Global Company
We are an international company in the UK and HK
Are you looking for SIEMENS 6ES7322-5RD00-0AB0 PLC Module Original and Made in Germany
We are an international company in the UK and HK
Save you 30% of the purchasing cost
Quick quote and quick delivery for each order/request.
Fast shipping and Quick Delivery use DHL/UPS/TNT
Supply voltage | ||
Load voltage L+ | ||
● Rated value (DC) | 24 V | |
● Reverse polarity protection | Yes | |
Input current | ||
from load voltage L+ (without load), max. | 160 mA | |
from backplane bus 5 V DC, max. | 85 mA | |
Power loss | ||
Power loss, typ. | 3 W | |
Digital outputs | ||
Number of digital outputs | 4 | |
Short-circuit protection | Yes; Electronic | |
● Response threshold, typ. | Output current with short-circuit protection, min. 20.5 mA + 10 % | |
Load resistance range | ||
● upper limit | 200 Ω; Two-wire connection | |
Output voltage | ||
● Rated value (DC) | 15 V | |
Output current | ||
● for signal "1" permissible range for 0 to 60 °C, max. | 20 mA; +/-10 % | |
Switching frequency | ||
● with resistive load, max. | 100 Hz | |
Cable length | ||
● unshielded, max. | 200 m | |
Interrupts/diagnostics/status information | ||
Diagnostic functions | Yes | |
Diagnostic messages | ||
● Diagnostic information readable | Yes | |
● Short-circuit | Yes | |
Diagnostics indication LED | ||
● Group error SF (red) | Yes | |
● Status indicator digital output (green) | Yes | |
● Channel fault indicator F (red) | Yes | |
Ex(i) characteristics | ||
Module for Ex(i) protection | Yes | |
Maximum values of output circuits (per channel) | ||
● Co (permissible external capacity), max. | 500 nF | |
● Io (short-circuit current), max. | 85 mA | |
● Lo (permissible external inductivity), max. | 5 mH | |
● Po (power of load), max. | 335 mW | |
● Uo (output no-load voltage), max. | 15.75 V | |
Potential separation | ||
Potential separation digital outputs | ||
● Potential separation digital outputs | Yes | |
● between the channels, in groups of | 1 | |
Standards, approvals, certificates | ||
Use in hazardous areas | ||
● Type of protection acc. to EN 50020 (CENELEC) | [EEx ib] IIC | |
● Type of protection acc. to FM | AIS CL.1, DIV 1, GP A, B, C, D; CL.I, DIV 2, GP A, B, C, D T4 | |
● Test number PTB | Ex-96.D.2102X | |
Ambient conditions | ||
Ambient temperature during operation | ||
● max. | 60 °C | |
Connection method | ||
required front connector | 20-pin | |
Weights | ||
Weight, approx. | 230 g |
AoteWell Automation Team Supply of PLC system, servo drive, HMI, display, electrical machinery, CNC machine tools and various parts of the system and the robot to maintenance, including all the major manufacturers.