16 kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB | 16 kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB | |
Address area | |||||||
I/O address area | |||||||
| 1 024 byte | 1 024 byte | 1 024 byte | ||||
| 1 024 byte | 1 024 byte | 1 024 byte | ||||
Process image | |||||||
| 1 kbyte | 1 kbyte | 1 kbyte | 1 kbyte | 1 kbyte | 1 kbyte | |
| 1 kbyte | 1 kbyte | 1 kbyte | 1 kbyte | 1 kbyte | 1 kbyte | |
Hardware configuration | |||||||
Number of modules per system, max. | 3 comm. modules, 1 signal board, 2 signal modules | 3 comm. modules, 1 signal board, 2 signal modules | 3 comm. modules, 1 signal board, 8 signal modules | 3 comm. modules, 1 signal board, 8 signal modules | 3 comm. modules, 1 signal board, 8 signal modules | 3 comm. modules, 1 signal board, 8 signal modules | |
Time of day | |||||||
Clock | |||||||
| Yes | Yes | Yes | Yes | Yes | ||
| 480 h; Typical | 480 h; Typical | 480 h; typical; 12 days min. at 40 °C | 480 h; Typical | 480 h; Typical | ||
| 60 s/month at 25 °C | 60 s/month at 25 °C | ±60 s per month | 60 s/month at 25 °C | 60 s/month at 25 °C | ||
Digital inputs | |||||||
Number of digital inputs | 8; Integrated | 8; Integrated | 14 | 14 | 14; Integrated | 14; Integrated | |
| 4; HSC (High Speed Counting) | 4; HSC (High Speed Counting) | 6; HSC (High Speed Counting) | 6; HSC (High Speed Counting) | 6; HSC (High Speed Counting) | ||
Source/sink input | Yes | Yes | Yes | Yes | Yes | ||
Number of simultaneously controllable inputs | |||||||
all mounting positions | |||||||
| 8 | 8 | 14; 14 inputs at 55 °C horizontal or 45 °C vertical | 14 | 14 | ||
Input voltage | |||||||
| 24 V | 24 V | 24 V; DC at 4 mA nominal | 24 V | 24 V | ||
| 5 V DC at 1 mA | 5 V DC at 1 mA | 5 V DC at 1 mA | 5 V DC at 1 mA | 5 V DC at 1 mA | ||
| 15 V DC at 2.5 mA | 15 V DC at 2.5 mA | 15 V DC at 2.5 mA | 15 V DC at 2.5 mA | 15 V DC at 2.5 mA | ||
Input current | |||||||
| 1 mA | 1 mA | 4 mA; nominal | ||||
Input delay (for rated value of input voltage) | |||||||
for standard inputs | |||||||
| 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four | 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four | 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 μs; 0.05 / 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 ms | Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four | Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four | ||
| 0.2 ms | 0.2 ms | 0.1 µs | 0.2 ms | 0.2 ms | ||
| 12.8 ms | 12.8 ms | 20 ms | 12.8 ms | 12.8 ms | ||
for interrupt inputs | |||||||
| Yes | Yes | Yes | Yes | Yes | ||
for counter/technological functions | |||||||
| Single phase: 3 @ 100 kHz & 1 @ 30 kHz, differential: 3 @ 80 kHz & 1 @ 30 kHz | Yes; Single phase: 3 @ 100 kHz & 3 @ 30 kHz, differential: 3 @ 80 kHz & 3 @ 30 kHz | Single phase: 3 @ 100 kHz & 3 @ 30 kHz, differential: 3 @ 80 kHz & 3 @ 30 kHz | Single phase: 3 @ 100 kHz & 3 @ 30 kHz, differential: 3 @ 80 kHz & 3 @ 30 kHz | |||
Cable length | |||||||
| 500 m; 50 m for technological functions | 500 m; 50 m for technological functions | 500 m; 50 m for technological functions | 500 m; 50 m for technological functions | |||
| 300 m; For technological functions: No | 150 m; For technological functions: No | 300 m; For technological functions: No | 300 m; For technological functions: No | |||
Digital outputs | |||||||
Number of digital outputs | 6 | 6 | 10 | 10 | 10 | 10; Relays | |
