MOBILE PANEL 177 PN

SIEMENS SIMATIC MOBILE PANEL 177 PN W 6AV6645-0BC01-0AX0

Country of origin : Germany
MOBILE PANEL 177 PN
SIMATIC MOBILE PANEL 177 PN W. INTEGRATED ENABLING BUTTON, STOP BUTTON, HANDWHEEL, KEY SWITCH AND ILLUMINATED PUSHBUTTON UNIT, CONFIGURABLE W. WINCC FLEXIBLE COMPACT VERSION 2005 AND HIGHER OR TIA PORTAL V11 AND HIGHER

6AV6645-0BC01-0AX0

Display
Design of displaySTN
Screen diagonal5.7 in
Number of colors256
Color typeColors
Resolution (pixels)
● Horizontal image resolution320 Pixel
● Vertical image resolution240 Pixel
Backlighting
● MTBF backlighting (at 25 °C)50 000 h
● Backlight dimmableNo
Control elements
Control elementsKeys and touch
Keyboard fonts
● Membrane keyboard
— user-definable label membrane keysYes
● Function keys
— Number of function keys14
— Number of function keys with LEDs8
● Keys with LEDYes; 8 with LED
● System keysYes
● Numeric/alphabetical inputYes / Yes
— hexadecimal keyboardYes
● Multi-key operationYes
— Number of multi-key operations2
Touch operation
● Design as touch screenYes; analog, resistive
Special operator controls
● Stop buttonYes
● Acknowledgement buttonYes
● Key-operated switchYes
● Illuminated pushbuttonYes
● HandwheelYes
Supply voltage
Design of the power supplyvia connection box
Type of supply voltageDC
Processor
Processor typeRISC 32-bit, 200 MHz
Drives
Diskette driveNo
CD-ROMNo
Hard diskNo
Memory
Type of memoryFlash / RAM
Memory available for user data2 048 kbyte
Type of output
Info LEDNo
Power LEDNo
Error LEDNo
Interfaces
Interfaces/bus type1 x RS485, 1 x Ethernet (RJ45)
Number of RS 485 interfaces1
● Transmission rate, max.0 Mbit/s
Number of USB interfaces0
Number of parallel interfaces0
Number of wireless interfaces0
PC card slotNo
CF card slotNo
Multimedia card/SD card slotcombined
Special interfaces1 x special interfaces
Industrial Ethernet
● Industrial Ethernet interface1 x Ethernet (RJ45)
● Industrial Ethernet status LED0
Protocols
PROFINETYes
Supports protocol for PROFINET IOYes
PROFIsafeNo
PROFIBUSNo
AS-InterfaceNo
Protocols (Ethernet)
● TCP/IPYes
Further protocols
● CANNo
● Data-HighwayNo
● DeviceNetNo
● INTERBUSNo
● Local Operating NetworkNo
● MODBUSYes
● SUCOnetNo
● other bus systemsYes
Degree and class of protection
Degree of protection acc. to EN 60529IP65
Standards, approvals, certificates
CertificationsCE, cULus, C-TICK, SIBE
CE markYes
cULusYes
RCM (formerly C-TICK)Yes
Suitable for safety functionsYes
Highest safety class achievable in safety mode
● Performance level according to ISO 13849-1d
Use in hazardous areas
● cULus Class I Zone 2, Division 2No
● FM Class I Division 2No
Ambient conditions
Free fall
● Fall height, max.1.5 m
Ambient temperature during operation
● min.0 °C
● max.40 °C
Ambient temperature during storage/transportation
● min.-20 °C
● max.60 °C
Relative humidity
● Operation, max.80 %
Operating systems
pre-installed operating systemWindows CE
Configuration
Message indicatorYes
Alarm system (incl. buffer and acknowledgment)Yes
Process value display (output)Yes
Process value default (input) possibleYes
Recipe managementYes
Configuration software
● WinCC flexible CompactYes
● WinCC flexible StandardYes
● WinCC flexible AdvancedYes
● WinCC Basic (TIA Portal)No
● WinCC Comfort (TIA Portal)Yes
● WinCC Advanced (TIA Portal)Yes
● WinCC Professional (TIA Portal)Yes
● Configuration toolWinCC flexible Compact Version 2005 or higher (to be ordered separately)
● 2. Configuration kitWinCC flexible Compact
— VersionVersion 2005
— Configuration toolWinCC flexible
— TypeCompact
Languages
Online languages
● Number of online/runtime languages5
Project languages
● Languages per project32
Functionality under WinCC (TIA Portal)
LibrariesYes
Applications/options[email protected]ervice, [email protected]
● Pocket WordNo
● Pocket ExcelNo
● PDF ViewerNo
● Media PlayerNo
● SIMATIC WinCC [email protected]Yes
