General information | ||
Hardware product version | 1 | |
Firmware version | V4.5 | |
Engineering with | ||
● Programming package | STEP 7 V5.3 SP2 or higher with HW update | |
CiR – Configuration in RUN | ||
CiR synchronization time, basic load | 60 ms | |
CiR synchronization time, time per I/O byte | 10 µs | |
Supply voltage | ||
Rated value (DC) | ||
● 24 V DC | No; Power supply via system power supply | |
Input current | ||
from backplane bus 5 V DC, typ. | 1.5 A | |
from backplane bus 5 V DC, max. | 1.8 A | |
from backplane bus 24 V DC, max. | 150 mA; Per DP interface | |
from interface 5 V DC, max. | 90 mA; At each DP interface | |
Power loss | ||
Power loss, typ. | 6.5 W | |
Memory | ||
Type of memory | other | |
Work memory | ||
● integrated | 30 Mbyte | |
● integrated (for program) | 15 Mbyte | |
● integrated (for data) | 15 Mbyte | |
● expandable | No | |
Load memory | ||
● expandable FEPROM | Yes | |
● expandable FEPROM, max. | 64 Mbyte | |
● integrated RAM, max. | 256 kbyte | |
● expandable RAM | Yes | |
● expandable RAM, max. | 64 Mbyte | |
Backup | ||
● present | Yes | |
● with battery | Yes; all data | |
● without battery | No | |
Battery | ||
Backup battery | ||
● Backup current, typ. | 970 µA; Valid up to 40°C | |
● Backup current, max. | 1 980 µA | |
● Backup time, max. | Dealt with in the module data manual with the secondary conditions and the factors of influence | |
● Feeding of external backup voltage to CPU | 5 V DC to 15 V DC | |
CPU processing times | ||
for bit operations, typ. | 0.018 µs | |
for word operations, typ. | 0.018 µs | |
for fixed point arithmetic, typ. | 0.018 µs | |
for floating point arithmetic, typ. | 0.054 µs | |
CPU-blocks | ||
DB | ||
● Number, max. | 8 191; Number range: 1 - 8191 | |
● Size, max. | 64 kbyte | |
FB | ||
● Number, max. | 6 144; Number range: 0 - 6143 | |
● Size, max. | 64 kbyte | |
FC | ||
● Number, max. | 6 144; Number range: 0 - 6143 | |
● Size, max. | 64 kbyte | |
OB | ||
● Size, max. | 64 kbyte | |
● Number of time alarm OBs | 8 | |
● Number of delay alarm OBs | 4 | |
● Number of cyclic interrupt OBs | 9 | |
● Number of process alarm OBs | 8 | |
Nesting depth | ||
● per priority class | 24 | |
● additional within an error OB | 2 | |
Counters, timers and their retentivity | ||
S7 counter | ||
● Number | 2 048 | |
Retentivity | ||
— adjustable | Yes | |
— lower limit | 0 | |
— upper limit | 2 047 | |
— preset | Z 0 to Z 7 | |
Counting range | ||
— lower limit | 0 | |
— upper limit | 999 | |
S7 times | ||
● Number | 2 048 | |
Retentivity | ||
— adjustable | Yes | |
— lower limit | 0 | |
— upper limit | 2 047 | |
— preset | No times retentive | |
Time range | ||
— lower limit | 10 ms | |
— upper limit | 9 990 s | |
IEC timer | ||
● present | Yes | |
● Type | SFB | |
Data areas and their retentivity | ||
retentive data area in total | Total working and load memory (with backup battery) | |
Flag | ||
● Number, max. | 16 kbyte | |
● Retentivity available | Yes | |
● Retentivity preset | MB 0 to MB 15 | |
● Number of clock memories | 8; in 1 memory byte | |
Data blocks | ||
● Number, max. | 8 191; Number range: 1 - 8191 | |
● Size, max. | 64 kbyte | |
Local data | ||
● adjustable, max. | 64 kbyte | |
● preset | 32 kbyte | |
Address area | ||
I/O address area | ||
● Inputs | 16 kbyte | |
● Outputs | 16 kbyte | |
of which distributed | ||
— MPI/DP interface, inputs | 2 kbyte | |
— MPI/DP interface, outputs | 2 kbyte | |
— DP interface, inputs | 8 kbyte | |
— DP interface, outputs | 8 kbyte | |
Process image | ||
● Inputs, adjustable | 16 kbyte | |
● Outputs, adjustable | 16 kbyte | |
● Inputs, default | 1 024 byte | |
● Outputs, default | 1 024 byte | |
● consistent data, max. | 244 byte | |
● Access to consistent data in process image | Yes | |
Subprocess images | ||
● Number of subprocess images, max. | 15 | |
Digital channels | ||
● Inputs | 131 072 | |
— of which central | 131 072 | |
● Outputs | 131 072 | |
— of which central | 131 072 | |
Analog channels | ||