| 4; 100 kHz Pulse Train Output | 4; 100 kHz Pulse Train Output | 4; 100 kHz Pulse Train Output | ||||
Short-circuit protection | No; to be provided externally | No; to be provided externally | |||||
Limitation of inductive shutdown voltage to | L+ (-48 V) | L+ (-48 V) | |||||
Switching capacity of the outputs | |||||||
| 0.5 A | 2 A | 0.5 A | 0.5 A | 2 A | ||
| 5 W | 30 W with DC, 200 W with AC | 5 W | 5 W | 30 W with DC, 200 W with AC | ||
Output voltage | |||||||
| 0.1 V; with 10 kOhm load | 0.1 V; with 10 kOhm load | 0.1 V; with 10 kOhm load | ||||
| 20 V | 20 V | 20 V | ||||
Output current | |||||||
| 0.5 A | 0.5 A | 0.5 A | ||||
| 0.1 mA | 0.1 mA | 0.1 mA | ||||
Output delay with resistive load | |||||||
| 1 µs | 10 ms; max. | 1 µs | 1 µs | 10 ms; max. | ||
| 5 µs | 10 ms; max. | 3 µs | 5 µs | 10 ms; max. | ||
Switching frequency | |||||||
| 100 kHz | 1 Hz | 100 kHz | 100 kHz | |||
Relay outputs | |||||||
| mechanically 10 million, at rated load voltage 100 000 | ||||||
Cable length | |||||||
| 500 m | 500 m | 500 m | 500 m | 500 m | ||
| 150 m | 150 m | 150 m | 150 m | 150 m | ||
Analog inputs | |||||||
Number of analog inputs | 2 | 2 | 2 | 2 | 2 | 2 | |
Input ranges | |||||||
| Yes | Yes | Yes | Yes | Yes | Yes | |
Input ranges (rated values), voltages | |||||||
| Yes | Yes | Yes | Yes | Yes | Yes | |
| ≥100k ohms | ≥100k ohms | ≥100k ohms | ≥100k ohms | ≥100k ohms | ≥100k ohms | |
Cable length | |||||||
| 100 m; twisted and shielded | 100 m; twisted and shielded | 100 m; twisted and shielded | 100 m; twisted and shielded | 100 m; twisted and shielded | 100 m; twisted and shielded | |
Analog outputs | |||||||
Number of analog outputs | 0 | 0 | 0 | 0 | 2 | 2 | |
Output ranges, current | |||||||
| Yes | Yes | Yes | ||||
Analog value generation for the inputs | |||||||
Integration and conversion time/resolution per channel | |||||||
| 10 bit | 10 bit | 10 bit | 10 bit | 10 bit | 10 bit | |
| Yes | Yes | Yes | Yes | Yes | Yes | |
| 625 µs | 625 µs | 625 µs | 625 µs | 625 µs | 625 µs | |
Analog value generation for the outputs | |||||||
Integration and conversion time/resolution per channel | |||||||
| 10 bit | 10 bit | |||||
Encoder | |||||||
Connectable encoders | |||||||
| Yes | Yes | Yes | Yes | Yes | Yes | |
1. Interface | |||||||
Interface type | PROFINET | PROFINET | PROFINET | PROFINET | PROFINET | PROFINET | |
Physics | Ethernet | Ethernet | Ethernet | Ethernet | Ethernet | Ethernet | |
Isolated | Yes | Yes | Yes | Yes | Yes | Yes | |
automatic detection of transmission rate | Yes | Yes | Yes | Yes | Yes | Yes | |
Autonegotiation | Yes | Yes | Yes | Yes | Yes | Yes | |
Autocrossing | Yes | Yes | Yes | Yes | Yes | Yes | |
Interface types | |||||||
| 1 | 1 | 1 | 1 | 2 | 2 | |
| Yes | Yes | Yes | Yes | Yes | Yes | |
Functionality | |||||||
| Yes | Yes | Yes | Yes | Yes | Yes | |
| Yes | Yes | Yes | Yes | Yes | Yes | |
| Yes | Yes | Yes | Yes | Yes | Yes | |
| Yes | Yes | Yes | Yes | Yes | Yes | |
| Yes | Yes | Yes | Yes | Yes | Yes | |
| Yes; as MRP client | Yes; as MRP client | Yes; as MRP client | Yes; as MRP client | |||
PROFINET IO Controller | |||||||
| 100 Mbit/s | 100 Mbit/s | 100 Mbit/s | 100 Mbit/s | 100 Mbit/s | 100 Mbit/s | |
Services | |||||||
| Yes | Yes | Yes | Yes | Yes | Yes | |
| Yes | Yes | Yes | Yes | Yes | Yes | |
| No | No | No | No | No | No | |
| Yes | Yes | Yes | Yes | Yes | Yes | |
| No | No | No | No | No | No | |
| No | No | No | No | Yes; as MRP client | Yes; as MRP client | |