● SIMATIC WinCC AuditNo
● Connection point identificationYes
Number of Visual Basic ScriptsNo
● Debugging in the simulatorNo
Task plannerYes
Help systemYes
● Number of characters per info text70
Message system
● Number of alarm classes32
● Number of messages2 000
● Bit messagesYes
— Number of bit messages2 000
● Analog messagesYes
— Number of analog messages50
● Telegram message procedure Alarm SNo
● System messages HMIYes
● System messages PLCNo
● System messages, other (SIMATIC S7, Sinumerik, Simotion, etc.)No
● Lines1
● Number of characters per message80
● Number of process values per message8
● Message indicatorYes
● acoustic feedbackNo
● First/last valueYes
Recipe management
● Number of recipes100
● Data records per recipe200
● Entries per data record200
● Recipe memory32 KB integrated Flash, expandable
Variables
● Number of variables per device1 024
● Number of variables per screen50
● Limit valuesYes
● MultiplexingYes
● StructuresYes
Images
● Number of configurable images500
● Permanent window/defaultYes
● Start screen configurableYes
● Image selection by PLCYes
● Image number in the PLCYes
Image objects
● Text objects2,500 text elements
● Number of I/O fields per image50
● Index of screen contextNo
● ReturnYes
● Graphics objectBit maps, vector graphics
Complex image objects
● Status/controlYes; With SIMATIC S7
● dynamic objectsDiagrams, bar graphs, sliders, invisible buttons
● MethodsTrend / profile
● Bar graphs
— Number of bars per chart5
● Limit value linesYes
● Number of visible switches per project1 000
Attributes for dynamic objects
● Color changeYes
● X/Y movementYes
● HideYes
● Angle of rotationNo
Lists
● Number of text lists per project300
● Number of entries per text list30
● Number of graphics lists per project100
Archiving
● Number of archives per device0
● Message archiveNo
● Process value archiveNo
● Archiving methods
— Sequential archiveNo
— Short-term archiveNo
● Memory location
— PC cardNo
— CF cardNo
— USB memoryNo
— EthernetNo
● Data storage format
— CSVNo
— TXTNo
● Online evaluation
— using trend curvesNo
Security
● Number of user groups50
● Number of user rights32
● Password export/importYes
Data carrier support
● PC cardNo
● CF cardNo
● Diskette driveNo
● Hard diskNo
Transfer (upload/download)
● Transfer of configurationSerial, Ethernet, automatic transfer recognition
Process coupling
● Connection to controllerS7-200, S7- 300/400, Win AC, PC (TCP/IP), SIMOTION, Modicon (Modbus), see the chapter “System interfaces”
● S7-1200Yes; with restrictions
● S7-1500Yes; with restrictions
● S7-200Yes
— PPI (point-to-point)No
— PPI networkNo
— MPINo
— PROFIBUS DPNo
— EthernetYes
● S7-300/400Yes
— MPINo
— PROFIBUS DPNo
— PROFINETYes
● LOGO!No
● SINUMERIKYes
● SIMOTIONYes
● S5No
— serialNo
— PROFIBUS DPNo
● TI 505No
● Allen Bradley (EtherNet/IP)Yes
● Allen Bradley (DF1)No
● Allen Bradley (DF485)No
● Mitsubishi (MC TCP/IP)Yes
● Mitsubishi (FX)No
● Mitsubishi (MP4)No
● Telemecanique (ADJUST)No
● Telemecanique (Uni-Telway)No
● OMRON (FINS TCP)No
● OMRON (LINK/Multilink)No
● Modicon (Modbus TCP/IP)Yes
● Modicon (Modbus)No
● GE-Fanuc (SNP)No
Functions
● Key repeatNo
● TAB sequenceYes
● Calculating functionsYes
● AnimateYes
● Menu tree editorNo
● Unit switchoverNo
Service tools/configuration aids
● Clean screenNo
● Touch calibrationYes
● Backup/Restore manuallyYes
● SimulationYes
● Device switchoverYes
● Delta transferYes
● Monitoring function for battery and memoryYes
● Trace (operation archive)No
Expandability/openness
● Open Platform ProgramYes
Peripherals/Options
PeripheralsPrinter
● PrinterYes
● SIMATIC HMI MM memory card: Multi Media CardYes
● SIMATIC HMI SD memory card: Secure Digital memory cardNo
● USB memoryNo
Mechanics/material
Enclosure material (front)plastic
Dimensions
Enclosure diameter245 mm
Depth of housing58 mm
Weights
Weight (without packaging)1.3 kg