● Inputs | 8 192 | |
— of which central | 8 192 | |
● Outputs | 8 192 | |
— of which central | 8 192 | |
Hardware configuration | ||
Number of expansion units, max. | 21 | |
connectable OPs | 63 without message processing, 16 with message processing | |
Multicomputing | No | |
Interface modules | ||
● Number of connectable IMs (total), max. | 6 | |
● Number of connectable IM 460s, max. | 6 | |
● Number of connectable IM 463s, max. | 4; Single mode only | |
Number of DP masters | ||
● integrated | 2 | |
● via CP | 10 | |
● Mixed mode IM + CP permitted | No | |
Number of operable FMs and CPs (recommended) | ||
● FM | See manual Automation System S7-400H fault-tolerant systems. Limited by number of slots and number of connections | |
● CP, PtP | See manual Automation System S7-400H fault-tolerant systems. Limited by number of slots and number of connections | |
● PROFIBUS and Ethernet CPs | 14; Of which max. 10 CP as DP master | |
Slots | ||
● required slots | 2 | |
Time of day | ||
Clock | ||
● Hardware clock (real-time) | Yes | |
● retentive and synchronizable | Yes | |
● Resolution | 1 ms | |
● Deviation per day (buffered), max. | 1.7 s; Power off | |
● Deviation per day (unbuffered), max. | 8.6 s; Power on | |
Operating hours counter | ||
● Number | 8 | |
● Number/Number range | 0 to 7 | |
● Range of values | 0 to 32767 hours | |
● Granularity | 1 hour | |
● retentive | Yes | |
Clock synchronization | ||
● supported | Yes | |
● to MPI, master | Yes | |
● to MPI, slave | Yes | |
● to DP, master | Yes | |
● to DP, slave | Yes | |
● in AS, master | Yes | |
● in AS, slave | Yes | |
Time difference in system when synchronizing via | ||
● MPI, max. | 200 ms | |
Interfaces | ||
Number of RS 485 interfaces | 2 | |
Number of other interfaces | 0 | |
1. Interface | ||
Interface type | Integrated | |
Physics | RS 485 / PROFIBUS + MPI | |
Isolated | Yes | |
Power supply to interface (15 to 30 V DC), max. | 150 mA | |
Number of connection resources | MPI: 44, DP: 32 | |
Functionality | ||
● MPI | Yes | |
● PROFIBUS DP master | Yes | |
● PROFIBUS DP slave | No | |
MPI | ||
● Number of connections | 44 | |
● Transmission rate, max. | 12 Mbit/s | |
Services | ||
— PG/OP communication | Yes | |
— Routing | Yes | |
— Global data communication | No | |
— S7 basic communication | No | |
— S7 communication | Yes | |
— S7 communication, as client | Yes | |
— S7 communication, as server | Yes | |
DP master | ||
● Number of connections, max. | 32 | |
● Transmission rate, max. | 12 Mbit/s | |
● Number of DP slaves, max. | 32 | |
Services | ||
— PG/OP communication | Yes | |
— Routing | Yes | |
— Global data communication | No | |
— S7 basic communication | No | |
— S7 communication | Yes | |
— S7 communication, as client | Yes | |
— S7 communication, as server | Yes | |
— Equidistance | No | |
— SYNC/FREEZE | No | |
— Activation/deactivation of DP slaves | No | |
— Direct data exchange (slave-to-slave communication) | No | |
Address area | ||
— Inputs, max. | 2 kbyte | |
— Outputs, max. | 2 kbyte | |
User data per DP slave | ||
— User data per DP slave, max. | 244 byte | |
— Inputs, max. | 244 byte | |
— Outputs, max. | 244 byte | |
— Slots, max. | 244 | |
— per slot, max. | 128 byte | |
2. Interface | ||
Interface type | Integrated | |
Physics | RS 485 / PROFIBUS + MPI | |
Isolated | Yes | |
Power supply to interface (15 to 30 V DC), max. | 150 mA | |
Number of connection resources | 32 | |
Functionality | ||
● PROFIBUS DP master | Yes | |
● PROFIBUS DP slave | No | |
DP master | ||
● Number of connections, max. | 32 | |
● Transmission rate, max. | 12 Mbit/s | |
● Number of DP slaves, max. | 125 | |
Services | ||
— PG/OP communication | Yes | |
— Routing | Yes | |
— Global data communication | No | |
— S7 basic communication | No | |
— S7 communication | Yes | |
— Equidistance | No | |
— SYNC/FREEZE | No | |
— Direct data exchange (slave-to-slave communication) | No | |
Address area | ||
— Inputs, max. | 8 kbyte | |
— Outputs, max. | 8 kbyte | |