| No | No | No | No | No | No | |
| No | No | No | No | No | No | |
| Yes | Yes | Yes | Yes | Yes | Yes | |
| 16 | 16 | 16 | 16 | 16 | 16 | |
| 16 | 16 | 16 | 16 | 16 | 16 | |
| 16 | 16 | 16 | 16 | 16 | 16 | |
| 16 | 16 | 16 | 16 | 16 | 16 | |
| Yes | Yes | Yes | Yes | Yes | Yes | |
| 8 | 8 | 8 | 8 | 8 | 8 | |
| The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data. | The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data. | The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data. | The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data. | The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data. | The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data. | |
PROFINET IO Device | |||||||
Services | |||||||
| Yes | Yes | Yes | Yes | Yes | Yes | |
| Yes | Yes | Yes | Yes | Yes | Yes | |
| No | No | No | No | No | No | |
| Yes | Yes | Yes | Yes | Yes | Yes | |
| No | No | No | No | No | No | |
| No | No | No | No | Yes; as MRP client | Yes; as MRP client | |
| No | No | No | No | No | No | |
| Yes | Yes | Yes | Yes | Yes | Yes | |
| Yes | Yes | Yes | Yes | Yes | Yes | |
| 2 | 2 | 2 | 2 | 2 | 2 | |
Protocols | |||||||
Supports protocol for PROFINET IO | Yes | Yes | Yes | Yes | Yes | Yes | |
PROFIBUS | Yes; CM 1243-5 required | Yes; CM 1243-5 required | Yes; CM 1243-5 required | Yes; CM 1243-5 required | Yes; CM 1243-5 required | Yes; CM 1243-5 required | |
AS-Interface | Yes; CM 1243-2 required | Yes; CM 1243-2 required | Yes; CM 1243-2 required | Yes; CM 1243-2 required | Yes; CM 1243-2 required | Yes; CM 1243-2 required | |
Protocols (Ethernet) | |||||||
| Yes | Yes | Yes | Yes | Yes | Yes | |
| No | No | No | No | No | No | |
| Yes | Yes | Yes | Yes | Yes | Yes | |
| Yes | Yes | Yes | Yes | Yes | Yes | |
| Yes | Yes | Yes | Yes | Yes | Yes | |
Open IE communication | |||||||
| |||||||
| 8 kbyte | 8 kbyte | 8 kbyte | 8 kbyte | 8 kbyte | 8 kbyte | |
| Yes | Yes | Yes | Yes | Yes | Yes | |
| 8 kbyte | 8 kbyte | 8 kbyte | 8 kbyte | 8 kbyte | 8 kbyte | |
| |||||||
| 1 472 byte | 1 472 byte | 1 472 byte | 1 472 byte | 1 472 byte | 1 472 byte | |
Further protocols | |||||||
| Yes | Yes | Yes | Yes | Yes | Yes | |
Communication functions | |||||||
S7 communication | |||||||
| Yes | Yes | Yes | Yes | Yes | Yes | |
| Yes | Yes | Yes | Yes | Yes | Yes | |
| Yes | Yes | Yes | Yes | Yes | Yes | |
| See online help (S7 communication, user data size) | See online help (S7 communication, user data size) | See online help (S7 communication, user data size) | See online help (S7 communication, user data size) | See online help (S7 communication, user data size) | See online help (S7 communication, user data size) | |
Open IE communication | |||||||
| Yes | Yes | Yes | Yes | Yes | Yes | |
| Yes | Yes | Yes | Yes | Yes | Yes | |
Web server | |||||||
| Yes | Yes | Yes | Yes | Yes | Yes | |
| Yes | Yes | Yes | Yes | Yes | Yes | |
Number of connections | |||||||
| 16; dynamically | 16; dynamically | 16; dynamically | 16; dynamically | |||
Test commissioning functions | |||||||
Status/control | |||||||
| Yes | Yes | Yes | Yes | Yes | Yes | |
| Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters | Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters | Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters | Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters | Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters | Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters | |
