■ STANDARD SPFCIFICATIONS
Measuring Range Limits: Temperature: -25C to 500C (-13 to 932F). Gauge pressure: Full vacuum to 42 MPa {420 kgf/ cm2}. Absolute pressure: 0 to 241 kPa {1800mmHg} absolute.
Measuring Elements: Refer to page 3 and 4.
Output Signal: 20 to 100 kPa, 0.2 to 1.0 kgf/cm2 or bar, or 3 to 15 psi, whichever specified.
Output Gauge: 0 to 200 kPa, 0 to 2 kgf/cm2 or bar, or 0 to 30 psi.
Air Supply: 140 kPa, 1.4 kgf/cm2 or bar, or 20 psi, whichever specified.
Air Consumption: 0.5 m3/h at 0C, 101.3 kPa {1.033 kgf/cm2} absolute (0.3 scfm).
Control Modes: On-off, proportional (P), proportional plus derivative (P+D), proportional plus integral (P+I), proportional plus integral plus derivative (P+I+D), differential gap, batch plus proportional plus integral (BATCH+P+I). Proportional band: 4 to 400%, direct or reverse. Integral time: 0.01 to 50 minutes. Derivative time: 0.05 to 50 minutes. Differential gap: 2 to 100%.
Indicating and Setting Scale: Effective nominal length 156 mm (6 inches). Black divisions and letters on white background.
Indicator Accuracy: Temperature T1A, T3B elements: 0.5% span or 0.3C, whichever is greater. Pressure P21, 22, 31, PR1, P42, 51, 52 elements: 0.5% span. Pressure P32, 72 elements: 0.75% span.
Pointers: Fluorescent red.
Set Point: Local (manual) set, standard. Remote (pneumatic) set, optional. In local set version internal set point knob is accessible by opening hinged door.
Door and Case: Aluminum alloy, finished with polyurethane paint. Light grayish green (Munsell 2.5GY5.0/1.0).
Degrees of Protection: IP53, NEMA 3. Operating Temperature Range: -30 to +80C ( -20 to +180F). Mounting: Surface, flush panel and 2-inch pipe.
Connections: In bottom of case. Air: Tapped for JIS R1/4 or 1/4 NPT male.
Pressure and vacuum: JIS Rc1/4 or 1/4 NPT female up to 140 kgf/cm2 or bar, 14 MPa, 2000 psi. JIS R1/2 or 1/2 NPT male up to 420 kgf/cm2 or bar, 42 MPa, 6000 psi.
Approximate Weight: 7.6 kg (17 lb) . . .MC43-A5C-N*A (excluding elements and bracket).