User data per DP slave | ||
— User data per DP slave, max. | 244 byte | |
— Inputs, max. | 244 byte | |
— Outputs, max. | 244 byte | |
— Slots, max. | 244 | |
— per slot, max. | 128 byte | |
3. Interface | ||
Interface type | Pluggable synchronization submodule (FO) | |
Plug-in interface modules | Synchronization submodule IF 960 6ES7 960-1AA04-0XA0 or 6ES7 960-1AB04-0XA0 | |
4. Interface | ||
Interface type | Pluggable synchronization submodule (FO) | |
Plug-in interface modules | Synchronization submodule IF 960 6ES7 960-1AA04-0XA0 or 6ES7 960-1AB04-0XA0 | |
Communication functions | ||
PG/OP communication | Yes | |
● Number of connectable OPs without message processing | 63 | |
● Number of connectable OPs with message processing | 16 | |
Global data communication | ||
● supported | No | |
S7 basic communication | ||
● supported | No | |
S7 communication | ||
● supported | Yes | |
● as server | Yes | |
● as client | Yes | |
● User data per job, max. | 64 kbyte | |
● User data per job (of which consistent), max. | 462 byte; 1 variable | |
S5 compatible communication | ||
● supported | Yes; (via CP max. 10 and FC AG_SEND and FC AG_RECV) | |
● User data per job, max. | 8 kbyte | |
● User data per job (of which consistent), max. | 240 byte | |
● Number of simultaneous AG-SEND/AG-RECV orders per CPU, max. | 64/64 | |
Standard communication (FMS) | ||
● supported | Yes; Via CP and loadable FB | |
Number of connections | ||
● overall | 64 | |
● usable for PG communication | ||
— reserved for PG communication | 1 | |
— adjustable for PG communication, max. | 0 | |
● usable for OP communication | ||
— reserved for OP communication | 1 | |
— adjustable for OP communication, max. | 0 | |
● usable for S7 basic communication | ||
— reserved for S7 basic communication | 0 | |
— adjustable for S7 basic communication, max. | 0 | |
● usable for S7 communication | ||
— reserved for S7 communication | 0 | |
— adjustable for S7 communication, max. | 0 | |
● usable for routing | 0 | |
— reserved for routing | 0 | |
— adjustable for routing, max. | 0 | |
S7 message functions | ||
Number of login stations for message functions, max. | 16 | |
Symbol-related messages | No | |
Block related messages | Yes | |
simultaneously active Alarm-S blocks, max. | 200 | |
Alarm 8-blocks | Yes | |
● Number of instances for alarm 8 and S7 communication blocks, max. | 10 000 | |
● preset, max. | 1 200 | |
Process control messages | Yes | |
Number of archives that can log on simultaneously (SFB 37 AR_SEND) | 64 | |
Test commissioning functions | ||
Status block | Yes | |
Single step | Yes | |
Number of breakpoints | 4 | |
Status/control | ||
● Status/control variable | Yes | |
● Variables | Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters | |
● Number of variables, max. | 70 | |
Forcing | ||
● Forcing | Yes | |
● Forcing, variables | Inputs/outputs, bit memories, distributed I/Os | |
● Number of variables, max. | 512 | |
Diagnostic buffer | ||
● present | Yes | |
● Number of entries, max. | 3 200 | |
— adjustable | Yes | |
— preset | 120 | |
Configuration | ||
Configuration software | ||
● STEP 7 | Yes | |
Programming | ||
● Command set | see instruction list | |
● Nesting levels | 8 | |
● Access to consistent data in process image | Yes | |
● System functions (SFC) | see instruction list | |
● System function blocks (SFB) | see instruction list | |
Programming language | ||
— LAD | Yes | |
— FBD | Yes | |
— STL | Yes | |
— SCL | Yes | |
— CFC | Yes | |
— GRAPH | Yes | |
— HiGraph® | Yes | |
Number of simultaneously active SFCs | ||
— RD_REC | 8 | |
— WR_REC | 8 | |
— WR_PARM | 8 | |
— PARM_MOD | 1 | |
— WR_DPARM | 2 | |
— DPNRM_DG | 8 | |
— RDSYSST | 8 | |
— DP_TOPOL | 1 | |
Number of simultaneously active SFBs | ||
— RDREC | 8 | |
— WRREC | 8 | |
Know-how protection | ||
● User program protection/password protection | Yes | |
Dimensions | ||
Width | 50 mm | |
Height | 290 mm | |
Depth | 219 mm | |
Weights | ||
Weight, approx. | 995 g |