Forcing | |||||||
| Yes | Yes | Yes | Yes | Yes | Yes | |
Diagnostic buffer | |||||||
| Yes | Yes | Yes | Yes | Yes | Yes | |
Traces | |||||||
| 2 | 2 | 2 | 2 | 2 | 2 | |
| 512 kbyte | 512 kbyte | 512 kbyte | 512 kbyte | 512 kbyte | 512 kbyte | |
Interrupts/diagnostics/status information | |||||||
Diagnostics indication LED | |||||||
| Yes | Yes | |||||
| Yes | Yes | |||||
| Yes | Yes | |||||
Integrated Functions | |||||||
Number of counters | 4 | 4 | 6 | 6 | 6 | 6 | |
Counting frequency (counter) max. | 100 kHz | 100 kHz | 100 kHz | 100 kHz | 100 kHz | 100 kHz | |
Frequency meter | Yes | Yes | Yes | Yes | Yes | Yes | |
controlled positioning | Yes | Yes | Yes | Yes | Yes | Yes | |
Number of position-controlled positioning axes, max. | 8 | 8 | 8 | 8 | 8 | 8 | |
Number of positioning axes via pulse-direction interface | Up to 4 with SB 1222 | Up to 4 with SB 1222 | Up to 4 with SB 1222 | Up to 4 with SB 1222 | 4; With integrated outputs | Up to 4 with SB 1222 | |
PID controller | Yes | Yes | Yes | Yes | Yes | Yes | |
Number of alarm inputs | 4 | 4 | 4 | 4 | 4 | ||
Number of pulse outputs | 4 | 4 | 4 | ||||
Limit frequency (pulse) | 100 kHz | 100 kHz | |||||
Potential separation | |||||||
Potential separation digital inputs | |||||||
| 500V AC for 1 minute | 500V AC for 1 minute | Functional isolation (Optocoupler) | No | 500V AC for 1 minute | ||
| 1 | 1 | 1 | 1 | |||
Potential separation digital outputs | |||||||
| Yes | Relays | Yes | Relays | |||
| No | No | No | No | |||
| 1 | 1 | 1 | 2 | |||
Permissible potential difference | |||||||
between different circuits | 500 V DC between 24 V DC and 5 V DC | 500 V DC between 24 V DC and 5 V DC | |||||
EMC | |||||||
Interference immunity against discharge of static electricity | |||||||
| Yes | Yes | Yes | Yes | Yes | Yes | |
| 8 kV | 8 kV | 8 kV | 8 kV | 8 kV | 8 kV | |
| 6 kV | 6 kV | 6 kV | 6 kV | 6 kV | 6 kV | |
Interference immunity to cable-borne interference | |||||||
| Yes | Yes | Yes | Yes | Yes | Yes | |
| Yes | Yes | Yes | Yes | Yes | Yes | |
Interference immunity against voltage surge | |||||||
| Yes | Yes | Yes | Yes | Yes | Yes | |
Interference immunity against conducted variable disturbance induced by high-frequency fields | |||||||
| Yes | Yes | Yes | Yes | Yes | Yes | |
Emission of radio interference acc. to EN 55 011 | |||||||
| Yes; Group 1 | Yes; Group 1 | Yes; Group 1 | Yes; Group 1 | Yes; Group 1 | Yes; Group 1 | |
| Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011 | Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011 | Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011 | Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011 | Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011 | Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011 | |
Degree and class of protection | |||||||
Degree of protection acc. to EN 60529 | |||||||
| Yes | Yes | Yes | Yes | Yes | ||
Standards, approvals, certificates | |||||||
CE mark | Yes | Yes | Yes | Yes | Yes | Yes | |
UL approval | Yes | Yes | Yes | Yes | Yes | Yes | |
cULus | Yes | Yes | Yes | Yes | Yes | Yes | |
FM approval | Yes | Yes | Yes | Yes | Yes | Yes | |
RCM (formerly C-TICK) | Yes | Yes | Yes | Yes | Yes | Yes | |
KC approval | Yes | Yes | Yes | Yes | Yes | Yes | |
Marine approval | Yes | Yes | Yes | Yes | Yes | Yes | |
Highest safety class achievable in safety mode | |||||||
| PLe | PLe | PLe | PLe | PLe | PLe | |
| SIL 3 | SIL 3 | SIL 3 | SIL 3 | SIL 3 | SIL 3 | |
Ambient conditions | |||||||
Free fall | |||||||
| 0.3 m; five times, in product package | 0.3 m; five times, in product package | 0.3 m; five times, in product package | 0.3 m; five times, in product package | 0.3 m; five times, in product package | ||
Ambient temperature during operation | |||||||
| 0 °C | 0 °C | 0 °C | 0 °C | 0 °C | 0 °C | |
| 55 °C | 55 °C | 55 °C | 55 °C | 55 °C | 55 °C | |
| 0 °C | 0 °C | 0 °C | 0 °C | 0 °C | 0 °C | |
| 55 °C | 55 °C | 55 °C | 55 °C | 55 °C | 55 °C | |
| 0 °C | 0 °C | 0 °C | 0 °C | 0 °C | 0 °C | |
| 45 °C | 45 °C | 45 °C | 45 °C | 45 °C | 45 °C | |
Ambient temperature during storage/transportation | |||||||
| -40 °C | -40 °C | -40 °C | -40 °C | -40 °C | -40 °C | |
| 70 °C | 70 °C | 70 °C | 70 °C | 70 °C | 70 °C | |
Air pressure acc. to IEC 60068-2-13 | |||||||
| 795 hPa | 795 hPa | |||||
| 1 080 hPa | 1 080 hPa | |||||
| 660 hPa | 660 hPa | 660 hPa | 660 hPa | 660 hPa | 660 hPa | |
| 1 139 hPa | 1 139 hPa | 1 139 hPa | 1 139 hPa | 1 080 hPa | 1 080 hPa | |
| -1000 to 2000 m | -1000 to 2000 m | -1000 to 2000 m | -1000 to 2000 m | -1000 to 2000 m | -1000 to 2000 m | |
Relative humidity | |||||||
| 95 %; no condensation | 95 %; no condensation | 95 %; no condensation | 95 %; no condensation | 95 %; no condensation | 95 %; no condensation | |
Vibrations | |||||||
| 2 g (m/s²) wall mounting, 1 g (m/s²) DIN rail | 2 g (m/s²) wall mounting, 1 g (m/s²) DIN rail | 2 g (m/s²) wall mounting, 1 g (m/s²) DIN rail | 2 g (m/s²) wall mounting, 1 g (m/s²) DIN rail | 2 g (m/s²) wall mounting, 1 g (m/s²) DIN rail | 2 g (m/s²) wall mounting, 1 g (m/s²) DIN rail | |
| Yes | Yes | Yes | Yes | Yes | Yes | |
Shock test | |||||||
| Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms | Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms | Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms | Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms | Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms | Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms | |
Pollutant concentrations | |||||||
| S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free | S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free | S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free | S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free | S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free | S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free | |
Programming | |||||||
Programming language | |||||||
| Yes; incl. failsafe | Yes; incl. failsafe | Yes; incl. failsafe | Yes; incl. failsafe | Yes; incl. failsafe | Yes; incl. failsafe | |
| Yes; incl. failsafe | Yes; incl. failsafe | Yes; incl. failsafe | Yes; incl. failsafe | Yes; incl. failsafe | Yes; incl. failsafe | |
| Yes | Yes | Yes | Yes | Yes | Yes | |
Know-how protection | |||||||
| Yes | Yes | Yes | Yes | Yes | Yes | |
| Yes | Yes | Yes | Yes | Yes | Yes | |
| Yes | Yes | Yes | Yes | Yes | Yes | |
Access protection | |||||||
| Yes | Yes | |||||
| Yes | Yes | |||||
| Yes | Yes | |||||
Cycle time monitoring | |||||||
| Yes | Yes | Yes | Yes | Yes | Yes | |
Dimensions | |||||||
Width | 90 mm | 90 mm | 110 mm | 110 mm | 130 mm | 130 mm | |
Height | 100 mm | 100 mm | 100 mm | 100 mm | 100 mm | 100 mm | |
Depth | 75 mm | 75 mm | 75 mm | 75 mm | 75 mm | 75 mm | |
Weights | |||||||
Weight, approx. | 370 g | 385 g | 435 g | 435 g | 585 g | 585 g |